Levitronix BFS-i04 User manual

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
First Release: 30-Nov-2022
Last Update: 26-Jun-2023
Bearingless Fan BFS-i04
870 Pa
4.4 m3/min
(3.5 inH2O)
(155 cfm)
USER MANUAL
This manual contains information necessary for the safe and proper use of the BFS-i04 bearingless fan.
Included are specifications for the standard configurations and instructions regarding its use, installation,
operation, adjustment, inspection, and maintenance. For special configurations refer to accompanying
information. Please familiarize yourself with the contents of this manual to ensure the safe and effective use
of this product. After reading this manual, please store it where the personnel responsible for operating the
bearingless fan can readily refer to it at any time.
The Levitronix®Service Software (with according manual Levitronix
Doc.# PL-4048-00) is available for
operation, troubleshooting, parameter logging or user specific configurations. For the bearingless fan the
Levitronix®Service Software version V2.0.9.6 or higher is needed.

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
2
Table of Contents
1SAFETY PRECAUTIONS........................................................................................................3
2SPECIFICATIONS...................................................................................................................4
2.1 Specification of Components............................................................................................................. 4
2.2 System Configuration ........................................................................................................................ 6
2.2.1 Standard System Configuration.....................................................................................................................6
2.2.2 System Configuration ATEX / IECEx.............................................................................................................6
2.3 Basic Dimensions of Main Components............................................................................................ 7
2.4 General Environmental Conditions.................................................................................................... 8
2.5 Pressure-Flow Curves ....................................................................................................................... 9
3ENGINEERING INFORMATION............................................................................................10
3.1 Power Supply and Consumption ..................................................................................................... 10
3.1.1 Power Consumption....................................................................................................................................10
3.1.2 Power Supply..............................................................................................................................................11
3.1.3 Inrush Current .............................................................................................................................................11
3.2 Sound Pressure Level ..................................................................................................................... 12
4INSTALLATION ....................................................................................................................13
4.1 Electrical Installation........................................................................................................................ 13
4.1.1 Installation Instructions for Power Supply and PLC Interface Signals .........................................................13
4.1.2 Electrical Schematics Overview of Motor Interface .....................................................................................15
4.2 Mechanical Installation .................................................................................................................... 16
4.2.1 Flange Sealing Recommendation ...............................................................................................................16
4.2.2 Mounting Proposals.....................................................................................................................................17
4.3 Installation Examples with Interface Panel...................................................................................... 18
5OPERATION .........................................................................................................................19
5.1 Operation of Bearingless Fan.......................................................................................................... 19
5.2 Operation for ATEX / IECEx Application ......................................................................................... 19
6TROUBLESHOOTING AND SUPPORT................................................................................20
6.1 Troubleshooting for Operation with PLC ......................................................................................... 20
6.2 Troubleshooting with Service Software........................................................................................... 20
6.3 Technical Support............................................................................................................................ 20
7APPENDIX ............................................................................................................................21
7.1 Regulatory Status ............................................................................................................................ 21
7.1.1 CE / UKCA Marking.....................................................................................................................................21
7.1.2 ATEX / UKEX / IECEx Certification and Marking.........................................................................................21
7.1.3 Disposal of Equipment –WEEE Directive 2012/19/EU ...............................................................................21
7.2 Symbols and Signal Words.............................................................................................................. 22

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
3
1 Safety Precautions
The BFS-i04 bearingless fan is designed to be used in industrial production machines and equipment
containing ventilation circuits. Typical applications are semiconductor and chemical manufacturing equipment.
Installation shall be done by qualified personnel only. The following safety precautions and all “CAUTION”,
“WARNING” and “DANGER” indications in the relevant sections shall be followed.
CAUTION
Do not under any circumstances open the fan. Levitronix®does not assume
responsibility for any damage occurring under such circumstances.
CAUTION
High magnetic field strength of fan rotor
The fan rotor contains magnets with high field strength. This may alter or
damage the calibration of sensitive electronic devices and measuring
instruments in the immediate surroundings. Keep at a safe distance from
computers, monitors and all magnetic data storage media (e.g. disks, credit
cards, audio and video tapes etc.).
CAUTION
Revolving fan rotor
The fan rotor operates at high rotational speeds. It may cause injury if fingers,
hands, hair, clothes, etc. are getting in touch with the revolving fan rotor. Do not
touch the fan rotor while it is moving.
!
WARNING
Hazardous voltage may be present
In case of usage of an inadequate AC/DC power supply, mains voltages may be
present (even if the system is designed for 24 VDC). The usage of a galvanically
separated power supply, which is certified by a 3rd party (UL or CE), is required.
Do not under any circumstances open the powered fan.
!
WARNING
High magnetic field strength of fan rotor if removed from motor
The fan rotor contains magnets with high field strength. If removed from motor,
pacemakers may be influenced, and magnetic forces may lead to contusions.
Only remove rotor if necessary. Keep distance to pacemakers and handle fan
rotor with care.
!
WARNING
TOXIC CHEMICALS may be present
When using the system to ventilate chemicals, skin contact and toxic gases may
be hazardous to your health. Wear safety gloves and other appropriate safety
equipment.
!
WARNING
Bearingless fan for ATEX / IECEX applications
Only specific types of the bearingless fan are classified for the use in Ex
classified locations. Refer to the corresponding section in the manual.

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
4
2 Specifications
2.1 Specification of Components
Figure 1: Standard fan
Figure 2: Accessories
1
2
E
F
C
B
D
A
A
B
C
D
4
5
9
10
6
7
8
3

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
5
Pos.
Component
Article Name
Article #
Characteristics
Value / Feature
1
Bearingless Fan
BFS-i04.1
100-10224
Voltage, Power Input
24 V DC ±10%, 80 W
(Option: 12 V DC ±5%, 20 W, with reduced max. speed of 10000 rpm)
Max. Pressure, Max. Flow
870 Pa (3.5 inH2O), 4.4 m3/min (155 cfm)
Point of Max. Power
700 Pa, 3.7 m3/min, 18000 rpm
(Optional 12 V supply voltage: 200 Pa, 2 m3/min, 10000 rpm)
ATEX / IECEx Marking
1258
II 2G Ex h mb IIC T6 Gb
II 2D Ex h mb IIIC T85 °C Db
Ambient and gas temperature range 0 to 40 °C
IP Rating
IP67
Electrical Interfaces
PLC with 2 analog inputs 4-20 mA
1 analog output 4-20 mA
1 digital input 0-24 V
RS485 interface, Modbus protocol (extended control or service through
fieldbus or Levitronix®Service Software)
Standard Firmware
V5.48
Mechanical Interface
Flange on both motor sides with mounting holes 4 x Ø 5.8 mm on
diameter 90 mm. Flange inside Ø 72 mm, outside 80 mm x 80 mm
Cable Length
5 m with TE connector for power and PLC signals
Materials
Polypropylene, electrically conductive, flame retardant
Cable: PVC jacket, PVDF bushing
Weight
0.5 kg, 1.1 lb
Table 1: Specification of standard configuration
Pos.
Component
Article Name
Article #
Characteristics
Value / Feature
2
Adaptor Cable Hybrid
ICH-5.1-03 (0.3 m)
190-10544
Specifications
PVC insulated open wires (2 x 0.75 mm2for power, 6 x 0.14 mm2for
signals) with TE connector
Purpose
Connection of fan cable to DC power supply and PLC signals
3
AC/DC Power Supply
See section 3.1.2 for a list of compatible and tested power supplies
4
Interface Panel
FIP-1.1
100-91638
Structure/Design
DIN-rail mountable PCB with connectors for:
- 4 x BFS-i04 fans (TE Connectivity 1-1827875-4)
- 1 x Power supply connector (Wago 2624-3103)
- 18 x PLC push-in (analog inputs/outputs, digital inputs, RS485)
- 1 x Circular COM for LUI-B.1 or USB-RS485 adaptor
Purpose
Easy wiring of power and PLC signals for up to four BFS-i04 fans, see
section 4.3 for further information
5
User Panel
LUI-B.1-06
100-30549
Specifications
Firmware A8.00, IP65, 5 to 24 V supply voltage
Purpose
Control of fan via handheld device
6
USB-RS485 Adaptor
YN-485I-TR
100-30392
Structure/Design
USB connector (A) with termination resistor and cable (2 m) with
connector pair (B and C) for external RS485 wire connection.
Magnetically isolated. Included is a USB space saver cable (D)
Purpose
Control or service of fan via USB port of a PC with Levitronix® Service
Software
7
IP Adaptor Cable
Signal 6 Wires
ICS-1.1-10 (1 m)
ICS-1.1-30 (3 m)
190-10344
190-10345
Specifications
PVC jacket, connectors: circular to circular type
Purpose
Connection of user panel (LUI-B.1) to interface panel (FIP-1.1)
8
IP Adaptor Cable
Signal 6 Wires
ICS-1.2-10 (1 m)
ICS-1.2-50 (5 m)
190-10440
190-10346
Specifications
PVC jacket, connectors: circular type to screw type
Purpose
Connection of user panel (LUI-B.1) to adaptor cable (ICH-5.1) and 5 to
24 V supply
9
IP Adaptor Cable
Signal 6 Wires
ICS-1.3-50 (5 m)
190-10389
Specifications
PVC jacket, connectors: circular type to screw type
Purpose
Connection of interface panel (FIP-1.1) to USB adaptor (YN-485I-TR)
10
ATEX Cable
Sealing System
ACS-A.1
(Roxtec)
100-90292
Materials
Sleeve (A) and Gasket (B): Stainless Steel, EPDM
Frame(C) and 2x Cable Module (D): Roxylon (EPDM Rubber)
Note
Lubricant (E) and measurement plates (F) are included
Table 2: Specification of standard accessories

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
6
2.2 System Configuration
2.2.1 Standard System Configuration
Figure 3: Standard system configuration (left) and connection with open wire adaptor (right)
Note: Connection options (right of dashed line) are interchangeable with Figure 4
2.2.2 System Configuration ATEX / IECEx
Figure 4: ATEX / IECEx system configuration (left) and connection with interface panel (right)
Note: Connection options (right of dashed line) are interchangeable with Figure 3
Integrated
Motor and
Electronics
Gas
In
Gas
Out
Mounting
Flange
Tubing
Flow or Pressure Sensor
(optional, not included)
Cable
Bushing
Gasket
(not included)
Impeller
MagLev Fan
Motor Cable
Chemical Resistance
and IP-67 Space
1
Signal Cable
8
User Panel
5
RS485 / USB Converter 6
PC Connection:
- System configuration
- Firmware update
- Monitoring
AC/DC
Power Supply
DC
Out AC
In
3
Screw type connector for open
wires included in cable packages
Motor Interface
- 1 Digital Input
- 2 Analog Inputs
- 1 Analog Output
- RS485 Interface
- DC Supply (+VDC, GND)
Adaptor Cable
2
RS485:
Connect either User Panel,
PC or fieldbus
Integrated
Motor and
Electronics
Gas
In
Gas
Out
Mounting
Flange
Tubing
Flow or Pressure Sensor
(optional, not included)
Cable
Bushing
Gasket
(not included)
Impeller
MagLev Fan
Motor Cable
Ex conform cable
sealing system
Ex Location
Outside of Fan:
Zone 1/21 or
Zone 2/22 or
Non-Classified
Chemical Resistance
and IP-67 Space
Ex Location
Inside of Fan:
Zone 1/21 or
Zone 2/22
1
4 x PLC Connection
2 x Analog Input
1 x Analog Output
1 x Digital Input
Fan
4
Fan
3
Fan
2
Fan
1
PLC Interface
Supply
COM
RS485 interface
for fieldbus
Signal Cable 7
Signal Cable
9
Easy coupling of
multiple fans for
serial or parallel
operation
User Panel
5
RS485 / USB Converter 6
PC Connection:
- System configuration
- Firmwareupdate
- Monitoring
AC/DC
Power Supply
DC
Out AC
In
3
4
Interface Panel
Easy andquick wiring of
up to 4 fans
10

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
7
2.3 Basic Dimensions of Main Components
For other configurations, components or more details refer to the according drawings.
Figure 5: Basic dimensions in mm [in] of bearingless fan BFS-i04.1
Note: Non-tolerated dimensions are for reference only, dimensions in inch are rounded only
Figure 6: Basic dimensions of adaptor cable ICH-5.1-03
Minimum Cable Bending Radius:
Permanent Installation: 5 x cable OD (32.5 mm [1.28 in])
Sometimes Moved: 10 x cable OD (65 mm [2.56 in])
Cables are not suited for sustained dynamic bending and movement
Standard Cable Configuration:
A = 5.00 m [196.85 in]
2
1
Wires:
Power: 2 x0.75 mm2, PVC
Signal: 6x 0.14mm2, PVC
Connector:
TE D1200 1-1827864-4
Motor Cable:
PVC, gray
Cable Bushing:
PVDFwith FKM-sealing
and FKM flatsealing ring
Housing and Rotor:
PP, electrically conductive,
flame retardant
Mounting Flange
Sealing Surface

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
8
Figure 7: Basic dimensions of interface panel FIP-1.1
Figure 8: Basic dimensions of user panel LUI-B.1
2.4 General Environmental Conditions
Condition
Limits
Usage
Indoor
Altitude
Up to 2000 m
Operating ambient temperature
0 to 40°C
Storage ambient temperature
(Extremes for Transportation)
-20 to 80°C
Operating humidity range (relative humidity)
15 –95% (non-condensing)
Storage humidity range (relative humidity)
(Extremes for Transportation)
15 –95% (non-condensing)
Normal storage conditions
Ambient temp.: 20 to 30°C
Relative humidity: 50% (non-condensing)
DC supply fluctuations
10% of nominal voltage
Transient over-voltages typically present on
the mains supply
Surge immunity according to EN 61000-4-5
(tested together with certified AC/DC power supply)
Pollution degree
2
Table 3: Environmental conditions for bearingless fan
4
5

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
9
2.5 Pressure-Flow Curves
Figure 9: Pressure-flow curves of bearingless fan BFS-i04.1
Note: Typical values measured for BFS-i04.1
•Pressure Drop Coefficient at 0 rpm: C = 0.506 (P = C x Q2, Q = Flow [l/s], P = Pressure Drop [Pa]).
•24 V / 12 V Supply Voltage: The maximum rotational speed is limited to 18000 rpm for 24 V supply
voltage and 10000 rpm for 12 V supply voltage.
•Negative Rotation Direction: Negative rotational speeds can be enabled in the EEPROM editor of
the Levitronix®Service Software or via Modbus command. This feature can be used to block an
existing flow, as replacement for actively controlled valves. If negative flow needs to be avoided for
safety reasons, it is recommended to install passive check valves or a safety shutdown mechanism to
deactivate the bearingless fan in case of negative flow.
•Serial or Parallel Operation of Multiple Fans: Multiple fans can be used to achieve higher pressure
or flow levels.
a. Serial: Pressure is multiplied by up to the number of fans, while flow remains unchanged
b. Parallel: Flow is multiplied by up to the number of fans, while pressure remains unchanged
020 40 60 80 100 120 140 160
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0
100
200
300
400
500
600
700
800
900
1000
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Flow / cfm
Pressure / inH2O
Pressure / Pa
Flow / m3/min
Atmospheric Pressure: 950 hPa, Air Temperature: 24 C
12000 rpm
10000 rpm
16000 rpm
8000 rpm
14000 rpm
18000 rpm
6000 rpm
24 V Supply Voltage,
Released Performance
Stability Limit
(Tilting)
12 V Supply Voltage,
Released Performance
020 40 60 80 100 120 140 160
-4.0
-3.5
-3.0
-2.5
-2.0
-1.5
-1.0
-0.5
0.0
-1000
-900
-800
-700
-600
-500
-400
-300
-200
-100
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Flow / cfm
Pressure / inH2O
Pressure / Pa
Flow / m3/min
-10000 rpm
-6000 rpm
Stability Limit
(Tilting)
0 rpm
-18000 rpm
24 V Supply Voltage,
Released Performance 12 V Supply Voltage,
Released Performance
6000 rpm
-12000 rpm

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
10
3 Engineering Information
3.1 Power Supply and Consumption
3.1.1 Power Consumption
Figure 10: Steady state power consumption vs flow and speed (DC input)
Note: Typical values measured for BFS-i04.1
Figure 11: Peak power consumption during acceleration (DC input)
Note 1: Typical values measured for BFS-i04.1 at operating point with maximum power consumption
Note 2: Dashed line: example of optional input power limitation
020 40 60 80 100 120 140 160
0
10
20
30
40
50
60
70
80
90
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Flow / cfm
Power Consumption / W
Flow / m3/min
Atmospheric Pressure: 950 hPa, Air Temperature: 24
12000 rpm
Atmospheric Pressure: 950 hPa, Air Temperature: 24Atmospheric Pressure: 950 hPa, Air Temperature: 24
16000 rpm
Atmospheric Pressure: 950 hPa, Air Temperature: 24
10000 rpm
8000 rpm
14000 rpm
18000 rpm
24 V Supply Voltage,
Released Performance
12 V Supply Voltage,
Released Performance
0
10
20
30
40
50
60
70
80
90
100
5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000 16000 17000 18000 19000
Power Consumption / W
Rotational Speed / rpm
24 V Supply Voltage,
Released Performance
12 V Supply Voltage,
Released Performance
12000 rpm / s 6000 rpm / s

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
11
•Steady State Power Consumption: Depends on the actual speed, pressure, and flow. Figure 10
visualizes the steady state power consumption for different operating points.
•Peak Power Consumption (short time): Occurs during acceleration and depends on the rotational
speed and the acceleration rate. Figure 11 visualizes the peak power consumption.
•Power Supply Rating: Depending on the operating point, one power supply may be used to power
several bearingless fans simultaneously, or a supply with lower power rating may be used (see also
section 3.1.2).
•Input Power Limitation: An optional input power limit may be set via Levitronix®Service Software or
Modbus protocol. If set, actual acceleration rate and/or maximum speed are reduced dynamically such
that the specified limit is not exceeded (±5 W tolerance). The extent to which they are reduced depends
on the power limit as well as the operating point. The dashed line in Figure 11 shows an example for
50 W at operating point with maximum power consumption. The fan accelerates with 12000 rpm / s
up to 12000 rpm, then gradually reduces the acceleration rate to prevent further increase in input
power. The maximum reachable speed in this operating point at 50 W input power is around
15300 rpm (see also steady state consumption, Figure 10).
3.1.2 Power Supply
It is highly recommended to evaluate used power supplies under demanding operating situations like fast
braking from maximum speed and during power on and take-off of the fan rotor.
The power rating of the supply may be chosen according to the desired operating point / maximum speed /
number of fans per supply –see Figure 10, Figure 11.
Table 4 shows a selection of power supplies tested at Levitronix®with according speed and/or input power
limitations. Please note that only the general functionality of the BFS-i04 in combination with the given supplies
was tested, and no recommendations in terms of reliability, efficiency, certifications, cost effectiveness or
similar are given.
Manufacturer
Article Name
Characteristics
Value / Feature
Recommended Limits
Traco Power
TIB 480-124
Voltage Input / Output
85 –265 V AC (full range) / 24 V DC
- No limit required (5 fans per power supply)
- Example limits for 8 fans per power supply:
Input power limit 85 W (peak)
Speed limit 16000 rpm (continuous)
Power Output
480 W / 720 W for 4 s
Certification / Standards
CB, UL, CSA, Semi F47
Traco Power
TIB 240-124
Voltage Input / Output
85 –265 V AC (full range) / 24 V DC
- No limit required (2 fans per power supply)
- Example limits for 6 fans per power supply:
Input power limit 55 W (peak)
Speed limit 13000 rpm (continuous)
Power Output
240 W / 360 W for 4 s
Certification / Standards
CB, UL, CSA, Semi F47
Traco Power
TIB 120-124
Voltage Input / Output
85 –265 V AC (full range) / 24 V DC
- No limit required (1 fan per power supply)
- Example limits for 4 fans per power supply:
Input power limit 40 W (peak)
Speed limit 12000 rpm (continuous)
Power Output
120 W / 180 W for 4 s
Certification / Standards
CB, UL, CSA, Semi F47
Traco Power
TIB 080-124
Voltage Input / Output
85 –265 V AC (full range) / 24 V DC
- No limit required (1 fan per power supply)
Power Output
80 W / 120 W for 4 s
Certification / Standards
CB, UL, CSA, Semi F47
Table 4: Specification of tested power supplies
The following power supplies were tested but failed to recover the DC voltage quick enough during fast braking
and accelerating tests, triggering a shutdown to error state on the fan:
Traco Power TSP 180-124
3.1.3 Inrush Current
The BFS-i04features an e-fuse limiting the inrush current. A peak value of 0.34 A with an I2t value of
0.006 A2s was measured by hot-plugging the BFS-i04with 5 m cable length to a 180 W power supply.

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
12
3.2 Sound Pressure Level
The sound pressure level emitted by the BFS-i04 depends strongly on the installation, operating point, and
rotational speed. It is recommended that customers measure the sound pressure level after installation of the
fan in their setup during typical operation.
Figure 12 shows the sound pressure levels measured at Levitronix®. The fan was installed at a height of about
1.8 m above ground into a closed duct system. Measurements were taken based on Semi S2 guidelines, i.e.
1 m traversed from the setup at a height of 1.2 m and 1.5 m above ground.
Figure 12: Sound pressure level vs rotational speed and measurement height
Note: Typical measured values of BFS-i04.1 installed in a closed duct system
35
40
45
50
55
60
8000 10000 12000 14000 16000 18000
Sound Pressure Level / dBA
Rotational Speed / rpm
24 V Supply Voltage,
Released Performance
12 V Supply Voltage,
Released Performance
1.5 m above
ground
1.2 m above
ground

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
13
4 Installation
4.1 Electrical Installation
!
WARNING
Protective Earth on Ex-Model
Bearingless fans placed in Ex classified locations must be connected to
protective earth, which must be done with the ground / earth wire according to
Table 5.
!
WARNING
Hazardous voltage may be present
Always isolate the electrical power supply before making or changing
connections to the unit.
In case of usage of an inadequate AC/DC power supply, mains voltages
may be present (even if the system is designed for 24 VDC). The usage
of a galvanically separated power supply, which is certified by a 3rd party
(UL or CE), is required.
CAUTION
The PLC pins are not galvanically isolated from the motor electronics.
4.1.1 Installation Instructions for Power Supply and PLC Interface Signals
•Connection: Connector type TE D1200 1-1827864-4 is used as the combined power and signal
connector of the fan. Counterpart is TE D1200 1-1903131-4 (adaptor cable available as accessory).
Connect power and desired interfaces to the respective pins according to Table 5 and connect the DC
supply ground to earth. Figure 14 provides a reference for hardware configuration of the PLC inputs
and outputs.
•Power requirement: See section 3.1 for the power consumption of the bearingless fan.
•PLC requirement: To operate the bearingless fan with a PLC, a minimum of one analog input is
needed for speed control, or a set of two analog inputs for process (pressure or flow) control. The
analog output can be used to monitor operating parameters. See Table 5 for an overview of the
standard functionality. For in-depth details on the configurability of PLC interface, please refer to the
firmware specification document (standard firmware: SW-3506-00).
•RS485 interface: To use RS485 as a control or service interface, an initialization resistor network
according to Figure 13, Figure 14 should be used to ensure stable communication and avoid
disturbance effects.
For service and debugging purposes with the Levitronix®Service Software an RS485 to USB converter
cable (initialization network included) can be ordered according to Table 2.
Do not use multiple master devices at the same time.
•RS485 Fieldbus Multi-System Arrays: Several systems can be directly connected to the same
RS485 master. See Figure 13.
Address setting of the fan units can be done with the Levitronix®Service Software and a PC.
A termination resistor is recommended for long bus lengths. Do not use closed ring arrangements.
Contact Levitronix®technical support (section 6.3) for further details and support.

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
14
Pin
Wire Color
Designation
Description
Standard Levels
B3
Blue
Digital input
Process / speed mode switch
5…24 V (min. 30 ms) Process mode
0 V / n.c. (min. 30 ms) Speed mode
B2
Pink
Analog input 1
Setpoint speed / process value
and enable / reset fan
4…20 mA 0…18000 rpm / 0…100 % setpoint
> 3.5 mA (edge triggered) On / reset
B1
Gray
Analog input 2
Actual process value
(pressure or flow sensor)
4…20 mA 0…100 %
A1
Yellow
Analog output
Actual speed
0…18000 rpm 4…20 mA
A4
Brown
RS485 +
RS485 interface
Modbus protocol
B3
White
RS485 -
A3
Red
Power +
Supply
+ 24 VDC ± 10 %
+ 12 VDC ± 5 % (reduced performance)
A2
Black
Power -
Ground. Must be connected to earth
Reference level to all analog / digital signals
Table 5: Standard configuration of motor connector
Note: Levels and assignments of analog and digital inputs and outputs are configurable in EEPROM editor of Levitronix®Service
Software or through Modbus protocol. See firmware specification (SW-3506-00) for detailed information
Pin
YN-485I-TR
Open wire to USB adaptor
ICS-1.2
Open wire to user panel LUI-B
ICS-1.3
Interface panel FIP to USB adaptor
1
-
RS485+
RS485+
2
-
RS485-
RS485-
3
-
Ground
Ground
4
Ground
-
-
5
RS485-
-
-
6
RS485+
+ 24 VDC supply for LUI-B
-
Table 6: Pin definition of screw type connectors on adaptor cables
Figure 13: Multi-fan system array on RS485 fieldbus
510 W
120 W
3.3..5 V
510 W
120 W
Termination:
Recommended for main bus line > 5 m
Initialization network:
Always recommended, to be implemented atmaster
Master Main bus line: < 100 m. Shielded twistedwires recommended
Branch bus lines: sum of all branch lengths < 33 m
System 1
System 2, 3
System 4, 5, 6
System n

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
15
4.1.2 Electrical Schematics Overview of Motor Interface
Figure 14: Electrical schematics of motor interface
Note 1: RS485 to USB converter cable with termination resistors to be ordered according to Table 2
Note 2: Do not use multiple master devices on the RS485 at the same time
Bearingless fan
interface circuit Example of user
interface circuit
240 W
240 W
27 kW
B3 / Blue:
Digital input
B2 / Pink:
Analog input 1
B1 / Gray:
Analog input 2
A1 / Yellow:
Analog output
A4 / Brown:
RS485+
B4 / White:
RS485-
GND
4..20 mA
4...20 mA
Personal
Computer
(Service)
5..24 V
4..20 mA
Max. pin voltage analog
inputs to GND = 10 V
Pin numbers, wire colors
and wire name
510 W
A3 / Red:
24 VDC
A2 / Black:
Ground / Earth
120 W
3.3..5 V
Signal pins are not galvanically
isolated to motor electronics
450 W
Tool
Control
510 W
RS485 - USB
Converter
with
Termination
3.3 V
AC/DC
Supply
24 VDC
100 kW
Combined power & PLC connector
Max. pin voltage digital
input to GND = 26.4 V
Input
Protection
35 V / 6 A

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
16
4.2 Mechanical Installation
CAUTION
High magnetic field strength of fan rotor
The fan rotor contains magnets with high field strength. This may alter
or damage the calibration of sensitive electronic devices and measuring
instruments in the immediate surroundings. Keep at a safe distance from
computers, monitors and all magnetic data storage media (e.g. disks,
credit cards, audio and video tapes etc.).
!
WARNING
High magnetic field strength of fan rotor if removed from motor
The fan rotor contains magnets with high field strength. If removed from
motor, pacemakers may be influenced, and magnetic forces may lead
to contusions. Only remove rotor if necessary. Keep distance to
pacemakers and handle fan rotor with care.
!
WARNING
Only specific BFS-i04 bearingless fans are classified for the use in Ex
classified locations. Refer to the corresponding section in the manual.
!
WARNING
In case separation of Ex classified locations is needed at installation, the
relevant safety precautions to fulfill the relevant regulatory requirements
must be considered.
•Ex cable sealing system: An Ex conform solution is needed for the motor cable to leave the Ex area.
One option is an Ex certified cable sealing system as listed in Table 2.
•Rotor handling: The rotor contains permanent magnets which can attract ferromagnetic parts.
Therefore, any ferromagnetic tools and tools with sharp edges should be kept away from the rotor to
avoid injury to personnel and damage to the rotor surface. Do not remove rotor from fan unless
necessary.
•Motor fixation before operation: The motor must be mounted rigidly before operation. The magnetic
bearing is not designed for movement of the fan during operation. Any movement (especially tilting) of
the fan during rotation may lead to a touch-down of the magnetic bearing with potential mechanical
damage to the system.
•Motor fixation, resonances: It should be avoided that the mounting construction can resonate with
the motor. Such resonances will lead to excessive motor currents, heat-up of the system and may lead
to malfunction of the magnetic bearing.
•Motor fixation within ducts: Do not use the fan as a structural element of a duct system. The flange
is not designed to withstand excessive force or torque.
•Mounting holes: The fan can be mounted with four M5 screws on the inlet flange and four M5 screws
on the outlet flange (see Figure 5).
•Cable bending radius: Minimum cable bending radius according to Figure 5 must be ensured.
4.2.1 Flange Sealing Recommendation
The pressure tightness of the fan flange was successfully tested at Levitronix®with the following reference
setup:
•Flat Gasket: Material FKM, thickness 3 mm, dimensions see Figure 15.
•Flange Counter Part: Material PP, thickness 10 mm.
•Screws: M5 screws, tightening torque 1 Nm.

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
17
Figure 15: Flat Gasket Dimensions (mm) used by Levitronix®
4.2.2 Mounting Proposals
BFS-i04 fans can be adapted into many different duct systems and may be operated in parallel or series to
achieve higher flow or pressure. This section shows a few of many possible mounting scenarios. For more in-
depth information contact Levitronix® technical support (section 6.3).
Figure 16: Possible mountings of BFS-i04 in different duct systems
Round duct,
small diameter Square duct
2 fans in series,
up to 2 x pressure
Round duct,
large diameter
2 fans in parallel,
up to 2 x flow rate 3 fans in parallel
3 x flow rate

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
18
Figure 17: Examples of mounting with through holes (left) and self-cutting thread inserts (right)
4.3 Installation Examples with Interface Panel
The interface panel FIP-1.1 can be used for easy wiring of up to four fans. The panel can be mounted to a DIN
rail. Figure 18 describes two of many possible scenarios. For more in-depth information contact Levitronix®
technical support (section 6.3). See section 3.1.2 for the selection of the power supply.
Figure 18: Examples of fan installation with interface panel FIP-1.1
Left: Four fans are connected to a single power supply and controlled individually through fieldbus interface
Right: Two fans are mounted in series and controlled through PLC. The first fan runs in process mode using the feedback from a
pressure or flow sensor, the second fan is configured to match the speed of the first one. They act as one process control unit with
higher pressure performance (the same configuration may be used with fans mounted in parallel to achieve higher flow performance)
Ain1
Ain2
Aout
Din
1
2
3
4
Ain1
Ain2
Aout
Din
Ain1
Ain2
Aout
Din
Ain1
Ain2
Aout
Din
Power
input
UI
RS485-
RS485+
Power supply
e.g. TIB-480-124
Fieldbus
Ain1
Ain2
Aout
Din
1
2
3
4
Ain1
Ain2
Aout
Din
Ain1
Ain2
Aout
Din
Ain1
Ain2
Aout
Din
Power
Input
UI
RS485-
RS485+
Power supply
e.g. TIB-240-124 Set pressure
or flow
(4..20 mA)
Speed
feedback
(4..20 mA)
Pressure
or flow
sensor
(4..20 mA)

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
19
5 Operation
CAUTION
Revolving fan rotor
The fan rotor operates at high rotational speeds. It may cause injury if fingers,
hands, hair, clothes, etc. are getting in touch with the revolving fan rotor. Do not
touch the fan rotor while it is moving.
Please consider the following notes for safe and successful operation of the bearingless fan BFS-i04 to prevent
injury to personnel or damage to equipment:
•Mounting: Only activate the bearingless fan if it is firmly mounted to a rigid non-movable structure.
•Mechanical Protection: Only activate the bearingless fan if the rotor is mechanically protected from
reaching into it. Operating the fan without protection might lead to serious personnel injury or damage
to equipment as a result of objects being pulled into the rotor blades.
5.1 Operation of Bearingless Fan
Operation and Interfaces:
•PLC:Control through analog and digital inputs and outputs.
•RS485, Service Software: Control through a PC. Service Software is available from Levitronix®
Technical Service Department (section 6.3), connection cable is available as accessory (section 2.1).
•RS485, Modbus commands: Digital control through superordinate customer control unit.
•RS485, User Panel: Control through the user panel LUI-B.1. Panel and connection cables are
available as accessories (section 2.1).
Fan control modes:
•Closed loop speed control: Internal sensors are used to measure the actual rotational speed to
assure accurate control of the setpoint speed.
•Closed loop process (pressure or flow) control: An external pressure or flow sensor must be
connected to the analog input of the PLC. Control parameters need to be adapted according to the
used sensor (response time, delay, scaling), the placement of the sensor (before/after, distance to fan)
and the setup of the hydraulic circuit. Contact Levitronix®Technical Service Department for assistance
(section 6.3).
Please refer to the firmware specification document for complete details about the operation of the BFS-i04
(document number for standard firmware: SW-3506-00). The document can be requested from Levitronix®
Technical Service Department (section 6.3).
5.2 Operation for ATEX / IECEx Application
Specific precautions may be considered while using the bearingless fan in potentially explosive gas
atmospheres according to ATEX / IECEx category 2G/2D (Zone 1 and 21) or 3G/3D (Zone 2 and 22).
!
WARNING
Operational Temperature 85°C T6
Maximum allowed gas temperature is 40°C / 104°F for the use in Ex
classified applications.
!
WARNING
Do not operate the fan against closed valves
Operation against closed valves might lead to increased gas
temperature.

User Manual for BFS-i04
www.levitronix.com
PL-3507-00, Rev00, DCO# 23-128
20
6 Troubleshooting and Support
6.1 Troubleshooting for Operation with PLC
The integrated PLC provides information about speed or process value. However, in case of an error, type and
cause of the error cannot be identified. For detailed analysis and debugging it is recommended to use the
Levitronix
Service Software (see below). Alternatively, the Status, Error, Warning and Message bytes can be
read using Modbus commands on the RS485 interface. The firmware specification document, available at the
Levitronix®Technical Service Department (see below), contains all details for configuration and interpretation
of these commands.
6.2 Troubleshooting with Service Software
The Levitronix
Service Software allows communication with the bearingless fan in connection with a PC and
an RS485 to USB converter (see Table 2).
The Service Software can be used to operate the system, for troubleshooting, parameter logging and user
specific system configuration. For usage of the Service Software contact the technical support (below).
6.3 Technical Support
For troubleshooting, support, and detailed technical information contact Levitronix
Technical Service
Department:
Levitronix
Technical Service Department
Bändliweg 30
CH-8048 Zurich
Switzerland
Phone for US: 888-569 07 18
Phone for outside US: +1 888-569 07 18
E-Mail: TechSupport@levitronix.com
Table of contents
Other Levitronix Fan manuals
Popular Fan manuals by other brands

Vortice
Vortice ARIANTE TOWER DESCRIPTION AND USE

nilan
nilan Comfort 250 Top installation instructions

Westinghouse
Westinghouse ETL-ES-GW-Contempra-WH22 owner's manual

Craftmade
Craftmade Chalice CL52 Specifications

Vortice
Vortice VORT PRESS 110 I LL Instruction booklet

AERMEC
AERMEC VES030 installation manual