Mounting instructions FLORIDA stove Creina d.d.
1. Mounting instructions
1.1. Foreword
Please read these instructions carefully and pay
attention to advices, especially to those for safe
handling.
Before you start with the installation of the stove,
check:
oIf all parts are included (Notify supplier if any of
the parts are missing)
oThe stove for potential damages (pay special
attention to glass, firedoor and coating
protection; Notify hauler, if damages are
found)
oThe functionality of all the movable parts
This manual is not a service handbook. Here
you won't find any instructions on how to repair
the stove.
1.2. Regulations
Following regulations and standards have to be
followed:
oEN 13 40
oState building regulations and provisions.
oFire-protection provisions.
oAll other European, national and local
regulations and provisions that deal with
installation of the stove.
2. Basic requirements
2.1. Installation area
2.1.1. Stove can be installed if:
oInstallation area is big enough to ensure
normal use (operating, cleaning …) of the
stove.
oWithin radiation area of the stove, there are
no load-bearing construction elements (ex.
pillars).
oSufficient air supply is secured.
oThere is at least one door or window that
leads out of the room where the stove is
installed.
oThere is a direct or indirect air connection
with another room.
2.1.2. Stove must not be installed:
oIn rooms, where highly inflammable and
explosive substances or their mixtures are
being manufactured, processed or stored.
oIn rooms that are ventilated and have safety
devices that prevent negative pressure.
oIn rooms that have no adequate air supply for
stove to work properly.
2.1.3. Installation requirements
oStove has to be installed in a way, that
connection parts (chimney flue, air conduit),
when needed of cleaning, are easily
accessible.
oWalls in installation area of the stove, must
be free of electrical and gas installations.
2.1.4. Air combustion conduit
oAir connection for additional air supply to the
room, where stove will be installed, has to
have a cross-section of at least 100 cm .
oFresh air conduit has to have an inbuilt
closing flap, where positions »open« -
»close«, must be clearly visible.
oWhen calculating the necessary air conduit
cross-section, local (elbows, filters etc.) and
line (conduit length) resistances have to be
taken into consideration.
oWhen air travels through operating
combustion chamber, it heats up.
oAir conduit's overflow resistance must not
exceed 4 Pa.
2.1.5. Floor protection
oIf floor, where stove will be located, is not fire
resistant, it has to be protected by a layer of
fire-resistant material (ex. 6 mm thick glass
plate).
oIncombustible floor area in front of the stove
has to be at least 50 cm long, while on the
sides the distance must not be less then 0
cm. (measured from stove walls)
V1.0 Lokaterm™ © 08/08 stran 4