LIGHTSAFE ERTSLEDPT User manual

Lightsafe_ERTSLEDPT_Instructions_Rev01
ERTSLEDPT
3 hour Non Maintained LED Twinspot
c/w Automatic Self-Test unction
Please read these instructions before installation and retain for the user/maintenance engineer for future reference
IMPORTANT NOTE:
The luminaire must be installed by a skilled electrician and to the most current electrical wiring and building
regulations
This product MUST be earthed and NOT be subject to an electrical insulation test (500/1000v) which will not be
covered by the warranty
This product should not be modified in any way, if modified this will invalidate any warranties and Firesafe will not be
liable for any damages caused
The person carrying out the installation is to check and verify that the total load on the circuit, including the rating of
the cable, fuse and/or circuit breaker is not exceeded
It is the responsibility of the installer to consider any fire risks and breach in any fire protection barriers or partitions,
and take the appropriate precautions
Emergency lighting should be installed and maintained in accordance with BS5266 and BS EN50172
INSTALLATION
1 Ensure the mains supply is isolated
2 Remove the 4 screws securing the lid
3 If screws or bolts are used to secure the unit then consideration will need to be given as not to comprise the
IP rating of the fitting for the environment the luminaire is to be installed
4 A permanent 230v AC supply is required to the live (L), Earth and neutral (N) terminals on the PCB
5 Ensure a gland or grommet is used to maintain the IP rating of the luminaire and that ALL electrical
connections are made good with no loose strands
6 Plug the battery lead into connector on the PCB
7 Secure the lid with the 4 screws
8 Restore the AC mains supply, ensure the LED indicators on the front of the lid, green charge LED, lamp 1 & 2
indicators are illuminated Green
9 Allow 24 hour to charge the batteries and record the installation date in the log book
10 After a 24 hour charge period test the luminaire for a full 3 hour duration by removing the 230v AC supply
and record the date of the commissioning on the battery pack inside the luminaire and also in the log book
11 Subsequent testing should be carried out in accordance with the British/European standards and recorded in
the log book

Lightsafe_ERTSLEDPT_Instructions_Rev01
Automatic Self-Test unction
The luminaire has an integral automatic self-test function
When the luminaire is connected to a 230v AC supply the luminaire will perform an automatic test, monthly and
annually The first monthly test will be performed approximately between 16
th
to 30
th
day and the annual test will be
between 200
th
to 360
th
day from initial power on
After the first annual test, the test routine will then be scheduled for every 30 days and every 360 day for the
monthly and annual tests The luminaire will retain the testing schedule for approximately 7 days without a 230v AC
supply (the internal battery still has to be connected)
Automatic Daily Test
The luminaire checks daily if the lamps are connected, if connected these will be indicated by the two green LEDs on
the lid marked as ‘Lamp 1 OK’ and ‘Lamp 2 OK’, if there is an issue, the relevant lamp LED will be extinguished and
the “Status Indicator” will flash red twice every three seconds Also as part of the daily check the fitting checks that
the battery is connected and that AC mains supply is present, if both are present then the Green Charge On LED on
the lid will be will be illuminated If the battery is not connected or there is an issue with the battery the (Charge On)
LED will extinguish and the “Status Indicator” will flash Red once every three seconds If there is no 230v AC supply
present all LED indicators on the lid will be extinguished and the luminaire will be in emergency mode
Monthly /Annual Test
The luminaire performs an automatic 10 minutes duration self-test every month and an annual test for the full 3
hours duration During the test all the LED indicators will be extinguished except for the (Status Indicator) which will
be flashing Red quickly to indicate the fitting is in test for the duration of the test, if the test has been completed and
satisfactorily then the (Charge On) and the two “Lamp Ok” LEDs will be a constant Green state
If during the test there is an issue with the light output, then the (Charge On) LED will be off and the status indicator
will flash Red twice every three seconds
If fitting does not complete the required emergency duration then the (status indicator) LED will flash Red three
times every three seconds
Manual Test
The luminaire has an internal test button (on the PCB) which has two functions;
1 When the button is pressed once, the schedule of self-test will be reset (i e from the 1
st
day installed)
2 When the button is pressed for three seconds, the fitting will enter a self-test mode for 10 minutes with the
same LED indication as the monthly/annual test (see above)

Lightsafe_ERTSLEDPT_Instructions_Rev01
ront Cover LED Indicator Status
All LED indicators Off: No AC supply present
Charge LED
On (Green): AC mains supply and battery connected
LED Off: test mode or battery/test fault
Status Indicator
Red Flash Once every 3 seconds: Issue with the battery during the daily test
Red Flash very quickly: Luminaire in manual/monthly/annual test mode
Red Flash Twice every 3 seconds: Fitting failed test - Issue with the light output during auto-test
Red Flash Three every 3 seconds: Fitting failed test – the battery duration was not achieved during auto-test
Failed Test / Reset: After a failed test and the fault has been rectified, the internal test button will
need to be pressed for 3 seconds to activate a self-test or remove the 230v AC
supply to reset the fault and LED indicator status
Maintenance
Repairs should only be carried out by suitably qualified person
Regular cleaning of luminaires should be carried out at regular intervals not only to ensure good optical performance
but also ensure that dirt does not accumulate to such an extent as to impair the electrical or thermal safety of the
fitting, this should be done with a soft damp cloth, do not use any chemicals or abrasives
Servicing should only be carried out after the fitting has been made electrically safe and the battery disconnected
Light Source Maintenance: the light source of this luminaire is not replaceable; in case the light source need to be
replaced (e g at the end of its life), the whole luminaire shall be replaced
Environment:
Please DO NOT dispose of electrical items or packaging as unsorted waste, use the recycling facilities provided by
your local authorities
TESTING
Ensure the luminaires are tested in accordance with 5266-8:2004 / BS EN 50172:2004
Daily: Ensure the green charge LED is illuminated
Monthly: Check the LED Indicator Status, if Green then the unit has passed the monthly test If the LED is flashing 2
or 3 times every 3 seconds then then luminaire has failed and will require an engineer to investigate,
record the result in the log book
Annually: Repeat the monthly inspection and record the result in the log book If the LED is flashing 2 or 3 times
every 3 seconds then then luminaire has failed and will require an engineer to investigate
Defects: Any defects or failures should be noted and recorded in the log book and actioned by a competent person
as soon as possible

Lightsafe_ERTSLEDPT_Instructions_Rev01
Technical Specification:
Voltage: 230v AC 50Hz
Power Factor 0 3PF, 40mA
Lamp: 2 x 1 5W
Wattage: 3 09W
Colour Temp: 6500K
Class: 1
Battery: 3 6V 3Ah Ni-Cd
Emergency Duration: 3 Hour
Recharge Time: 24 hours
Auto test: Every month 10 minutes test duration, annually 3 hours test duration
Fuse: 1A
Temp Range: 0˚c – 40˚c
Dimensions: (L)292, (H)279, (D)68mm
Weight: 1,008g
IP: IP65
Warranty:
This product is covered by an extended warranty for 2 years from date of purchase
Batteries are regarded as a consumable item, and as such, are not covered by the Extended Warranty periods and
are only covered by a 1 year warranty
The extended warranty is available following installation in the UK or Ireland by a competent person in accordance
with the current building and IEE wiring regulations
For full terms and conditions in regards to our extended warranty please refer to the website
Due to our policy of continuous improvement we reserve the right to change specification without prior notice
Errors and omissions excepted These instructions have been carefully checked prior to publication However, no responsibility
can be accepted by Firesafe for any misinterpretation of these instructions
LIGHTSA E
Distributed by: FIRESAFE
10 Sandersons Way,
Blackpool, FY4 4NB
Email: sales@firesafe co uk
Web: www firesafe co uk
Part No:
Date:
Date:
Signed Date Signed Date Signed Date Signed Date
1 Short
2 Short
3 Short
4 Short
5 Short
6 Short
7 Short
8 Short
9 Short
10 Short
11 Short
12 Full Duraiton
INSTALLATION / TEST
RECORDS
Location:
Installed By
Comissioned By:
OURTH YEAR
MONTH TEST IRST YEAR SECOND YEAR THIRD YEAR
Table of contents
Other LIGHTSAFE Light Fixture manuals
Popular Light Fixture manuals by other brands

Lightolier
Lightolier SV T5 STRIP specification

Ibiza
Ibiza LED6EYES user manual

High End Systems
High End Systems Cyberlight user manual

Spa Electrics
Spa Electrics RETRO Installation & owner's manual

Philips
Philips Selecon Operation manual

Kind LED Grow Lights
Kind LED Grow Lights K5 WIFI Series instruction manual