King Pigeon M T Series User manual

Page 2of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
Modbus TCP Ethernet Remote I/O Module Model List
Model
Descriptions
DC Output
DC Input
Typical Power
Consumption
M100T
1 RJ45,1 RS485, 2 DI, 2 AI, 2 DO
1 DC
9~36VDC
160mA@12V
M110T
1 RJ45,1 RS485, 4 DI, 4 DO
1 DC
M120T
1 RJ45,1 RS485, 4 DI, 4 AI, 2AO(0-10V), 4 DO
1 DC
24~36VDC
90mA@24V
M130T
1 RJ45,1 RS485, 8 DI, 4 DO
1 DC
9~36VDC
150mA@12V
M140T
1 RJ45,1 RS485, 8 DI, 8 DO
1 DC
M150T
1 RJ45,1 RS485, 8 DI, 4 AI, 4 DO
1 DC
M160T
1 RJ45,1 RS485, 8 DI, 8 AI, 8 DO
1 DC
M200T
1 RJ45,1 RS485, 2AO(0-10V)
1 DC
24~36VDC
90mA@24V
M210T
1 RJ45,1 RS485, 4 DI
1 DC
9~36VDC
160mA@12V
M220T
1 RJ45,1 RS485, 4 DO
1 DC
160mA@12V
M230T
1 RJ45,1 RS485, 4 AI
1 DC
160mA@12V
M240T
1 RJ45,1 RS485, 4 RTD, 2/3 wire PT100/PT1000
1 DC
100mA@12V
M310T
1 RJ45,1 RS485, 8 DI
1 DC
150mA@12V
M320T
1 RJ45,1 RS485, 8 DO
1 DC
M330T
1 RJ45,1 RS485, 8 AI
1 DC
M340T
1 RJ45,1 RS485, 8 RTD, 2/3 wire PT100/PT1000
1 DC
100mA@12V
M410T
1 RJ45,1 RS485, 16 DI
1 DC
160mA@12V
M420T
1 RJ45,1 RS485, 16 DO
1 DC
110mA@12V
Special instructions for ordering:
1) If the model provides digital input, the DIN default type: wet contact, optional: dry contact. The input type
cannot be changed after manufacturer delivered. The DIN1 default is high-speed count mode; it can be
changed to low-speed count mode by open the shell and change the internal jumper. If require dry contact
input, please note when ordering, if DIN1 require high-speed pulse count mode then must be wet contact.
2) If the model provides digital output, the DO type is SINK, DO1 supports high-speed pulse output; DO2 can be
used to control the direction of the stepper motor. DO default is sink,can control ≤24V DC ≤0.5A relay
directly ,otherwise must connect external relay.
3) The model number: M240T, M340T support thermal resistance temperature transmitter default type: PT100,
optional: PT1000, if you need PT1000 type of thermal resistance, please note when ordering.
4) All models support the register mapping, can extend I/O or meters via Modbus RTU protocol.
5) Each model’s I/O port qty is referred to the above table only. As MXXT series use same housing, those I/O
port hardware terminal blocks on the device which not described in the table is not valid.

Page 3of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
Table of Contents
【UPGRADE HISTORY】...........................................................................................................................................................4
1. Brief introduction.................................................................................................................................................................4
2.Standard Packing List............................................................................................................................................................ 5
3. Mainly Features....................................................................................................................................................................6
4. Technical Specifications....................................................................................................................................................... 6
5. Physical Layout and Installation Diagram............................................................................................................................ 9
5.1 Physical Layout....................................................................................................................................................... 9
5.2 Led Instruction...................................................................................................................................................... 10
5.3 Interface Instructions for installation................................................................................................................... 10
5.4 RTD/AI/AO............................................................................................................................................................. 15
RS485...................................................................................................................................................................19
5.5 Setup the DIN1 High Speed Pulse Count & Low Speed Pulse Count Mode:.............................................................20
6. Initialize/Reset the Module................................................................................................................................................21
7. Settings&Operation........................................................................................................................................................... 21
7.1 Ready to Set up:....................................................................................................................................................21
7.2 Selection Description................................................................................................................................................22
7.3 Basic Setting......................................................................................................................................................... 23
7.4 Network Settings.................................................................................................................................................. 24
7.5 Slave Settings........................................................................................................................................................25
7.6 Register list........................................................................................................................................................... 27
7.7 System Log............................................................................................................................................................ 29
8. Modbus Protocol................................................................................................................................................................30
8.1Introduction to Modbus Register Address............................................................................................................... 30
8.1.1 Read Input Coil (Function Code 2: Read Coil)............................................................................................... 30
8.1.2 Read and Write Holding Coil........................................................................................................................ 31
8.1.3 Read Input Register...................................................................................................................................... 32
8.1.4 Read and Write Holding Register......................................................................................................................... 34
8.1.5 Mapping Register----Transit BIT Register Address....................................................................................... 36
8.1.6 Mapping Register----Transit 16-Bit Register Address.................................................................................. 36
8.2Example of reading and writing registers.................................................................................................................36
8.2.1 Read the input coil of this device.................................................................................................................36
8.2.2 Read this device holding coil........................................................................................................................37
8.2.3 Write device holding coil..............................................................................................................................39
8.2.4 Read native input register............................................................................................................................ 41
8.2.5 Read local holding register...........................................................................................................................42
8.2.6 Control the local holding register.................................................................................................................44
8.3Read device map register......................................................................................................................................... 46
8.3.1Read Bit mapping address data46
8.3.2Rewrite the bit mapping address data..........................................................................................................47
8.3.3Read 16-bit mapped address data................................................................................................................ 48
8.3.4Write 16-bit mapped address data............................................................................................................... 49
9. Warranty............................................................................................................................................................................ 50
10.Appendix Application of MQTT......................................................................................................................................52

Page 4of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
【UPGRADE HISTORY】
1. Brief introduction
The MxxxT Ethernet Remote I/O Module is an industrial class, isolated designed, high reliability, high stability and
high precision data acquisition module, embedded 32-Bit High Performance Microprocessor MCU, Integrated 1
Industrial 10/100M adaptive Ethernet module inside. It provides multi I/O, supports standard Modbus TCP,
supports modbus master and slave, can be integrated into SCADA, OPC server, and other automation systems. It is
design for working in the harsh industrial application environment, widely used in a variety of industrial
automation, security monitoring system, automatically measurement and control system.
The MxxxT Ethernet Remote I/O module provides a RS485 interface, through the RS485 bus, it can cascade
Modbus I/O devices or Modbus meters, e.g.: a variety of digital input or digital outputs, analog inputs or outputs,
thermal resistance IO module combination, save costs. At the same time, the Ethernet Remote I/O module has
register mapping function, the cascade Modbus I/O data are automatically collected to the register mapping area,
the TCP Client polling without waiting then can get a quick response to meet the industrial timely requirements.
The MxxxT Ethernet Remote I/O module provides different I/O ports for variety applications. Includes
optical-isolated digital inputs, compatibles dry contact and wet contact, supports max 700KHz high speed pulse
counter, digital outputs supports 10Hz~300Khz high speed pulse output or relay outputs, isolated 12bits analog
inputs, supports 0~5V, 0~10V, 4~20mA, 0~20mA analog signal, 12bits analog outputs, supports 0~10VDC signal
DATE
FIRMWARE VERSION
HARDWARE VERSION
DESCRIPTION
2017-04-17
V1.0
2019-11-18
V2.0
V2.0
2020-11-08
V2.3
V3.1
1. Add DIN2~DIN12 pulse counting function
2. Add Modbus protocol example
3. Add MQTT protocol
4. Modify some errors
This user manual has been designed as a guide to the installation and operation of MxxT Ethernet Remote I/O Module.
Statements contained in the manual are general guidelines only and in no way are designed to supersede the
instructions contained with other products.
We recommend the advice of a registered electrician before any Installation work.
King Pigeon Hi-Tech.Co., Ltd, its employees and distributors, accept no liability for any loss or damage including
consequential damage due to reliance on any material contained in this manual.
King Pigeon Hi-Tech.Co., Ltd, its employees and distributors, accept no liability for any Network upgrading or due to
the technology specifications contained in this manual.

Page 5of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
output, resistance thermal detector inputs compatibles 2/3 wires PT100 and PT1000. All of the I/O ports are high
sampling frequency and special filtering strategy to ensure its reliability.
The MxxxT Ethernet Remote I/O module can work at wide working voltage range, the range is 12 ~ 36VDC with
anti-reverse protection design. Also, it provides 1channel 12~36VDC power output for external device to save
wiring cost.
2.Standard Packing List
Ethernet Remote I/O Module X 1, Card type Manual X 1, 35mm Standard DIN rail fixed Bracket*1.
Note: The package does not include AC/DC Adaptor.

Page 6of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
3. Mainly Features
Standard Modbus TCP protocol and Modbus RTU over TCP communication protocol and MQTT protocol;
Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog;
Power supply 9~36V DC with over voltage and phase-reversal protection;
Management and configuration via LAN connection configuration software for easy operation and
maintenance;
Integrated 10/100M adaptive Ethernet port, With 15KV ESD protection;
Optical isolated digital input(Compatible Dry or Wet type), supports max 700KHz high speed pulse counter;
Support DIN2~DIN12 as a low-speed pulse counter. The anti-jitter time can be set to 1~2000ms, the default is
1ms, and the corresponding pulse frequency is up to 1KHz;
DO supports Sink output,DO1 can be used as high-speed pulse output, supports 10Hz~300KHz ;
Isolated analog input, 12-bit resolution, supports 0~20mA,4~20mA,0-5VDC, 0-10VDC;
Analog output, 12-bit resolution, supports 0-10VDC;
RTD input, supports PT100 and PT1000 resistance sensor, compatible 2 or 3 wires;
High sampling frequency and special filtering strategy to ensure reliability;
1 RS485 Serial port, supports Modbus RTU Master/Slave, can extend I/O modules;
Supports register mapping function and extend I/O inquiry strategy;
Supports TCP Client and TCP Server, supports max. 5 TCP Client connections;
Provides 1 channel VDC power source output for external device, saving wiring cost;
LED instructions work status, with reset button to reset, easy on-site installation and commissioning;
Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for
industrial applications in the field;
Small size, L82 * W40 * H99mm, compatible wall installation and DIN35mm industrial rail installation.
4. Technical Specifications
• Digital Input
Type
Wet Contact (NPN or PNP), Dry Contact. Default wet contact, if need dry
contact ,pleases tell us when order
I/O Mode
DI or Pulse Counter
Dry Contact
• On: short to GND, logic=1
• Off: open, logic=0
Wet Contact (DI to COM)
• On: 10 to 30 VDC,logic=1
• Off: 0 to 3 VDC,logic=0
Pulse Counter Frequency
Only the 1st Channel can be used as pulse counter, Compatibles DI and
counter simultaneously. Counter value will save if power off.

Page 7of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
High Speed Mode: Max. 700Khz(Default);
Low Speed Mode: Max. 10KHz (Optional, can open the cover to choose
low speed mode.);Support DIN2~DIN12 as the low-speed pulse counter:
the anti-shake time can be set from 1 to 2000ms, the default is 1ms, and
the corresponding pulse frequency is up to 1KHz.
Digital sampling frequency
500Hz,3 times ACK
Digital filtering strategy
Support Anti-Shake Mechanism
Isolation
Optical Isolated,3k VDC or 2kVrms
• Digital Output
Type
Sink or pulse (default is sink, can control ≤24V DC ≤0.5A relay
directly ,otherwise must connect external relay)
I/O Mode
Sink or Pulse Output
Pulse Output Frequency
10Hz~300KHz(Only the 1st Channel is Sink type can be used as high speed
pulse output)
Over-Voltage Protection
50V DC
Over-Temperature Shutdown
175°C (typical), 150°C (min.)
Load Current
Max.500 mA per channel
Digital sampling frequency
500Hz
• Analog Input
Type
mA/V
Resolution
12 bits
input impedance
Voltage type: >1M ohms
Current type: 162 ohms
Input Range
0~5VDC , 0~10VDC, 0~20 mA, 4~20mA,
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
Sampling frequency
20Hz
• RTD Input
Sensor Type
PT100 or PT1000(default PT100,If need PT1000,please tell us when order)
Measurement Range
-50 ~ +300℃
Resolution
0.1°C or 0.1 ohm
Input Connection
2 or 3-wire
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75 ℃
Sampling frequency
20Hz
• Analog Output
Type
0-10V DC

Page 8of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
Resolution
12 bits
Output Range
0 to 10 VDC
Load Current
1A (max.)
Accuracy
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
• Working Power Requirements
Input Voltage
9~36VDC for no-AO output model,
24~36VDC for AO output model;
Peak Voltage:+40VDC, Power consumption: Less than 2W,
• LAN
Ethernet
10/100 Mbps adaptive Ethernet module, RJ45 ports
Protection
15KV ESD Protection
Protocols
Modbus TCP Master or Slave, TCP/IP
TCP Connection
Can be TCP client and server. As TCP server, support max 5 TCP client
connection
• Serial Port
RS485
MODBUS RTU Master or Slave.
Protection
15KV ESD Protection
Modbus Slave address
1~247
Polling Frequency
Default is 50mS,range:30-65535mS
Baud Rate
2400,4800,9600,19200,38400,57600,115200,128000Bps;
Mapping registers
Bit registers: 300, 16-Bit register: 300. Total 600 mapping registers.
• Physical Characteristics
Wiring
I/O cable max. 14 AWG
Dimensions
82x 40 x 99 mm
Weight
300 g
Mounting
DIN rail or wall-mounted
• Environmental Limits
Operating Temperature
Standard Models: -20 to 70°C (-4 to 158°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)

Page 9of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
5. Physical Layout and Installation Diagram
5.1 Physical Layout
35mm Standard DIN rail fixed Bracket:

Page 10 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
5.2 Led Instruction
LED Indicator Instruction
Power Indicator: Power on the device,PWR will always on.
Link Indicator: MODBUS TCP connection successful will always on.
RS485 Indicator: Flicks while receiving data on RS485 Serial port.
RS485 Indicator: Flicks while sending data on RS485 Serial port.
Digital input status indicator, turn on or input high level, or will close.
Digital Output status indicator, turn on or output high level, or will close.
5.3 Interface Instructions for installation
See below interface definition, please connect the correct wires.
Interface Definition Instruction
DC in 9~36V
+
DC9~36V positive input, 1A, for power on the Unit. If need to use the AO port,
then please power on it by DC24~36v.
–
DC9~36V negative input.
DC Out 9~36V
+
DC Power output positive for external device, output voltage= input voltage.

Page 11 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
GND
DC Power output negative external device, output voltage= input voltage
Reset
Reset button. Recovery the parameters to factory default value.
ETHERNET
Ethernet port.
RS485
A
RS485 data A
B
RS485 data B
GND
RS485 data ground if required.
Digital Input
DINx+
The x channel digital input positive
GND
Digital input negative
Digital Output
DOx+
The x channel Digital Output High Level or Relay NO port.
GND
Sink output: GND (For output type is SINK.)
COM
Relay output: COM.(For output type is Relay)
Analog Input
AINx+
The x channel Analog input positive.
GND
Analog input negative.
Analog Output
AOx+
The x channel Analog output positive.
GND
Analog output negative.
RTD Input
RTDx+
The x channel Resistance Thermal input positive.
RTDx -
Resistance Thermal input negative.
COM
Resistance Thermal input COM port.
5.4 Typically Wiring Instruction:
Safety ground
The grounding wire helps prevent the effects of electromagnetic interference. Before connecting the device, ground the
device through the ground screw connection.
Note: The product should be installed on the surface of a well-grounded device, such as a metal plate
DI&DO
Digital input (DI) supports up to 16 channels, with dry contact/wet contact type optional, and the default type is wet
contact.Digital output (DO) supports up to 16 channels and supports sink type.

Page 12 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
DI Internal interface principle block diagram
DI&DO
DIN1~DIN
16
1~16 digital input
COM
Digital input common
DO1~DO1
6
1~16 digital (sink) output
COM
Digital output common

Page 13 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
DI Wiring (dry contact)
DI Wiring (NPN sensor)
DI wiring (PNP sensor)

Page 14 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
DO Internal interface principle block diagram

Page 15 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
DO wiring (sink)
5.4 RTD/AI/AO
The top terminal pins are multiplexed functions, and the specific function definitions are determined
according to the model selection table.
Tips:
Resistance Thermal Detector (RTD) compatibles 2-wire or 3-wire, please reference above mentioned wiring instruction. If
the sensor near the module and the wire resistance is small can be ignored, can be used 2-wire wiring, if the distance is far
and the wire resistance affect the value, should be used 3-wire way connection.
RTD/AI/AO
PT1+ ~ PT8+
1st ~ 8th PT100/PT1000 input positive
PT1- ~ PT8-
1st ~ 8th PT100/PT1000 input negative
GND
PT100/PT1000 input ground
AI1 ~ AI8
The 1st ~ 8th analog input positive
COM
The 1st ~ 8th analog quantity common terminal
AO1&AO2
1st & 2nd analog output positive
COM
1st & 2nd analog output common terminal

Page 16 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
RTD Block diagram of internal interface principle
RTD wiring (PT100)
AI Block diagram of internal interface principle
Analog input type selection
On the left side of the device, each AI input channel can choose the input type by itself. The three switches
include: 1, 4~20mA/0~20mA; 2, 0~5V; 3, 0~10V. The user needs to select the correct type according to
the output type of the transmitter. When selecting, please turn the switch to the corresponding position,

Page 17 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
and at the same time, select the corresponding type on the configuration software. The labels are as
follows:
AI wiring (2 wire)
AI Wiring (3 wire)

Page 18 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
AO Block diagram of internal interface principle
AO wiring

Page 19 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
RS485
RS485 Wiring
RS485
A
RS485 Data A
B
RS485 Data B
GND
RS485 Data Ground

Page 20 of 56 King Pigeon Hi-Tech. Co., Ltd. Ver 2.3
Industrial Ethernet Remote I/O Module
IoT Data Acquisition Module
Ethernet
5.5 Setup the DIN1 High Speed Pulse Count & Low Speed Pulse Count Mode:
The DIN1 can be used as pulse counter, default is high speed mode, the max. Frequency is 700Khz. it can be change
to low speed pulse count mode by open the shell, and change the JP2&JP3’s jump Caps to the right side2PINs, see
below pictures.
High speed mode:
Short-circuit the upside 2 pins of
JP2&JP3’s with Caps.
Low speed mode:
Short-circuit the downside 2 pins
of JP2&JP3’s with Caps.
Ethernet
Indicator light
Status
Description
Link indicator
(yellow)
Always bright
Connection established
Flashing
Transferring data
Lights off
Connection lost
Rate indicator
(green)
Always bright
100Mbps mode
Lights off
10Mbps mode
This manual suits for next models
18
Table of contents
Popular I/O System manuals by other brands

ST
ST ST7 Series user guide

Allen-Bradley
Allen-Bradley 1794-IM8 installation instructions

Bose
Bose ControlSpace ESP-88 installation instructions

M-system
M-system R7 Series instruction manual

Mitsubishi Electric
Mitsubishi Electric CL1XY2-DT1D5S user manual

GV international
GV international d1031q instruction manual