Lennox CLIMATIC 50 User manual

1
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
1
Climatic 50
Wireless System
Roof-Top, Aircoolair & Compactair
Version 23
INSTALLATION
OPERATING &
MAINTENANCE MANUAL
Ref : CL50-RoofTop-IOM-Wireless-0708-E
LENNOX have been providing environmental solutions since 1895, our range of Baltic TM rooftop continues to meet
the standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and
uncompromising attention to detail. Engineered to last, simple to maintain and Quality that becomes a standard.
Further Information on www.lennoxeurope.com.
All the technical and technological information contained in this manual, including any drawing and technical
descriptions provided by us, remain the property of Lennox and must not be used (except in operation of this
product), reproduced, issued to or made available to third parts without the prior written agreement of Lennox.
The technical informations and specifications contained in this manual are for reference only. The manufacturer reserves the
right to modify these without warning and without obligation to modify equipment already sold.

2
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
2
TABLE OF CONTENTS
Page
INTRODUCTION 3
Compatibility 3
Important Warning 3
WIRELESS 4
Function 4
Description 4
Terminology 4
Wireless 4
Wireless network 4
ZigBee™ 4
Advantages of the wireless solution 4
Advantages of ZigBee™ 4
The advantages of working at 2.4 GHz 5
LENNOX© CONCEPTION 5
INSTALLATION 6
Access point 6
General warnings 6
Terminal and Sensor 6
CONFIGURATION 7
Visualization with the DS50 7
Setting the addresses 7
Automatically search for the wireless communication channel 8
Connecting the devices (Binding) 9
Open Domain 9
Reset devices 10
Note: 11
SETTING AND ASSIGNMENT 11
Terminal 11
Sensor 11
Choice of probes 11
TERMINAL DCw 13
Display 13
Keypad 13
Information Displayed 14
Mode 14
Zone 14
ON/OFF 14
Clock button 14
Clock from terminal 15
FRESH AIR button 15
Multifunction button 16
Functions 16
Sleep 16
Alarms 17
Setting the Parameters 17
Editing the user parameters 17
Editing the factory parameters 17

3
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
3
INTRODUCTION
Compatibility
This documentation is compatible with the programs Roof Top and Aircoolair:
Ranges Baltic I, Baltic 410, Flexy I, Flexy II, FX,AC and LV, starting from the version 23.0
Important Warning
Any parameter modification should be carried out by trained and licensed competent
technician.
Before start-up or restart of a unit controlled by Climatic 50, it is mandatory to check adequacy between Climatic
50 and the unit with its options.
38xx menus for unit and options
39xx menus for communication
In case of wrong parameters, I/O links could be incorrect and may create some operation problems for the units
and ultimately breakdowns.
Lennox cannot be held responsible for any claims on the units due to a wrong parameters sequence or a
parameters modification carried out by non competent technicians. In this case, the warranty will be legally null and
void.
Any wiring modification on the CLIMATIC 50 must be done by Lennox technician or employees
having valid electrical qualification and authorisation.
For any modification of wiring on the 24V supply or on 4-20mA sensor, check the polarity prior to apply the
power. Wrong polarity may cause serious damage and destroy the Plan network. Lennox will not accept liability for
damage caused by wrong power connection or any wiring modification done by people without valid training and
qualifications.
Any external connection with the unit, using 24Vac voltage should not exceed a length of more than 30m. It
concerns external contacts connected to Climatic™50 logical inputs or humidifier control connection to the output
0-10v.
Over 30 m,the installer must interface this information with relays or converters or a external 24V supply.
In any case, the 24Vac control voltage must not be used to drive external function with Climatic™50 logical
output
WARNING: Separate as much as possible probes, displays, logical input cables from power
cables with strong inductive load, in order to avoid possible electromagnetic perturbations

4
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
4
WIRELESS
Function
The CAREL© / LENNOX© Wireless system is designed for all HVAC/R applications that require the monitoring of the
ambient conditions (temperature and for the future humidity) and/or the control of the ambient comfort based on the
requirements of the end user (operating mode, set point, …).
Description
Wireless is made up of:
• DCw (display):
An innovative wireless terminal with integrated sensors for measuring the temperature and humidity.
With the Climatic™ Roof-Top soft is it possible to have au maximum 1 DCw by unit.
• SCw (sensor):
Wireless sensors that measure the temperature and humidity.
With the Climatic™ Roof-Top soft is it possible to have au maximum 6 SCw by unit.
• APw (access point):
RS485/ZigBee™ gateway hat collects the information from the terminals and sensors.
With the Climatic™ Roof-Top soft is it possible to have au maximum 1 APw by unit.
• ARw (repeater):
ZigBee™ to ZigBee™ device that relays the wireless signals, allowing greater distances between the access point
and terminals or sensors
The Humidity management and the repeater are not currently available
Terminology
Wireless
Wireless means “without wires”, in contrast to the term “wired”.
Wireless network
Telecommunications system (series of devices, appliances, methods and protocols) for the transmission of information
via radio, typically radiofrequency technology used instead of wired connections, making the systems particularly flexible.
ZigBee™
Zigbee™ is a set of specifications based on the IEEE-802.15.4 standard for the creation of Wireless Personal Area
Networks (WPAN).
Comparable in some ways to Bluetooth, it stands out for its very low power consumption and the reduced cost of
implementation, despite having a maximum data transfer speed of 250 Kbit/s.
ZigBee™ devices, with compact dimensions and low costs, are designed to work in dedicated self-organised networks
(Mesh networks) and are used in many fields.
Advantages of the wireless solution
Advantages of a wireless network over a wired network
Mobility of the terminals;
Ease of installation and connection of the devices;
Coverage even where obstacles are present;
Flexibility in the event of structural modifications;
Reduction in wiring costs;
Scalability in the interconnection of terminals;
Sturdiness.
The advantages of wireless networks can overcome some of the intrinsic limits in wired systems.
Advantages of ZigBee™
Standard technology;
Reduced costs ;
Can be used globally;
Reliable;
Supports a large number of nodes;
Easy configuration;
Long battery life;

5
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
5
Secure data transmission.
The advantages of working at 2.4 GHz
The band centred around 2.45 GHz (used in the Wireless system) is the only one that can be used all over the world,
without needing to apply for special licenses. In addition, the ISM band (Industrial, Scientific and Medical) exploits the full
potential of the standard, that is, can use 16 transmission channels with a bit rate of 250 Kbit/s.
LENNOX© CONCEPTION
50m
Display
DCw
6 Sensors (T° only)
SCw
Access Point
APw
Cable length up to 100m:
LiYCY
-
P (0.34 mm ²), 2 pairs with general shield
The Lennox© Wireless system is designed around an Access Point per unit. The latter, in a bubble radius of 50 meters
at most, allows connection to wireless displays 'DCw' and a maximum of 6 probes 'SCw'
The display allows the display and adjusting the parameters of the unit connected.
For probes, a setting can send to the unit concerned the average value of probes desired.
If the bus Master/Slave is made between units, the value of one or other probes connected to an APw may be sent to
another unit
50m
2 Sensors
for Unit 2
Access Point
APw
Master/Slave Connection
3 Sensors
f
or
U
nit 1
U
nit 1
U
nit
2
SCw
1
SCw
2
SCw
3
SCw
4
SCw
5

6
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
6
INSTALLATION
Access point
APw
For this option the BM50 must be fitted on the Field-bus (or Analog Selection) port with the PCO100FD10 card (3 pins)
This card is used to interface a BM50 Field-bus with an RS485 type bus.
The card provides optically coupled isolation between the regulator and the RS485serial network.
If a board tLan, PCO100TLN0 (2 pins), is already present in the Field-Bus port, you need to replace it by a board RS485
(3 pins), PCO100FD10
Similarly, the BE50 is different depending on the type of bus, by default it is installed a BE50-tLan, PCOE00TLN0, in the
case of an option Wireless BE50-RS485 must be put in place, PCOE004850.
Fasten the APw to the wall with the cable gland facing downwards;
Tighten the antenna in the special housing (4), position it vertically to the floor;
Connect the ‘+’ and ‘-‘ of RS485 network to terminal (2);
Connect the power supply to terminal (1) ‘+’ from ‘G’ and ‘-‘ from ‘G0’.
General warnings
The APw must be positioned in the same open-space that the display DCw or probes SCw.
• Fasten the APw in the desired position, considering that as the device being installed is a radio device, the following
simple rules must be observed:
Avoid enclosing the appliance between two metal walls;
The efficiency of radio transmission is reduced when there are obstacles, metal shelving or other objects that may
block the reception of the wireless signals;
If the product is wall-mounted, fasten it to a masonry wall rather than a metal wall, to improve the range of the
signal;
Remember that the best position for the APw is one where it is “visible” to the other devices. It should be positioned
in such a way as to minimise any obstacles;
Like all radio equipment, avoid installing the APw near other electronic appliances, so as to avoid interference.
Do not install the instruments in environments with the following characteristics:
Strong vibrations or knocks;
Exposure to water sprays;
Exposure to direct sunlight or the elements in general;
If the appliance is used in a way that is not described by the manufacturer, the specified level of protection may be
affected.
Terminal and Sensor
DCw & SCw
The terminal and the sensor can be fastened to the wall using the support shown in the figure (included with the product).

7
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
7
Part A shown in the figure is used to lock the instrument to the support. A screwdriver will be required to remove the
instrument. This plastic part may be essential for hotel-type applications. For applications where the instrument needs to be
removed frequently (residential, office,…) part A can be eliminated simply.
CONFIGURATION
The following chapter describes the procedure for setting the address, configuring and connecting the devices for the
creation of a wireless domain connectable to the Climatic of the unit.
The procedure includes:
1. setting the address of the access point
2. setting the address of the terminals
3. setting the address of the sensors
4. Connecting the modes. In this phase, the terminals and the sensors are associated with the access point.
Visualization with the DS50
The Wireless option must be activated in the program Climatic ™ 50 by 3941 setpoint.
If a DCw must be installed; settle the 3942 setpoint by 1 (0 if not DCw)
The number of SCw installed must be setting in 3943 (between 0 and 6)
All other parameters of the option Wireless are visible on the special screens
To enable these special screens press the button 'Prg' when you're on the menu 000 or menus data 2xxx. Then you
move from one screen to another, press the buttons '↑' or '↓' to see the screen desired.
Setting the addresses
This is a fundamental phase in setting up the system, and allows each device to be identified uniquely.
Important: the address can only be set at this time. Any changes, when the channel has been set (see Automatically
search for wireless communication channel), will be ignored. The address can only be changed after having reinitialised the
device (see Resetting the devices).
Access point
APw
Position the dip-switch in the following manner:
No. 1 to Off
No. 2 to Off
No. 3 to Off
No. 4 to On
This configuration is at No. 8
Power up the access point;
Check that LED L1 (yellow) on the left is always on and the others are off. If the LEDs are not in this
status, reinitialise the access point (see Resetting the devices);

8
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
8
Automatically search for the wireless communication channel
The wireless system requires of use a transmission channel for the communication of the wireless messages between
the various devices. The best communication channel for the environment in question is automatically selected by the
access point, using the following procedure:
Power up the access point (the left LED must be on steady);
Press the button and check the activation sequence
For around 10 seconds
For around 20 seconds
The instrument is ready for the use.
The transmission channel has been selected and will be sent to the repeaters, sensors and terminals during the binding
phase.
Important:
• If the sequence is not as indicated, reinitialise the device
• If the instrument is reinitialised, all the instruments associated with it will be disconnected and will need to be connected
again.
DS50
In the special screens, search the screen beginning with [ Wireless (APw) ]
For an APw perfectly set and connected we have the following screen:
If the connection is correct between the BM50 and
APw the symbol ‘’ appears on the second line.
If the symbol ‘’ is displayed instead of a symbol ‘’ it
means that communication between the BM50 and APw is
not achieved. In this case check the cable connection
between the two packages or addressing the APw if these
points are correct reset the APw and / or cut and replace
the 24V of the box
If on the second line the state east to Off and on the
third line the text [Access Point] is not present, repeat the
Automatically search for the wireless communication
channel (described above).
Terminal
DCw
Perform the following steps for the correct connection to an existing network.
Power up the terminal by removing the insulating tab from the battery compartment;
Check that the display comes on and the text OFF is shown;
Press the “ON/OFF” button.
Check that the symbol (antenna) is off. This means that the instrument is ready to be connected to a new network;
otherwise, it means that the device has been previously been associated and needs to be reinitialised.
Access the parameters menu. Pressing simultaneously, for a few seconds, on the two buttons at the bottom;
Enter the value 16 for the desired network address for the parameter loc09;
Enter the password (22 default) for parameter loc 10.
Check that the instrument is not connected to any network, by making sure that parameter loc 12= OFF.
Sensor
SCw
Open the battery compartment and set the Desired network address using the 8 dipswitches (0 = OFF; 1 = ON), as
shown in the table.

9
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
9
DipswitchSCw Address 1 2 3 4 5 6 7 8
N°1 21 On Off On Off On Off Off Off
N°2 22 Off On On Off On Off Off Off
N°3 23 On On On Off On Off Off Off
N°4 24 Off Off Off On On Off Off Off
N°5 25 On Off Off On On Off Off Off
N°6 26 Off On Off On On Off Off Off
The address can be set but the device will not be able to connect to the access point. When pressing the button the LED
will flash quickly a number of times to indicate that the address is not valid.
Connecting the devices (Binding)
The logical connection between the access point and the wireless terminals/sensors is called binding.
The operation must be performed after setting the addresses.
Open Domain
Switch on the access point and check that the LED on the left is flashing
OPEN DOMAIN: press the button of APw and the 3 LEDs flash together.
DS50
You can open the Domain with the DS50. In the special screens, search screens starting with [Wireless (DCw) Clo] or
[Wireless (SCw 1) Clo] or if you have several SCw.
The cursor blinks at the top left of the screen. Press
the button '' to move the cursor over the text 'Clo'.
Press the buttons ‘↓ or ↑ to see the text 'Ope. After a
few seconds 3 LEDs on APw must flash and the symbol
'' indicates the opening of the domain.
To close the domain do the same.
.
Terminal
DCw
After having opened the domain on the access point:
Access the parameters menu
Enter the password (22 default) for parameter loc 10.
Set parameter loc12 to ON
the terminal displays “bin” and subsequently
–– “On” if the connection was successful
–– “no” if the connection failed.
Automatically exit the parameter programming menu.
CHECK: On the first valid transmission the terminal displays the “antenna” symbol.

10
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
10
The access point indicates that the connection has been made by sequentially activating the 3 LEDs .
DS50
In the special screens, search the screen beginning with [ Wireless (DCw) Clo]
For an DCw perfectly set and connected we have the following screen:
If the connection is correct the symbol ‘’ appears on
the second line.
If the symbol '' is displayed instead of a symbol '' it
means that the Wireless communication does not, or
more. In this case check the position of the display
compared to APw
The third line shows the power of communication.
The fourth shows the percentage of charging the
battery.
Sensor
SCw
After having opened the domain on the access point:
Insert the battery, paying attention to the polarity.
Check that LED (A) comes on for a few seconds.
Press the button located on the rear of the sensor (B) once.
The LED on the sensor (A) remains on until the device is connected to the access point.
Note:
If the LED flashes once rather than remain on steady, it means that it has already been associated with another access
point. In this case, reinitialise the sensor.
The access point indicates that the connection has been made by sequentially activating the 3 LEDs .
CHECK: The sensor will be correctly associated if each time the button is pressed once the LED flashes once.
DS50
In the special screens, search the screen beginning with [ Wireless (SCw 1) Clo] or several
For an SCw perfectly set and connected we have the following screen:
If the connection is correct the symbol ‘’ appears on
the second line.
If the symbol '' is displayed instead of a symbol '' it
means that the Wireless communication does not, or
more. In this case check the position of the sensor
compared to APw
The third line shows the power of communication.
The fourth shows the percentage of charging the
battery.
Reset devices
To reinitialise the devices to the initial purchase status, proceed as follows.
Access point
APw
Important: All the devices previously associated will be removed from the access point/repeater (no devices connected =
0).
Press the button, 10 seconds, until the 3 LEDs remain on steady (not flashing).
Release the button.
The LEDs will start flashing quickly;
The device is reinitialised if after a few seconds the LED on the left remains on steady.

11
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
11
Terminal
DCw
The following procedure reinitialises the terminal and removes the connection to the reference access point.
Access in the parameter programming procedure and set loc21 = ON.
Parameter loc21 is used to return the terminal to the default configuration (including the supervisor address).
Sensor
SCw
The address of the sensor can only be set again if it has first been associated with an access point; in the case the
connection to the access point in question will be removed.
Press the button on the rear until the LED flashes (10s);
Release the button;
The LED will flash quickly;
The device is reinitialised if when pressure the button again the LED remains on for 15s.
Note:
Resetting the terminal/sensor does not eliminate the space reserved for the terminal inside the access point. Note that,
after resetting the terminal/sensor, the number of devices on the access point remains unvaried.
SETTING AND ASSIGNMENT
Terminal
DCw
In the special screens, search the screen beginning with [ Wireless (DCw) ]
This screen can display the temperature, and humidity,
as measured by the display and adjust an offset to these
sensors.
To change the value of an offset:
The cursor blinks at the top left of the screen. Press
the button '' to move the cursor to the value of offset
temperature.
Press the buttons '↓' or '↑' to change the value.
Then press, again, the button '' to validate the new
value and position the cursor on the value of the offset
humidity.
Then press, again, the button '' to validate the new
value and position the cursor in the upper right corner.
Sensor
SCw
In the special screens, search the screen beginning with [ Wireless (SCw) ] or several
This screen can display the temperature, and humidity,
as measured by the sensor and adjust an offset to these
sensors.
To change the value of an offset:
The cursor blinks at the top left of the screen. Press
the button '' to move the cursor to the value of offset
temperature.
Press the buttons '↓' or '↑' to change the value.
Then press, again, the button '' to validate the new
value and position the cursor on the value of the offset
humidity.
Then press, again, the button '' to validate the new
value and position the cursor in the upper right corner.
Choice of probes
Warning: if this is not carried out, the unit will work with its return probe, and not with the probes system Wireless.
The following special screens to select the probes used by the unit.
You'll find 12 screens identical; representing 12 units can be connected to Master/Slave.
Each unit has the opportunity to work on the average values of sensors connected to all units slaves bus. (Altogether it is
possible to work on the average of 84 probes of the bus, 7x12)

12
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
12
The number in the upper right shows the unit affected by this setting. (Unit connected by the DS50)
The number of the second line indicates the number of different cards that could be connected to the bus Master/Slave.
(Note: Even if the unit is not connected to the bus that screen will be displayed)
The first column represents the symbol DCw may be connected to this unit slave.
The following six columns represent the symbol SCw may be connected to this unit slave.
A symbol '' indicates that a probe is present and connected to the slave
A Symbol '' indicates that the values of this probe will not be used for the unit concerned.
A Symbol '' indicates that the values of this probe will be used for this unit.
To change the choice of assignments (a make on 12 pages):
The cursor blinks at the top left of the screen. Press the button '' to move the cursor to the square of DCw.
Press the buttons ‘↓ or ↑ to change status.
Then press, again, the button '' to validate the new value and position the cursor on the following square corresponding
to the first probe SCw.
Then press, as many times as necessary, button '' to reposition the cursor on the other probes then at the top right
corner
The last special screen shows the result of averaging probes selected for this unit.

13
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
13
TERMINAL DCw
This chapter describes the functional characteristics of the terminal.
Display
Key:
1 Main field.
2 Operating mode indicator
3 Flat battery indicator
4 Wireless connection active with the APw
5 Display in °C/°F indicator
6 Set mode for the value of field 1
7 Fresh Air display indicator
8 Secondary field.
9 Time in 12/24 h mode indicator
10 Occupancy mode active
11 Time band active (1 or 2) indicator
12 Sleep mode indicator. The digit shows the hours
remaining
13 Lock button/function active
14 Active alarm. Field 8 shows “E” + alarm code 1 to 255
Keypad
Front buttons
(Numbered from 1 to 6, from top to bottom, left to right)
n. Button meaning
1 Mode ON/OFF
Pressed briefly:
• Terminal ON if the instrument is OFF.
• Return to the main screen.
Pressed and held (3 s):
• Terminal OFF.
2 Time Bands
Pressed briefly:
• Enter time band setting mode.
Pressed and held (5 s):
• Enter clock setting mode.
3 Fresh Air
Pressed briefly:
• Change percentage of Fresh Air (UP/DOWN buttons to change value).
4 Up
From the main menu increase the value of the set point displayed in the
large field. From the other menus display the variables or the parameters
or set the value if first pressing the multifunction button.
5 Multifunction
Each time the button is pressed displays the menu set for parameters loc
7, 8, 13, 14, and 15. To change, if available, the values displayed in the
menus, press the up/down buttons.
6 Down
From the main menu decrease the value of the set point displayed in the
field. From the other menus display the variables or the parameters or set
the value if first pressing the multifunction button
3 & 6 Fresh Air + Down
+
Pressing Fresh Air/DOWN together accesses the parameters menu.
Press the UP/DOWN buttons to access the desired parameter and the
multifunction button to set the value, again using the UP / DOWN buttons.
Press the multifunction button again

14
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
14
Information Displayed
Mode
Dead zone, Blower to Off
Dead zone, Blower to On
Cooling mode
Heating mode
Electrical heaters to On
Zone
Zone A
Zone B
Zone C
Unoccupied
BMS
ON/OFF
Button pressed and held for 3 sec
Clock button
The button is used to set:
• The time bands.
• The clock
Key:
Select band number
Select HOUR, MINUTES and ON/OFF/TEMP fields
Set the value of the field
Terminal time bands
The terminal can save up to two daily events with the automatic changeover of the ambient settings at set times.
Key:
Enter time band setting mode by pressing once
Band 1 can now be programmed, with HOUR digits flashing
1. Enter the start hours for band 1 using the and buttons
2. Press to select MINUTES
3. Enter the start minutes for band 1 using the and buttons
4. Press to select ON/OFF/TEMP
5. Enter the action of band 1 using the and buttons
OFF
ON
Temperature set point: 8 °C to 32 °C
6. Press to select band 2 and repeat steps 1 to 5
To exit the time band setting mode:
• by time around 30 s after the last button was pressed

15
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
15
• Manually by pressing
The enabling of the time bands is indicated in normal operation by the symbols and the number of the band
that is active at that time.
Note: from when programming until the expiry of the first band, only the symbols without indicating the number
of the active band.
The time bands can be disabled by selecting the value Off in step No. 4 above.
Example: with manual set point 21°C.
Clock from terminal
Key:
Enter clock setting mode when pressed and held for 5 seconds.
The clock can now be set, with the hour digits flashing
• Enter the current hours using the and buttons
• Press to select MINUTES
• Enter the current minutes using the and buttons
To exit clock setting mode:
• By time around 30 sec after the last button was pressed
• Manually by pressing
FRESH AIR button
Set the % of outside air mixed (mainly for applications with ARIA).
• Pressing the button once displays the %FA already set in the main field.
• Each time the and button is pressed increases/decreases the %FA in steps of 1%FA.
To exit the FRESH AIR function:
• By time, 5 seconds after the last button is pressed
• Manually by pressing the button .

16
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
16
Multifunction button
Used to manage the display/setting of the five functions shown in the following list:
Value function notes
0 No function
1 Set temperature Modifiable
2 Temperature Display only
3 Set humidity Modifiable
4 Humidity Display only
5 Clock Display only
6 Sleep Modifiable
7 °C/°F Modifiable
Pressing once displays the configured functions, in sequence.
• Each time the UP/DOWN button is pressed increases/decreases the function selected (where modifiable)
To exit the selected function:
• By time, 5 seconds after the last button is pressed
• Manually by pressing
The functions that can be associated are configured using parameters loc 7, loc 8, loc 13, loc 14, and loc 15.
loc 7 Field displayed when pressing multifunction once
loc 8 Field displayed when pressing multifunction the second time
loc 13 Field displayed when pressing multifunction the third time
loc 14 Field displayed when pressing multifunction the fourth time
loc 15 Field displayed when pressing multifunction the fifth time
Note:
• The humidity value is displayed on the temperature-only model as “---“.
• The humidity set point can also be displayed/set on the temperature only model.
Functions
Display
The numeric fields on the display can be configured based on requirements.
Parameters loc1 and loc2 are used to customise these fields.
Main display (loc1)
loc1 display notes
1 Temperature Default
2 Set Temperature COMFORT displayed if COMFORT function active (loc)
3 Humidity “---” if humid. sensor not fitted
4 Set Humidity -
Secondary display (loc2)
loc2 display notes
0 no display Blank
1 Temperature -
2 Set Temperature COMFORT displayed if COMFORT function active (loc)
3 Humidity “---” if humid. sensor not fitted
4 Set Humidity -
5 Clock Default
Sleep
The Sleep function is especially useful at night, when the decrease in body temperature (due to sleep) changes our
perception of the ambient temperature.
• Association with the multifunction button.
In this case:
• Press the multifunction button until reaching the following screen.
To exit the selected function:

17
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
17
• By time, 5 seconds after the last button is pressed
• Manually by pressing the button
The enabling of the function is highlighted on the display in normal status:
The operating hours count down until the time (3h) expires, after which the Sleep function will end.
Upon activation of the function is for the time requested, the unit will be forced to Uno mode
Alarms
An alarm/warning from the BM50 can also be shown on the display.
Setting the Parameters
The terminal features a series of internal parameters to customise the device according to the type of use.
The parameters are divided into two categories:
• User –parameters modifiable by the user without entering the password
• Factory –parameters modifiable only after having entered the password
Editing the user parameters
Editing the factory parameters
Use the procedure described in the previous paragraph to access parameter loc10, and enter the password (default 22).
The factory parameters (loc9, loc11 to loc21) can now be displayed and set.

18
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
18
Loc Description Values Min Def lt Max
Loc1 It sets up the visualization of the great
field
1 = setpoint temperature (C°/F°)
2 = temperature (C°/F°)
3 = setpoint humidity (%Rh)
4 = humidity (%Rh) 1 2 4
Loc2 It sets up the visualization of the small
field
0 = No visualization
1 = setpoint temperature (C°/F°)
2 = temperature (C°/F°)
3 = setpoint humidity (%Rh)
4 = humidity (%Rh)
5 = Clock 0 5 5
Loc3 24 or 12h AM/PM 0 = 24H
1 = AM/PM 0 0 1
Loc4 Value in C° degrees to the setpoint of
temperature in the sleep mode Not used -
5.0°C
0.0°C +5.0°C
Loc5 Ambient calibration probe temperature +/-10°C -
9.5°C
0.0°c +9.5°C
Loc6 Ambient calibration probe humidity +/- 10% -10%
0% +10%
Loc7 It sets up the visualization to the first
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0 1 6
Loc8 It sets up the visualization to the second
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0 4 T. & Hu
6 T. only 6
Loc9
Address for the supervisor. For its
formulation it is necessary that finishes
is not associated they to some Access
Point. If finishes the parameter is
associated they is alone in reading. If
she wants herself to be removed from
the net they finishes look [16..199] 16 16 199
Loc10
It concurs to insert the password in
order to approach the parameters with
password
The value of the password is
defined from P11. And present a
value of default decided in factory
in order to concur the first access. 0 22 999
Loc11
Modification the password of access
(P10) 000-998 = new password
999 = it eliminates the password 0 999
Loc12
If set up to ON it eliminates finishes
them from the running net
disassociandolo from just the Access
Point
ON = Current value
OFF = Removal of the terminal on
the current network Off On On
Loc13
It sets up the visualization to the third
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0 3 T. & Hu
0 T. only 6

19
CLIMATIC™50 –IOM –Rooftops/ Aircoolair
CL50
-
ROOFTOPS
-
IOM
-
Wireless
-
0708
-
E
19
Loc Description Values Min Def lt Max
Loc14
It sets up the visualization to the quarter
pressure of the key multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0 6 T. & Hu
0 T. only 6
Loc15
It sets up the visualization to the fifth
pressure of looks at table description
parameters multifunction key
multifunction ()
0 BLANK. The field remains empty
1 Setpoint of temperature
2 Temperature
3 Setpoint humidity
4 Relative humidity
5 Clock
6 Timer of sleep 0 0 6
Loc16
Resistance Automatic from BM50 Off Off On
Loc17
It sets up the allowed modalities in the
system of conditioning through key
MODE Automatic from BM50 0 0 6
Loc18
Modality lock. Several rules except the
keys come block to you to the keys
second up/down Automatic from BM50 0 0 (Keys were
Liber to) 15
Loc19
Set the mode of occupation. It is a
function of the terminal which makes it
possible to send to the supervisor if a
person misses or present. When that a
key is in a hurry the person is present in
the definite state of Occupation for a
definite time. With Not used 0 0 3
Loc20
If qualified limits the variation of the
setpoint of temperature through keys
up/down to a range of +/- 3C° (+/- 6°F).
They In place of visualizing the setpoint
finishes visualizes the degrees to add or
to embezzle to this (from -3C°/-6F° to
+3C°/+6F°) OFF = Disable function
ON = Enable function Off Off On
Loc21
Factory parameters. To set up to ON for having the
factory parameters. Off Off On
Other manuals for CLIMATIC 50