
The device or duct connection is via a surrounding 60 or
80 mm wide flange made of aluminium. Prior to installa-
tion, the components should be checked for significant
deficiencies (e.g. transport damage) and completeness,
and, where applicable, consultation with Klingenburg
GmbH concerning how best to proceed is advised. If
multiple humidifiers are delivered together, the data of the
type plates should be compared, to avoid mixing up as-
sembly units.
The humidifier must be installed on a level, horizontal sur-
face with the appropriate load-bearing capacity. With a
suspended assembly, only permissible fixing materials
may be used. The device must be oriented horizontally
on all sides.
The water drainage outlet of the CERTO must be connect-
ed with a suitable siphon ensuring compliance with appli-
cable regulations.
Subsequently, the water drainage must be checked by fill-
ing the inside of the humidifier with water. Once the unit
has been successfully connected to the air duct network
or device housing, no further correction is possible in the
event of any deviation from the horizontal position!
A uniform air flow should be supplied. The fitting of rectifi-
ers is only seldom required.
The water supply between the high-pressure side of the
pump and the nozzle holder/distributor of the Klingenburg
humidifier is connected via the 3 m long high-pressure
hose supplied.
Only qualified and authorized personnel are allowed to
work with the humidifier system.
Persons transporting or working on and with the system
must have read and understood the relevant parts of the
operating instructions and in particular the chapter
“Safety instructions”.
In addition, the operator must be informed by the operator
about possible dangers.
10
Assembly / Commissioning
Û
Installation
Û
Caution !
The maximum input pressure of the pump assembly must
not exceed 5 bar. Operating at any higher a pressure will
damage the pump.
Prior to installation, the oil level should be checked and
adjusted as required.
The individual steps are described in detail in the installa-
tion section.
Achtung !
The pump assembly may only be used with the corre-
sponding humidifier. The pump must be operated with the
corresponding controller. Non-compliance will invalidate
any guarantee claims.
Verbindungsleitungen
The control unit must be wired according to the on-site
circuit diagram.
Motor and sensor cables must be laid separately and
shielded.
The pump assembly is equipped with pressure controllers
(D1-D2) on both the low and high-pressure sides. These
must always be connected to the respective controller
connections.
The water supply between the on-site water pipe and the
pump station input is connected via the 3 m long 1/2”
low-pressure hose supplied. Other hose lengths of up to
10m are also available.
The on-site water supply pipe to the pump must be con-
nected to the device in either rising or falling fashion. Any
forms of connection allowing air pockets to form must al-
ways be avoided. The connection hoses must be properly
sealed.
For the installation of the droplet separator and the nozzle sys-
tem, please observe the installation instructions provided by Klin-
genburg and enclosed with the delivery of your humidifier.
Û
Pump
Û
Caution !
Û
Connecting cables
Attention !
The entire Klingenburg humidifier
should be protected from frost!
!!
Any other use that does not conform to the intended use
described above is not permitted.
Such use and changes to hardware and software will re-
sult in the loss of any warranty claims.
Improper use
!
Attention !
Û
Observance of the assembly instructions