
Installation Guide
8 18-HD99D1-1A-EN
5.6 Wired Zone Sensors: 5.7 Component Wiring:
The right side of the zone panel is for wired
thermistors:
ZZSENSAL0400AA Wired sensors can be
incorporated in several ways:
1. Standalone temperature sensing for a zone.
2. Multiple sensors are wired in a series /
parallel circuit for averaging (see figure
below).
3. In conjunction with other sensors for
temperature averaging; using a wired sensor
alongside a wireless sensor, thermostat
or system controller. Wired temperature
sensors connected to the zone panel are
for temperature sensing only and CANNOT
sense relative humidity.
NOTE: Do not connect more than two wires per
wired temperature sensor terminal.
NOTE: Wired zone sensors can be used for
averaging. Refer to the ZZSENSAL0400A
installation guide for details.
Control wiring is easy for installations and that
only require a single transformer. The indoor
unit transformer will power and control all
components. Most components have multiple
ports to make wiring easy:
• VS Outdoor Unit = 1 connection ports
• TAMX = 2 connection ports
• S8V2-C Furnace = 3 connection ports
• System Controller = 2 ports
• Zone Panel = 2 connection ports
NOTE: The system controller ships with a 4X
distribution board to assist with point-to-point
wiring if needed. With all components being
powered from the same source, use the easiest
connection method for the installation.
NOTE: The second port on the bottom of the hub
can only be used when the hub wiring is OK to
be exposed, e.g., ush mounting of the hub and
wiring on a stud in unconditioned space.
Control wiring is more challenging if a secondary
transformer is needed. The 8X distribution board
will also be required to isolate the transformer
loads.
• The Indoor unit, outdoor unit, and air cleaner
should be powered from the indoor unit
transformer.
Do not run sensor wires
and 24 VAC wires in the
same stat wire bundle.
Temperature
thermistor