A two-stage vacuum pump is recommended
if moisture is to be removed by evacuation.
A single-stage pump will not remove
moisture. An electronic vacuum gauge
calibrated in microns is recommended for
recording vacuum. Connect the vacuum
meter to some point on the system, such as
the purge connection on the condenser, so
the actual vacuum is read rather than the
vacuum at the vacuum pump. The pump
should be connected to both the low and
high pressure sides with copper tube or high
vacuum hoses (1/2 inch I.D. minimum)
A vacuum of 500 microns and below is
recommended to effectively remove
moisture from the system. Close the valve
at the pump and watch the gauge. If the
system contains moisture or a leak is present
the vacuum gauge will show a rise in
pressure. When there is no visible rise in
system pressure for 12 hours after the
vacuum valve is shut off, evacuation is
complete.
IV. ELECTRICAL
The power supply voltage, phase and
frequency must match what is shown in the
condensing unit data plate. All wiring must
be carefully checked against the condensing
unit wiring diagram.
V. CHARGING THE SYSTEM
Weigh the refrigerant cylinder before
charging the system so an accurate record
can be made of the amount of refrigerant put
in the system.
Connect the suction service gauge to the
compressor suction service valve and the
discharge service gauge to the receiver
outlet port. The third hose from the
charging manifold should be connected to
the refrigerant cylinder.
CAUTION: NEVER charge liquid
refrigerant through the suction side of the
system.
When initially charging a system that is in a
vacuum, liquid refrigerant can be directly
added into the receiver until the system
pressure equalizes with pressure in the
refrigerant cylinder.
Start the system and finish charging until the
sight glass is clear.
Outdoor condensing units are furnished with
a condenser flooding type of head pressure
control valve for cold weather operation.
This valve should be set at 180 psig for
better performance for this unit. The correct
refrigerant charge must be added at start up.
Table 2 indicates the refrigerant charge at
different ambient temperature.
Determine the ambient temperature at the
time of charging the system and locate this
temperature at the top of table 2. Next
locate the condensing unit model number
and the refrigerant type on the left side of
the table. Read from left to right until you
reach the column for the days ambient
temperature. Record the condensing unit
charge at this set of conditions. Next locate
the column for the winter design
temperature and record the condensing unit
charge. The difference between these two
values is the additional refrigerant that must
be added to the system for proper winter
operation.
VI. OPERATION CHECKOUT
1) Check electrical connections, fan blade
set screws and refrigerant connections. Be
sure they are tight.
2) Check the low pressure control setting.
See Table 3 for proper setting.
3) With the system operating, check the
supply voltage. It must be within +/- 10%
of the voltage marked on the unit nameplate.
4) Check the room thermostat setting. Be
sure it functions properly.
5) Check the compressor amp draw. It must
not exceed the value on the unit data plate.
6) After the room temperature is reached,
the expansion valve superheat must be
checked. Too low suction superheat may