Link ZZON2PNLA200ZA User manual

18-HD99D1-1A-EN
Zoning Installation Guide
SC360 System Controller /
UX360 Smart Thermostat
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES.
IMPORTANT - Proper application is critical when installing zoning systems. Not done correctly,
the HVAC and zoning system will not provide the expected comfort. Reference application
bulletins CNT-APG003-EN/Trane and CNT-APG004-EN/AS for detailed information on Zoning
Application.
IMPORTANT - This Document is customer property and is to remain with this unit. Please return to
service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to
be met in connection with the installation. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be
referred to your installing dealer or local distributor.
Model ZZON2PNLA200ZA
With Link technology
TM

Installation Guide
2 18-HD99D1-1A-EN
2. Zoning Overview
Contents
1. Safety
s
sWARNING
!
This information is intended for use by
individuals possessing adequate backgrounds
of electrical and mechanical experience. Any
attempt to repair a central air conditioning
product may result in personal injury and/or
property damage. The manufacturer or seller
cannot be responsible for the interpretation of
this information, nor can it assume any liability
in connection with its use.
s
sWARNING
!
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and
troubleshooting of this product, it may
be necessary to work with live electrical
components. Failure to follow all electrical
safety precautions when exposed to live
electrical components could result in death or
serious injury.
SPECIFICATION DESCRIPTION
Model ZZON2PNLA200ZA
Product Link Zone Panel
Size 6.2” width x 5.0” height x 1.2” depth
Storage Temperature -40 °F to + 175 °F, 5% to 95% RH non-condensing
Operating Temperature -40 °F to + 150 °F, 5% to 95% RH non-condensing
Input Power* 24VAC from external transformer (Range: 18~30VAC)
Power Consumption 2VA for each Zone Panel (damper VA not included)
Wire Usage Minimum 18-guage NEC approved control wiring
Communications CAN BUS /CAN System Bus
* On every application, 24VAC loads should be reviewed to be sure the indoor unit control power
transformer is adequately sized.
1. Safety ............................................................2
2. Zoning Overview .......................................... 2
3. General Information......................................3
4. Link Zoning Preparation and Mounting......4
5. Zoning Components.....................................5
6. Pre-congurationzoningchecklist.......... 13
7. Trane/AS Diagnostics Mobile App ............14
8. Link Zoning Commissioning .......................18
9. Zone 1 Sensor Setup.................................... 28
10. Sensor Assignment.................................... 29
11.ZoningAirowTest...................................33
12. Zoning Settings and Parameters .............37
13. Zone Panel Replacement ..........................39

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 3
Zone Panel Kit SKU Zone Expander SKU 8x Distribution Kit SKU
1 - Zone Expander
Assembly
1 - Zone Panel Assembly 1 - 8x Distribution Board Assembly
1 - Zone Panel Installer’s
Guide
1 - 8x Distribution Board Installer’s
Guide
1 - 8x Distribution
Board Kit
2 - Field wiring CAN
connectors (in a bag)
1 - CAN bus harness - 6 ft
(1st dist. board to 2nd dist. board)
1 - Box with labeling 4 - Zip ties 10- Field wiring CAN connectors
(in a bag)
1 - CAN bus harness - 6 ft
(dist. board to ZP or 1ZP to 2ZE) 4 - Mounting screws, 4 Wall anchors
4 - Mounting screws, 4 Wall anchors 1 - Box with labeling
1 - Box with labeling
3. General Information
3.1 What’s in the Box?
3.2 Accessories
Zoning settings are available only when a
Zone Panel is connected and discovered on
the system bus.
Sensor Accessories:
• Wired Remote Indoor Sensor
(ZZSENSAL0400AA)
• Wireless Remote Air Temperature Sensor
(ZSENS930AW00MA)
Zoning Accessories:
• Zone Kit (ZZON2KITA200ZAA, contains a
Panel and a Large Distribution Board)
• Zone Panel (ZZON2PNLA200ZA, Panel
only, no Distribution Board)
• Small (4x) Distribution Board
(BDIS2SMLA200UAA)
• Large (8x) Distribution Board
(BDIS2LRGA200UAA)
• Modulating Zone Dampers (round,
rectangular and slip-in dampers are
available)
Zone Panel(s) must be powered. Following are the steps required before enabling zoning:
1. Zone Panel(s) must be connected to the communicating bus (R, DH, DL, B).
2. All non-communicating zone temperature sensors must be connected to the corresponding zone
slots.
3. One UX360 thermostat and one SC360 system controller must be connected to the communicating
bus.
4. All dampers should be installed and connected to the corresponding zone damper output.

Installation Guide
4 18-HD99D1-1A-EN
4. Link Zoning Preparation and Mounting
Mounting Hole
Mounting
Hole
Wire Strain
Relief
Wire Strain
Relief
Mounting
Hole
Mounting Hole
Follow the below steps to mount the Link Zoning
Controller:
1. Mounting to studs: Drill 1/8” pilot holes in
the four locations marked.
2. Mounting to drywall: If mounting to drywall
with no studs behind it, enlarge pilot holes to
3/16” for anchors. Gently tap anchors into the
holes.
3. Align Link Zoning Controller to the holes.
4. Attach base to the wall using four screws
provided. Do not over tighten.
1/8” for screw
into studs
3/16” for drywall
anchors
DRILL HOLES

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 5
5. Zoning Components
Link system Communication
bus connections
Indoor temperature
thermistors
ZZSENSAL0400A
terminal inputs
Power open /
power close
dampers
terminal
outputs
5.1 Label the wires:
Zoning requires a lot of wires.
• Wires to the damper motors
• Wires to the zone sensors
• Wires to the communicating system
It is recommended to label each wire after pulling
it to its location.
Crossing wires between components can
add hours of troubleshooting time to the
commissioning process.
Labeling can be done with a wire tag or use a
fine-tip permanent marker and write on the jacket
of the stat wire as shown.
IMPORTANT: Be careful to provide plenty of
room to strip the wire back without removing
the labeling.
ZONE 1 SENSOR
DAMPER
DAMPER
ZONE 1
ZONE 2

Installation Guide
6 18-HD99D1-1A-EN
5.3 Low Voltage Wire Connectors:
Link mode uses simple connectors for low voltage
connections. These connections are color coded
which makes the installation easier and quicker.
Wire Colors
R Red
DH White
DL Green
B Blue
Do the following to make the connections from
the actual thermostat wire to the connector.
NOTE: These connectors are necessary at the
communicating outdoor unit, communicating
indoor unit, distribution board(s), system
controller and communicating accessories.
1. Strip the Red, White, Green, and Blue
thermostat wires back 1/4”.
2. Insert the wires into the connector in the
correctly colored locations.
3. When you feel it release, allow each wire
to slide in further.
4. Pull back on the wires individually and
slightly and check if the wires are seated
properly. If each wire does not pull out for all
four wires, the connection is complete.
5. Connectors are ONE-TIME-USE ONLY. If the
thermostat wire gets broken off inside of the
connector, the connector must be replaced.
NOTE: DO NOT REUSE THE CONNECTOR
– REPLACE IT INSTEAD.
6. Wire colors are for illustration purposes only.
If using a different color, ensure it lands at
the correct terminal throughout all of the
communicating control wirings.
NOTE: For use with 18 ga. solid core thermostat wire.
5.2 Damper Wiring/System Notes:
Zone Dampers
Terminal Description Color Used
Zone 1
Common
Power Open
Power Closed
Zone 2
Common
Power Open
Power Closed
Zone 3
Common
Power Open
Power Closed
Zone 4
Common
Power Open
Power Closed
Zone 5
Common
Power Open
Power Closed
Zone 6
Common
Power Open
Power Closed
Wired Thermistor
Terminal Description Color Used
Zone 1
Common
Power Open
Power Closed
Zone 2
Common
Power Open
Power Closed
Zone 3
Common
Power Open
Power Closed
Zone 4
Common
Power Open
Power Closed
Zone 5
Common
Power Open
Power Closed
Zone 6
Common
Power Open
Power Closed
RDHDLB
CAN
Connector
Strip the control
wire back- 1/4”

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 7
5.4 Damper Wire Connectors: 5.5 Duct Dampers:
The damper connectors are push-pin connectors.
Follow the below instructions to ensure proper
attachments/removal of wires:
1. Do not push the release tabs when inserting
the wires.
2. Cut all stat wires to the same length to ensure
all wires are inserted to the same depth within
the connector.
3. Gently pull back on each wire to ensure it is
fully seated.
NOTE: It is the recommended practice to strip
the thermostat cable jacket back several inches
and insert one wire at a time into the connector
until you are sure it is seated.
4. To remove a wire, press on the release tabs
and pull the wire from the connector.
5. Do not connect more than two wires per
terminal. If more dampers are required, wire
them together externally to the zone panel.
• Each Link Zone panel can support up to three
zones.
• Power open / power closed dampers are
required.
• The damper relays can support up to four
dampers per zone.
• Be consistent with the wire coloring throughout
all damper connections.
• Each Trane/American Standard brand damper
is rated at 1.5 VA.
• 60-second travel dampers are required. See
the configuration section for details.
NEC Class II Control Wiring (24V)
Wire Size Max. Wire Length
18 AWG 150 ft
16 AWG 225 ft
14 AWG 300 ft
Release Tab
PO = Power Open
PC = Power Close
Common = Common

Installation Guide
8 18-HD99D1-1A-EN
5.6 Wired Zone Sensors: 5.7 Component Wiring:
The right side of the zone panel is for wired
thermistors:
ZZSENSAL0400AA Wired sensors can be
incorporated in several ways:
1. Standalone temperature sensing for a zone.
2. Multiple sensors are wired in a series /
parallel circuit for averaging (see figure
below).
3. In conjunction with other sensors for
temperature averaging; using a wired sensor
alongside a wireless sensor, thermostat
or system controller. Wired temperature
sensors connected to the zone panel are
for temperature sensing only and CANNOT
sense relative humidity.
NOTE: Do not connect more than two wires per
wired temperature sensor terminal.
NOTE: Wired zone sensors can be used for
averaging. Refer to the ZZSENSAL0400A
installation guide for details.
Control wiring is easy for installations and that
only require a single transformer. The indoor
unit transformer will power and control all
components. Most components have multiple
ports to make wiring easy:
• VS Outdoor Unit = 1 connection ports
• TAMX = 2 connection ports
• S8V2-C Furnace = 3 connection ports
• System Controller = 2 ports
• Zone Panel = 2 connection ports
NOTE: The system controller ships with a 4X
distribution board to assist with point-to-point
wiring if needed. With all components being
powered from the same source, use the easiest
connection method for the installation.
NOTE: The second port on the bottom of the hub
can only be used when the hub wiring is OK to
be exposed, e.g., ush mounting of the hub and
wiring on a stud in unconditioned space.
Control wiring is more challenging if a secondary
transformer is needed. The 8X distribution board
will also be required to isolate the transformer
loads.
• The Indoor unit, outdoor unit, and air cleaner
should be powered from the indoor unit
transformer.
Do not run sensor wires
and 24 VAC wires in the
same stat wire bundle.
Temperature
thermistor

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 9
5.8 8X Distribution Board:
The bottom left header must be connected to
the communication circuit from the indoor unit
transformer whenever the calculated load requires
the installation of a second transformer.
This connection provides Link communication
to the distribution board and extends this
communication to all devices connected to the 8X
distribution board.
NOTE:
• The 24V Ris not connected to port 8. This
break in Reliminates the need for
transformer phasing.
• Since the two 24VAC transformers are
isolated, phasing is not a concern.
• Do not ground the secondary side of the
second transformer.
• Leave this secondary voltage oating.
The 8X distribution board provides eight
connection points for Link communication and the
24-volt power source.
The bottom of the distribution board has two
dedicated headers for the secondary transformer
and connection to the indoor unit.
Ports one through seven are to control devices
from the second transformer load.
• Furnaces will require the installation of the
50VA transformer when incorporating an
electronic air cleaner.
The Link control components (system controller,
thermostat, and zone panels) will be controlled
through the secondary transformer. The
transformer that powers the zone panels will also
power the dampers.
• This wiring technique separates the system
loads from the zoning loads; allowing
each transformer to control the dedicated
components.

Installation Guide
10 18-HD99D1-1A-EN
5.9 Transformer Sizing: 5.10 Air Handler Transformer Sizing:
Most smaller zone systems will not require a
secondary transformer.
This table shows the transformer loads in a Link
communicating system; showing furnace and air
handler loads within one table.
Use the following tables specific to the indoor unit
type being installed components to determine if
a secondary transformer is required to power the
zoning components that will be connected to the
8X distribution board.
• Enter the quantity of each device
• Multiply the quantity as per the VA for each
device
• Add up the Total VA per operating conditions
This chart is based on worst-case conditions
• Each load is full load condition (FLA)
• All loads will never be energized at the same time
Unit VA
Each Quantity Total
VA
System Controller 4
Thermostat 8
VS Outdoor Unit 115
TAMX Air Handler 212
Heater Relay 34
S8V2-CFurnace IFC 411.3
Furnace Gas Valve 510.3
Zone Panel 2
Dampers 1.5
Air Cleaner 20
Total System VA
1: SmartChargeTM Solenoid-Applicable only to
cooling in SmartCharging Mode
2: AHC=10VA+2VA for onboard heater relays
3: 5VA per 5KW with TAMX (15KW heater = 15VA)
4: IFC = 5VA in idle / cooling mode; 11.3 VA for W2
5: W2 gas heat protection
NOTE: Fan power & bypass humidiers
require a separate transformer dedicated to the
humidier being installed.
NOTE: The only transformer load for the VS
outdoor unit is the SmartCharge™ solenoid. This
solenoid is only energized in the SmartCharge™
test mode. The TAMX indoor heat relays and
furnace gas valve will be disabled during the
SmartCharge™ test mode.
Evaluate the Quantity and Total VA for each
possible components in the system.
The Total System VA is based on worst-case
conditions.
The air handler ships with a 75VA transformer.
This transformer can support Total System VA
loads up to 80 VA without requiring a secondary
transformer.
Heating Operation
Unit VA
Each Quantity Total
VA
System Controller 4
Thermostat 8
Air Handler 12
Heater Relay 4
Zone Panel 2
Dampers 1.5
Air Cleaner 20
Total System VA
Cooling Operation
Unit VA
Each Quantity Total
VA
System Controller 4
Thermostat 8
VS Outdoor Unit 15
Air Handler 10
Zone Panel 2
Dampers 1.5
Air Cleaner 20
Total System VA

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 11
5.11 Furnace Transformer Sizing:
Evaluate the Quantity and Total VA for each
possible components in the system.
The Total System VA is based on worst-case
conditions.
The furnace ships with a 35VA transformer.
This transformer can support Total System VA
loads up to 40 VA without requiring a secondary
transformer.
If a Communicating Air Cleaner (EAC or ACCE) is
installed, install the 50 VA transformer that ships
with the air cleaner.
The 50 VA EAC transformer can support Total
System VA loads up to up to 55 VA without
requiring a secondary transformer.
Evaluate the quantity and total VA for each
possible components in the system.
The Total System VA is based on worst-case
conditions.
• Enter the quantity of each device
• Multiply the quantity per the VA for each
device
• Add up the total VA per operating conditions
for both Primary transformer and secondary to
obtain Total system VA.
Secondary Transformer
Component VA Each Total VA
Secondary VA
Primary VA
Total VA
Heating Operation
Unit VA
Each Quantity Total
VA
System Controller 4
Thermostat 8
Furnace IFC 11.3
Furnace Gas Value 10.3
Zone Panel 2
Dampers 1.5
Air Cleaner 20
Total System VA
Cooling Operation
Unit VA
Each Quantity Total
VA
System Controller 4
Thermostat 8
VS Outdoor Unit 15
Furnace IFC 11.3
Zone Panel 2
Dampers 1.5
Air Cleaner 20
Total System VA

Installation Guide
12 18-HD99D1-1A-EN
* = The 4X Distribution
Borad may be used
when ACCE is not applied.
TAMX Zoned System
Minimal Zoned 2 Stage Furnace System
Can be 2 or 3 zone
dampers per zone

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 13
2 Stage Furnace Zoned System where the
loads require an external transformer
6. Pre-configuration Zoning Checklist
• All Link system components have CAN harness
connections. Ensure all pieces of the system are
connected and powered.
• Ensure all zone panels, dampers, and wired sensors
are wired correctly to the intended zones.
• Zoning Configuration can be done from the Diagnostics
Mobile App or the Thermostat, all tests and settings
are available from either the Mobile App connected to a
Link system or locally at the thermostat.

Installation Guide
14 18-HD99D1-1A-EN
7. Trane or American Standard Diagnostics Mobile App
For ease of installation, zoning can also
be configured and tested from the Trane
or American Standard Diagnostics Mobile
App.
7.1 Download the App: Trane Diagnostics App
American Standard Diagnostics App
Follow below steps to download the App:
1. Search “Trane Diagnostics” or
“American Standard” in the App Store®
or Google Play™ Store and click
“Install” to download the app.
2. You can also scan the QR code and
select “Trane” or “American Standard”
from there.
3. Accept all permissions (Bluetooth,
Location, Camera).
4. Accept the terms and conditions.

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 15
1. Use your ComfortSite username and
password to log in to the app.
2. If you do not have ComfortSite access, contact
your dealer admin or
support@comfortsite.com for help.
7.2 LOGIN to the App:

Installation Guide
16 18-HD99D1-1A-EN
1. Enable connectivity on the homeowner’s Trane
Link Smart Thermostat or American Standard
Smart Thermostat.
NOTE: This action may not be required for
new system installation.
2. Select “CONNECT TO SYSTEM” on the
mobile application.
3. Select the equipment to connect.
4. Select “Next” for setup assistant.
5. Follow the prompts and complete each
category as required.
6. Your newly connected equipment
should appear on the dashboard under
“EQUIPMENT SUMMARY” once you have
completed the setup process.
7.3 Connecting to a Link System:

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 17
Access Zoning Configuration by pressing “Zoning”
from the Configuration menu.
Follow the same commissioning steps in the app
that you would from the thermostat:
1. Enable zoning.
2. Select dampers automatically or manually.
3. Select “Run Auto Zone Sizing”.
NOTE: Automatic Zone Size Mode is preferred.
4. Assign zone sensors.
7.4 Zoning Configuration:

Installation Guide
18 18-HD99D1-1A-EN
8. Link Zoning Commissioning
The Support & Feedback tab within
the tech app provides short videos
to support zoning configurations,
assigning sensors and running the
airflow test mode.
8.1 Enable Zoning:
NOTE:
“Enable Zoning” is toggled to ON automatically
when you enter into Zoning Conguration.
The default
is automatically set to ON.
The Enable Zoning toggle is auto-enabled when Link
detects a zone panel on the communicating bus.
This toggle can be turned off if needed; such as a
new construction house where the zone sensors are
not installed yet. If the toggle is turned off without
zone sensors configured, the Link system will
control system operation as a standard non-zone
system and control system capacity from the UX360
thermostat. If this toggle is turned off before zoning
is configured and sensors are assigned; then Link
will open all dampers and control system capacity
from the smart thermostat. If this toggle is turned
off after zoning has been configured, then Link will
run the system in single-zone mode (see the zone
priority segment for single-zone mode details).
NavigatetoZoningConguration:
Menu>Service>EnterTechnicianAccess>Proceed>Conguration>Zoning
Refer to the videos for additional
support when needed.
8.2 Damper Travel Time:
60 Seconds. Cannot be modified.
7.5 Support & Feedback tab:

SC360 System Controller / UX360 Smart Thermostat
18-HD99D1-1A-EN 19
8.3 Renumber Zone Panels:
Renumbering zone panels is necessary when
there are two zone panels within the system.
If the zone numbers are not correctly auto-
assigned to two zone panels, initiate the
renumbering of the zone panels BEFORE
beginning zoning configuration.
The zone panel number LEDs on the two zone
panels will be swapped as a result.
Renumber Zone Panels:
Link will auto-detect the zone panels that are
wired into the communicating bus and auto-
discover zone panel numbers.
Link will auto-discover based on a first come / first
serve basis. The first zone panel that responds to
a Link communication message is Zone Panel 1.
The other zone panel will be Zone Panel 2. If
there is only one zone panel in a system, it will be
detected as Zone Panel 1.
• Zone Panel 1 controls zones 1 through 3
• Zone Panel 2 controls zones 4 through 6
Each zone panel will have a series of LEDs for
communication and zone panel numbering.
• The COMM LED will flash the number of
devices on the communication bus
• The Zone Panel 1 LED is a white LED
(bottom left image)
• The Zone Panel 2 LED is a blue LED (bottom
right image)
Zone panel 1
Zone panel 2
These LEDs are bright and can be seen at a
distance for easy viewing.
Zone renumbering has no impact on system
operation or zone names. It only swaps the zone
numbering from one panel to another.

Installation Guide
20 18-HD99D1-1A-EN
• If the arbitration of the zone panels are
reversed from the desired numbering, then
press the “Renumber Zone Panels” button
before proceeding with zoning configuration.
• Link will ask if you wish to renumber zone
panels. Confirm by pressing the blue button to
“Switch Zone Panels” or select the option for
“No Change”.
• If proceeding to switch, Link will take a few
seconds to renumber the zone panels and you
will see the LED indicators move positions as
shown below.
Zone panel 2
Zone panel 1
Zone panel 2
Zone panel 1
Zone panel 2 Zone panel 1
Table of contents