LEAKSAFE SOLUTIONS |WATERSWITCH3USER GUIDE
PAGE 3
3 red ashes & no beeps every 15 seconds
VALVE CLOSED DUE TO NO FLOW TIMER BEING
EXCEEDED
Rapid beeping for 15 seconds then 3 red ashes &
3 beeps every 60 seconds
VALVE CLOSED DUE TO WATER CONTINUOUS
FLOW TIMER BEING EXCEEDED
Rapid beeping for 15 seconds then 2 red ashes &
2 beeps every 60 seconds
VALVE CLOSED DUE TO A WATER LEAK
BEING DETECTED
Rapid beeping for 15 seconds then 1 red ash & 1
beep every 60 seconds
VALVE CLOSED DUE TO MAINS POWER FAIL
(if this option was selected)
Green ashing every second & 2 beeps
VALVE CLOSING
Green ash every 60 seconds
WATER VALVE CONTROL OPERATING ON
BATTERY POWER
Fast green ashing every 0.5 second & 1 beep
VALVE OPENING
Solid green
WATER VALVE CONTROL OPERATING ON
MAINS POWER
4 orange ashes & 4 beeps every 60 seconds
VALVE HAS BECOME DISCONNECTED FROM
WATER VALVE CONTROL (if this option was
selected)
1 orange ash & beep every 60 seconds
LOW BATTERIES, CHANGE BATTERIES ASAP
2. INDICATORS AND ALARMS
LEAK ALARM VALVE OPERATING
WARNING
3. RESETTING AND OPENING THE VALVE AFTER A LEAK ALARM
3.1: Resetting the system after a leak has been detected
The Water Valve Control will shut the valve on the incoming water main or pipe if a leak detection tape is in contact with water.
1. Press the “WATER OFF” button on the Water Valve Control it will beep once and mute the alarm – the valve remains closed. If
the alarm continues, and you have a detection tape directly connected to the Water Valve Control, unplug the tape then press
the “WATER OFF” button on the Water Valve Control to mute the alarm.
2. Identify where in the property the leak has occurred.
3. If you have wireless leak detector transmitters installed the one that has instigated the alarm will be beeping. If none of the
Transmitters are beeping but you have a leak detection tape or tab directly connected to the Water Valve Control then this is
where the leak is.
4. Repair the leak and dry the leak detection tape. Tapes should be unplugged and dried either naturally, or with a hairdryer on a
medium setting held 1M away from the tape, or on a warm (not hot) radiator.
5. Reposition and reconnect the tape once dry.
6. Press “WATER ON” on the Water Valve Control to open the valve.
PLEASE NOTE:
If you have a ow meter installed the WARNING light will ash (no beeps) when water is owing through the meter.