KIOUR ICE V3 User manual

1
ICE MACHINE TEMPERATURE CONTROLLER Model ICE V3
ATTENTION Firmware V3
Read carefully these instructions before installing and using this device and keep them for future reference. Attention to installation and electrical wiring. Use this
device only as described in this document and never use itself as a security device. The device must be disposed of in accordance with local standards for the collection
of electrical and electronic equipment.
DESCRIPTION
ICE is an ideal thermostat for sprinkling ice machine. It has two NTC/PTC sensors: one is for the evaporator temperature and the other is for the ice bucket in order to terminate
the production when the bucket is full. It has 3 indication digits of temperature display with an accuracy of 0.5°C and 4 buttons. Three relays (for compressor 30Α, water pump
10Α, and defrost 10Α) with NO contact, three adjustable timers in minutes for the control of the compressor/water pump and defrost relays, electrical or HOT-GAS defrost
mode, OFF mode for the device and an alarm buzzer for high or low temperature. The device is mounted on a panel hole 29x71mm and it is restrained with plastic side brackets.
For more indications regarding the alarms please see the alarm’s table at page 3.
DEVICE OPERATION WITH ELECTRIC DEFROST
During start-up, the defrost relay is activated and timer t2 starts counting. The screen displays t2 time duration, which counts backwards, while the indications and
turn on. If the evaporator temperature is lower than the set point after the defrost, all operations and relays will be deactivated automatically and the screen will
display the indication “ΕΕΕ”. The alarm is automatically deactivated after the restart of the device using the ON/OFF button or by toggling the power supply. Manual defrost
duration is based on timer t2 and does not end based on the defrost end temperature –parameter dE5.
When timer t2 elapses, the defrost relay is deactivated and timer t3 starts counting while the compressor and water pump relays are activated. The display
shows the current evaporator temperature and the indications ,T2 and light up. When the evaporator temperature reaches the set point, timer t1 begins counting,
while the compressor and water pump relay remain activated until timer t1 elapses. The display shows time duration of timer t1, which counts backwards, while the indications
, and light up. When timer t1 elapses, the compressor and water pump relays are deactivated, and afterwards the cycle starts again with the activation of defrost
relay, etc.
If a malfunction occurs in the cooling circuit and the evaporator temperature does not decrease, the aforesaid process will end based on timer t3. All functions and relays
will be deactivated automatically and alarm "FFF" will be displayed. The alarm is automatically OFF by restarting the thermostat from the power supply or the ON / OFF
button.
When the ice bucket temperature sensor reaches the SP2, the production will stop when the last production of ice drops on the bucket and the cycle ends. On screen the
indication “FUL” is displayed until the bucket temperature reaches SP2+dF2 and the cycle resumes.
The aforesaid cycle repeats continuously without interruption during the smooth operation of the thermostat.
In case of evaporator’s temperature sensor failure or OFF device state, all thermostat functions are deactivated.
In case of bucket temperature sensor failure, the cycle continues and does not stop because of this failure.
HOT-GAS OPERATION
Parameter do set the defrost function in electric or HOT-GAS mode. Only in hot-gas defrost mode (do = 1), the compressor relay works in parallel with the defrost relay, for
time t2.
1. Press and parameter SP2 is displayed.
2. Press and its value is displayed while the arrows
change its value.
3. Press to store the new value. Now the device is operating with the new value.
By pressing at the same time and , the device switches ON/OFF.
INDICATIONS AND BUTTONS FUNCTION
Display indications
compressor ΟΝ
water pump ΟΝ
defrost ON
dFr
manual defrost ΟΝ
timer ΟΝ
Τ2
evaporator temperature
ΤS
ice bucket temperature
alarm ΟΝ
malfunction ON
Keyboard
enter/exit the parameter’s menu
display the parameter’s value
enter parameter’s value
manual defrost
up arrow
display evaporator temperature
down arrow
mute buzzer
ON/OFF device (check below)
display ice bucket temperature
ADJUSTING THE ICE BUCKET SET POINT
SWITCHING ON / OFF THE DEVICE

2
By pressing for 3 seconds the , manual defrost starts and ends when timer t2 elapses.
PROGRAMMING A PARAMETER
ATTENTION: to gain full access to the parameter’s menu, the 5th parameter Cod must be adjusted to 22 (see parameter table page 2).
1. Press to enter the parameter menu.
2. Choose the parameter you want to adjust by pressing or and press to display its value.
3. Press or to change its value and then press to store the new value.
4. Press to exit the parameter menu.
Model ICE power supply : 230VAC 50/60Hz / Maximum power consumption: 3W.
It is recommended using a power supply safety fuse: 0.5Α(not included)
Evaporator and ice bucket temperature sensors NTC 10K 1% 25°C ΙΡ68 and temperature range -50÷+110°C (-58÷+230°F) (or PTC 1Κ 25oC with temperature range -50 ÷
+150°C (-58÷+302°F) not included) / Accuracy: ±0.5°C
Alarm buzzer
Compressor relay 30Αres. 250VAC normally open contact / Pump and defrost relays 10A res. 250VAC normally open contact / Max current load 16Α
Connections: cable cross section 2.5 mm² for all relays / cable cross section from 0.25 to 1.0 mm² for the sensors
Connections with terminal blocks 18A using cable with cable cross section up to 2.5 mm² / It is recommended using a torque wrench with maximum torque 0.4Nm
Operating temperature: -15÷+55°C / Storage temperature: -20÷+80°C
Dimensions 37x79x81mm / The device is mounted on panel hole 29x71mm and restrained with plastic side brackets / Protection IP65 front
Firmware: V3
ELECTRICAL DIAGRAM - DIMENSIONS
ATTENTION: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such
a way that it cannot be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power
supply of the device before proceeding to any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct
sunlight or rain. Prevent electrostatic discharges and sharp objects from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic
disorders. Signal cables must never be in the same pipe with the power supply cables. ATTENTION: Read carefully the technical specifications and make sure that the working
conditions are appropriate. According to safety standards, the device must be fastened in such a way that it cannot be removed without the use of tools.
Dimensions are in mm. The device is mounted on panel hole with cut 29x71mm and restrained with plastic side brackets.
PARAMETER TABLE
No
description
min
max
ICE
UOM
1
SΡ2
ice bucket SET POINT: temperature control of the ice bucket
-50
+150
1
°C/°F
2
SLo
minimum temperature limit of SPo
-50
SΗi
-20
°C/°F
3
SHi
maximum temperature limit of SPo
SLo
+150
8
°C/°F
4
dF2
differential of temperature sensor ice bucket SP2
1
+150
4
°C/°F
5
Cod
code to enter parameter’s menu Cod = 22
0
255
0
-
6
Cr
minimum pause time of the compressor
0
4
0
minutes
7
dE5
defrost’s end temperature: in case of evaporator’s sensor malfunction (LF1), defrost does not end based on
the dE5 parameter but when timer t2 elapses.
1
70
20
°C/°F
8
dt
(not used)
-
-
-
-
9
SPo
Evaporator SET POINT: temperature control of the evaporator
SLo
SΗi
-12
°C/°F
10
do
Derfrost Mode: electrical for do = 0 or hot-gas for do = 1 (the compressor relay works in parallel with the
defrost relay during the defrosting process)
0
1
0=electrical
-
11
dr
(not used)
-
-
-
-
12
SEN
Type of sensor NTC/PTC. 0 = PTC / 1 = NTC
0
1
0 = PTC
-
13
SE1
zero adjustment of evaporator temperature sensor
-9
+15
0
°C/°F
14
SE2
zero adjustment of ice bucket temperature sensor
-9
+15
0
°C/°F
15
tS
(not used)
-
-
-
-
16
FC
Switch between °C/°F (0=°C, 1=°F) ATTENTION: toggling between °C/°F does not change SPo
0
1
0=°C
°C/°F
17
t1
countdown timer where the compressor relay remains activated as long as the evaporator reaches the
desired set temperature
1
255
10
minutes
18
t2
countdown timre where the defrost relay remains ON
1
255
2
minutes
19
dHL
delay time until the activation of the alarm “AHi” and “ALo”
0
99
0
minutes
20
t3
maximum compressor operating time during the cooling process until it reaches the desired set point. At the
end of time t3, all functions and thermostat relays are deactivated and "FFF" indication is displayed. The
alarm is deactivated automatically by restarting the device
0
255
30
minutes
21
ΑLo
low evaporator temperature alarm
-50
+150
-30
°C/°F
22
ΑHi
high evaporator temperature alarm
-50
+150
+35
°C/°F
MANUAL DEFROST
TECHNICAL SPECIFICATIONS

3
ALARM TABLE
1
LF1
Evaporator temperature sensor failure. In this case all functions and relays are automatically deactivated.
2
LF2
Ice bucket temperature sensor failure where the cycle continues without any interruption
3
ΑLo
Low evaporator temperature alarm
4
ΑHi
High evaporator temperature alarm
5
FFF
Cooling failure. All functions and relays are deactivated automatically after the end of time t3.
The alarm is automatically deactivated by restarting the device.
6
EEE
Upon completion of the defrosting procedure, the evaporator temperature remains less than the SPo. All functions and relays are deactivated automatically.
The alarm is automatically deactivated by restarting the device.
7
FUL
The bucket is full with ice. The ice production stops until the bucket sensor reaches SP2+dF2 temperature.
8
EEr
Error in RAM memory: rewrite the first parameter SP2 (check page 1 –adjusting the Set Point)
The alarms LF1, LF2, ALo, AHi are deactivated automatically when the cause of their activation is no longer present
Made in Greece.
The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an
authorized technician. The guarantee covers only the replacement or the service of the device. KIOUR PC implements a Quality Management System according to EN ISO
9001:2015 Standard with registration number 01013192. KIOUR preserves the right to adjust its products without further notice.
392 Mesogeion Avenue Agia Paraskevi 153 41 Τ: 210 6533730 F: 210 6546331 [email protected] www.kiour.com
V3.0.0
Table of contents
Popular Thermostat manuals by other brands

Honeywell
Honeywell Tradeline T8611M installation instructions

Braeburn
Braeburn 2000 user manual

ICM Controls
ICM Controls SC 2001 Installation, operation & application guide

Honeywell Home
Honeywell Home T3 quick start guide

ICM Controls
ICM Controls SC 4811 Installation, operation & application guide

CPI
CPI inTouch manual