!#"
"
the 3/8" line to the lower (liquid) fitting on the condenser, and to the "Refrigerant In" on the
ice maker. The 1/2" line connects to the upper (inlet) fitting on the condenser, and the
"Refrigerant Out" on the ice maker.
6. Each fitting on the line sets, condenser and ice maker is self-sealing, and should be
tightened 1/4 turn more than hand tight. Always use a backup wrench to prevent tubing twist
when tightening these fittings.
7. The condenser fan motor requires power supply provisions that comply with all
applicable code requirements. The Ice Maker is provided with wire connection pigtails that
include an L1 RED wire for connection to the fan motor circuit along with L2 and Grounding
conductors. CAUTION: For multiple-circuit installations fan power must be provided separately
by a circuit that will not be interrupted so that the fan motor will run continuously.
8. The refrigerant lines should be routed inside the building or otherwise mechanically
protected wherever possible.
AMPACITY
Minimum ampacity does not indicate typical running current value. Refer to equipment NAME
PLATE data. Use minimum ampacity value for sizing branch circuit conductors up to 25 feet
length. For conductor length over 25 feet up to 100 feet, increase 1 AWG size. Over 100 feet
requires 2 or more AWG size increase.
BRANCH CIRCUIT PROTECTION
Proper protection must be provided by either fuse(s) or HACR type circuit breaker(s). Each ice
maker must be provided with a separately protected circuit with no other load(s). A fused
disconnect installed adjacent to each ice maker is recommended (must be supplied by the
installer), and may be required by local codes. NORMAL protector size is based on rated
voltage and operation at lower than extreme temperature limits. When branch circuit conductors
are sized to permit, increasing the protector size (up to the specified maximum) may avoid
nuisance protector opening under harsh operating conditions.
Remote condenser Ice Maker models from the factory are provided with adequate refrigerant
charge to accommodate all acceptable condenser ambient temperatures and up to 50 ft.
refrigerant lines. The Ice Maker Nameplate label on the rear of the cabinet indicates the factory
charge amount, maximum total charge, and refrigerant type. Ice makers are provided with re-
sealable refrigerant line connection couplings.
All Ice Maker models are intended FOR INDOOR USE ONLY with PERMANENT
CONNECTION TO THE FIELD ELECTRICAL SUPPLY. The remotely-installed condensers
supplied by Kold-Draft
®
may be installed outdoors.
Other operating condition requirements:
Ice maker ambient air temperature: MINIMUM 45°F and MAXIMUM 90°F.
Remote condenser ambient air temperature: 110° F MAXIMUM.