Phone: (844) LEDONE6 | Fax: 1-510-217-9461 | Web: www.ledonecorp.com
Date: _______________ Location: _____________________________________
Product: ___________________Project: ________________________________
Quantity: _____________Catalog #: ____________________________________
FEATURES
•Listed to UL924
•Test to CSA C22.2 NO. 141 Field or factory
installation
•Wattage Adjustable: 10W / 15W / 20W
•Constant output power
•Output LVLE Compliant
•Battery: Ni-MH
•Battery Charging Current: 250mA
•Battery:
oOver voltage protection
oLow voltage protection
oOver temperature protection
oShort circuit protection
•Ambient Temp: 0°-50°C (32°F-122°F)
•5-year warranty
AC OPERATION
•AC power is present. The AC driver operates
the LED load (the LED load must be less than
100W) as designed. The emergency pack is
charging in a standby mode. The test button
will be lit showing that the battery is
charging.
TESTING
•Press the test button to cut the power to the AC driver and switch
the system to emergency mode.
•Release the test button to return to normal mode.
•Switch off the circuit breaker to simulate a full power outage.
•For initial testing, allow the unity to charge approximately 1 hour.
Then conduct a short discharge test.
•Allow for a 24-hour charge before conducting a 1-hour test.
EMERGENCY OPERATION
•When the AC power goes out, the emergency
pack detects the power outage and
automatically switches to the emergency
mode. The LED load is illuminated for a
minimum of 90 minutes. When the AC power
is restored, the emergency pack switches
back to normal mode and starts to recharge.
NFPA 101 Life Safety Code Schedule
•Monthly:
oEnsure that the test button light is illuminated. Conduct a
30-second discharge test by depressing the test button.
The LED load should operate at reduced output.
•Annually:
oEnsure that the test button light is illuminated. Conduct a
full 90-minute discharge test by depressing the test
button. The LED load should operate at reduced output.
LED LOD-EXTED Emergency Driver Series