Magic-Pak MCE4 Series User manual

507860-01 Issue 1927 Page 1 of 14
Save these instructions for future reference
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MCE4 Series
Electric Cooling Package Unit
Manufactured By
Allied Air Enterprises LLC
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
Improper installation, adjustment, alteration, service, or
maintenance can cause injury or property damage. Refer
to this manual. For assistance or additional information,
consult a qualied installer or service agency.
WARNING
Table of Contents
Installation ...................................................................1
Operation...................................................................10
Maintenance..............................................................10
Accessories ...............................................................11
Wiring Diagrams........................................................13
The installation of this appliance must conform to the requirements of the National Fire Protection Association; the National
Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical Code Part 1, CSA 22.1
(latest edition) in Canada; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should
be consulted before installation is made. Such applicable regulations or requirements take precedence over the general
instructions in this manual.
CAUTION
(P) 507860-01
*P507860-01*
Installation
These units are not approved for mobile home
applications. Such use could result in property damage,
personal injury, or death.
WARNING
General
These instructions explain the recommended method of
installation of the MCE4 electric cooling unit and associated
electrical wiring.
This unit is designed and approved for use as a self-
contained air-to-air air conditioning system with optional
CLIMATE GUARD™ coated coils.
These instructions, and any instructions packaged with
mating components and/or accessories, should be carefully
read prior to beginning installation. Note particularly any
CAUTIONS or WARNINGS in these instructions and all
labels on the units.
These instructions are intended as a general guide only,
for use by qualied personnel and do not supersede any
national or local codes in any way. Compliance with all local,
state, provincial, or national codes pertaining to this type of
equipment should be determined prior to installation.

Page 2 of 14 507860-01Issue 1927
Minimum and maximum operation conditions must be
observed to assure maximum system performance
with minimum service required. Refer to Table 1 for the
application limitations of the unit.
Table 1. Application Limitations
Outdoor Ambient Air Temperature °F
Minimum DB Maximum DB
Cool Cool Heat
65 115 75
Indoor Ambient Air Temperature °F
Minimum Maximum
DB/WB DB DB/WB DB
Cool Heat Cool Heat
62/57 50 90/72 80
DB = Dry Bulb
WB = Wet Bulb
Location
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
WARNING
For information on wall sleeves and grille accessories, see
the Accessories section.
The design is certied for thru-the-wall or up-to-the wall
(inside wall) installation only. The interior portions of
the unit may be surrounded by a closet with clearances
to combustible material held to 0” at the sides, top, and
front of the plenum. All servicing and cleaning of the unit
can be performed from the front. If installed in a closet
or utility room, provide 25” clearance in front for service
if the door to the room is not in line with the front of the
unit (see Figure 1). Accessibility clearances must take
precedence over re protection clearances.
Units that comply with the maximum cabinet leakage 2% of
rated airow requirements of ANSI/ASHRAE 193 (complies
with IECC 2015) are identied on the rating plate.
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualied service personnel should install or service
this equipment. Installation and service performed by
unqualied persons can result in property damage,
personal injury, or death.
WARNING
For your safety, do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any
other appliance. Such actions could result in property
damage, personal injury, or death.
WARNING
The unit must be installed with approved wall sleeve
and grille accessories for safe operation. Improper
installations could result in property damage, personal
injury, or death.
WARNING
Inspection
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted
on the carrier’s freight bill. Take special care to examine
the unit inside the carton if the carton is damaged. File a
claim with the transportation company. If any damages
are discovered and reported to the carrier do not
install the unit, as claim may be denied.
Check the unit rating plate to conrm specications
are as ordered.
Limitations
The unit should be installed in accordance with all national
and local safety codes.
Limitations of the unit and appropriate accessories must
also be observed.
The outdoor fan is designed to operate against no more
than .10” w.c. static pressure.

507860-01 Issue 1927 Page 3 of 14
Figure 1. Minimum Clearances
ExteriorWall
Wall Sleeve
(one each side)
InteriorWall
Clearances*
MountingStrap
(one each side)
3/4" Plywood Riser
Floor
Front of Unit
Sill Plate
4" Min.
Unit must be supported by platform, which must be
level with sill plate of hole in exterior wall.
Platform (field supplied) -
Side View
Clearance to combustible materials is 0” at the side, top, and front of plenum. If accessibility clearances are greater
than clearances to combustibles, accessibility clearances take precedence.
The front of the unit must be accessible for service. If the unit is enclosed, providing a door or access panel opposite
the front of the unit is the preferred method of providing access. The door or access panel must be at least 30” wide
(centered on the unit) and as tall as the unit.
IMPORTANT
The unit must be installed with approved wall sleeve and grille
accessories for safe operation. Improper installations could result
in property damage, personal injury, or death.
Cabinet
Height
Minimum Unit Clearance
Front* Sides
44” or 48” 4” 1”
56” or 68” 5”
* Listed clearance is using front return with
no front return duct installed. If a return
duct (top or front) is installed, enough
clearance must be provided for the drain
trap installation.
Top View
Supply Duct
Opening
Clearance to
Front of Unit*
Front of Unit
1”
Min.
1”
Min.
Optional Front
Return Opening
May be used with or
without attached ductwork
Return Duct
Opening

Page 4 of 14 507860-01Issue 1927
The outside of the unit may be ush with the face of
the exterior wall, and it should not be obstructed with
trees, landscape materials, or building structure. Unit
can be installed recessed with appropriate wall sleeve
accessories. There is no minimum clearance required on
locating the unit to an interior corner of a building.
If the unit is installed in a residential garage, it must be
located or protected to avoid physical damage by vehicles.
The unit must be installed so that no electrical components
are exposed to water.
This unit must be installed level to allow for proper
drainage of the unit base pan and indoor drain pan.
CAUTION
Wall Sleeve and Louver Grille Installation
Refer to installation instructions included with the wall
sleeve kit and the louver grille kit along with Figure 2 for
guidance in assembling and installing the wall sleeve and
louver grille.
The sleeve is not intended as the sole support for
the unit. An additional support must be provided for
adequate support (see Figure 2).
CAUTION
Installing and Securing Unit to Wall Sleeve
1. Make sure the gaskets attached to the sleeve are not
damaged.
2. Verify divider panel is positioned properly. Refer to
Table 2 for wall sleeves that allow for multiple divider
panel locations.
ASLEEVE**-2 ASLEEVE**-5 Orientation
of Flange
Model Two
Positions
Three
Positions
MCE4-11-09,12,18 Lower Lower Down
MCE4-11-24
UpMCE4-11-30 Upper Middle
MCE4-11-36 N/A Upper
Table 2.
Figure 2. Wall Sleeve and Louver Kit Installed
NOTE: Platform must be constructed so that it is level with sill plate of wall opening.

507860-01 Issue 1927 Page 5 of 14
3. Place the MCE unit into the wall sleeve. Lift leading
end of unit and walk unit onto the sleeve. Once in
the sleeve, lower the unit into position. This prevents
damage to the base pads. Assure that the unit is level
and completely seated against the gaskets on the wall
sleeve. The unit must be supported by a eld-supplied
base platform.
Figure 3. Positioning Divider Panel
Flange Up Orientation
Flange Down Orientation
4. Use the two installation brackets to secure the unit to
the wall sleeve (see Figure 4). The units are shipped
with the brackets placed in the return air compartment.
Hook each bracket into the front edge of the wall sleeve
side. Position the bracket so it can be bent around the
front corner of the unit. Remove one of the two screws
in that position on the unit. Line up one of the holes in
the installation bracket with the screw hole and attach
the bracket to the unit with that screw. Make sure to
fasten tight enough that the seal is maintained. Trim
o excess bracket if applicable.
Figure 4. Securing Unit
Installation
Brackets
Remove and replace screw to secure bracket
(one each side)
Do not screw into the side of the drain pan, or into the
indoor coil or heat strip.
CAUTION
5. Inspect the t up of the unit to the wall sleeve. Verify
that the gaskets of the wall sleeve make a complete
seal to the unit paying particular attention to top and
bottom corners of unit to sleeve seal. Caulk if needed.
Ductwork
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors
of America (ACCA).
Check unit air supply outlet for debris before making
ductwork connections.
It is recommended that supply and return duct connections
at the unit be made with exible joints. If exible ducts are
used, a 6” sheet metal starter collar is required.
The supply and return air duct systems should be designed
for the CFM and static requirements of the job (see Table
3). They should not be sized to match the dimensions
of the duct connections on the unit. The return duct
should be sealed to the unit casing and terminate outside
the space containing the unit.
Optional Front Return
As shipped, units are congured for attaching supply and
return ductwork to the top of the unit. Return air may be
brought in through the optional front return opening. To
open the optional front return and close o the top return
opening, perform the following steps.
1. Rotate knob to release lter access panel and remove
panel.
a. For all units except 3-ton models, position lter
access panel to close o top return opening.
Secure at rear using two sheet metal screws.
Secure in front using knob. See Figure 5.
b. For 3-ton models, eld fabricate a sheet metal
panel to close o the top return opening.
2. Seal panel to top of unit with tape or mastic.
NOTE: If ductwork is attached to the optional front return
opening, provisions to service unit lter must be provided.
Figure 5. Secure Filter Access Panel

Page 6 of 14 507860-01Issue 1927
Airow Performance as a Function of External Static Pressure
Model
Indoor Blower
Speed
0.1 “w.c. 0.2 “w.c. 0.3 “w.c. 0.4 “w.c. 0.5 “w.c.
SCFM Watts HP SCFM Watts HP SCFM Watts HP SCFM Watts HP SCFM Watts HP
*MCE4-11-091*P
(FAN) 355 28 0.04 320 31 0.04 275 35 0.05 230 38 0.05 160 42 0.06
(COOL)† 375 31 0.04 330 33 0.04 285 37 0.05 N/A N/A N/A N/A N/A N/A
(COOL) N/A N/A N/A N/A N/A N/A 390 55 0.07 370 58 0.08 330 62 0.08
0 kW
TAP 4 (HEAT)* 375 31 0.04 330 33 0.04 285 37 0.05 240 40 0.05 180 44 0.06
TAP 5 (HEAT) 465 47 0.06 425 51 0.07 390 55 0.07 370 58 0.08 330 62 0.08
3 kW
TAP 4 (HEAT)* 430 41 0.05 410 45 0.06 385 49 0.07 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 520 58 0.08 500 63 0.08 475 68 0.09 440 73 0.10 400 77 0.10
5 kW
TAP 4 (HEAT)* 525 59 0.08 505 65 0.09 480 69 0.09 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 615 81 0.11 590 88 0.12 560 94 0.13 530 99 0.13 500 103 0.14
*MCE4-11-121*P
TAP 1 (FAN) 355 28 0.04 320 31 0.04 275 35 0.05 230 38 0.05 160 42 0.06
TAP 2 (COOL)†420 40 0.05 380 42 0.06 355 46 0.06 N/A N/A N/A N/A N/A N/A
TAP 3 (COOL) N/A N/A N/A 480 62 0.08 445 66 0.09 415 70 0.09 380 74 0.10
0 kW
TAP 4 (HEAT)* 420 40 0.05 380 42 0.06 355 46 0.06 315 50 0.07 275 54 0.07
TAP 5 (HEAT) 515 58 0.08 480 62 0.08 445 66 0.09 415 70 0.09 380 74 0.10
3 kW
TAP 4 (HEAT)* 430 41 0.05 410 45 0.06 385 49 0.07 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 520 58 0.08 500 63 0.08 475 68 0.09 440 73 0.10 400 77 0.10
5 kW
TAP 4 (HEAT)* 525 59 0.08 505 65 0.09 480 69 0.09 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 615 81 0.11 590 88 0.12 560 94 0.13 530 99 0.13 500 103 0.14
*MCE4-11-181*P
TAP 1 (FAN) 355 28 0.04 320 31 0.04 275 35 0.05 230 38 0.05 160 42 0.06
TAP 2 (COOL)†660 103 0.14 640 109 0.15 610 114 0.15 580 119 0.16 550 124 0.17
TAP 3 (COOL) 725 131 0.18 710 135 0.18 685 140 0.19 660 146 0.20 640 152 0.20
0 kW
TAP 4 (HEAT)* 660 103 0.14 640 109 0.15 610 114 0.15 580 119 0.16 550 124 0.17
TAP 5 (HEAT) 725 131 0.18 710 135 0.18 685 140 0.19 660 146 0.20 640 152 0.20
3 kW
TAP 4 (HEAT)* 430 41 0.05 410 45 0.06 385 49 0.07 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 520 59 0.08 500 63 0.08 475 67 0.09 440 72 0.10 400 77 0.10
5 kW
TAP 4 (HEAT)* 525 60 0.08 505 65 0.09 480 70 0.09 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 615 81 0.11 590 88 0.12 560 95 0.13 530 100 0.13 500 103 0.14
7 kW
TAP 4 (HEAT)* 685 108 0.14 670 116 0.16 645 122 0.16 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 790 153 0.21 770 160 0.21 750 166 0.22 720 172 0.23 700 177 0.24
10 kW
TAP 4 (HEAT)* 790 153 0.21 770 160 0.21 750 166 0.22 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 890 211 0.28 870 217 0.29 850 222 0.30 820 226 0.30 800 230 0.31
N/A: Do not operate unit using this blower speed at this external static pressure.
† As shipped speed for Cooling operation. Blower speed must be eld adjusted to Speed Tap 3 for higher duct static applications.
* As shipped speed for Heating operation. Blower speed must be eld adjusted to Speed Tap 5 for higher duct static applications.
Table 3. Blower Performance (208V or 230V)

507860-01 Issue 1927 Page 7 of 14
Airow Performance as a Function of External Static Pressure
Model
Indoor Blower
Speed
0.1 “w.c. 0.2 “w.c. 0.3 “w.c. 0.4 “w.c. 0.5 “w.c.
SCFM Watts HP SCFM Watts HP SCFM Watts HP SCFM Watts HP SCFM Watts HP
*MCE4-11-241*P
TAP 1 (FAN) 455 41 0.05 420 45 0.06 385 49 0.07 365 52 0.07 320 57 0.08
TAP 2 (COOL)†810 146 0.20 790 158 0.21 780 166 0.22 755 173 0.23 735 179 0.24
TAP 3 (COOL) 870 179 0.24 860 184 0.25 845 194 0.26 815 202 0.27 785 206 0.28
0 kW
TAP 4 (HEAT)* 810 146 0.20 790 158 0.21 780 166 0.22 755 173 0.23 735 179 0.24
TAP 5 (HEAT) 870 179 0.24 860 184 0.25 845 194 0.26 815 202 0.27 785 206 0.28
5 kW
TAP 4 (HEAT)* 555 65 0.09 540 69 0.09 510 73 0.10 480 76 0.10 N/A N/A N/A
TAP 5 (HEAT) 645 88 0.12 630 94 0.13 605 100 0.13 580 105 0.14 550 110 0.15
7 kW
TAP 4 (HEAT)* 775 140 0.19 765 145 0.19 745 150 0.20 725 154 0.21 N/A N/A N/A
TAP 5 (HEAT) 875 184 0.25 865 193 0.26 845 201 0.27 825 208 0.28 800 215 0.29
10 kW
TAP 4 (HEAT)* 875 184 0.25 865 193 0.26 845 201 0.27 825 208 0.28 N/A N/A N/A
TAP 5 (HEAT) 995 253 0.34 980 260 0.35 980 267 0.36 960 272 0.36 900 276 0.37
*MCE4-11-301*P
TAP 1 (FAN) 590 42 0.06 530 48 0.06 430 55 0.07 380 60 0.08 315 65 0.09
TAP 2 (COOL)†1015 152 0.20 985 161 0.22 940 170 0.23 910 177 0.24 875 184 0.25
TAP 3 (COOL) 1115 192 0.26 1080 201 0.27 1045 210 0.28 1015 219 0.29 980 227 0.30
0 kW
TAP 4 (HEAT)* 1015 152 0.20 985 161 0.22 940 170 0.23 910 177 0.24 875 184 0.25
TAP 5 (HEAT) 1115 192 0.26 1080 201 0.27 1045 210 0.28 1015 219 0.29 980 227 0.30
5 kW
TAP 4 (HEAT)* 740 65 0.09 705 74 0.10 640 83 0.11 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 820 81 0.11 790 91 0.12 740 100 0.13 675 109 0.15 600 117 0.16
7 kW
TAP 4 (HEAT)* 860 91 0.12 835 100 0.13 795 108 0.14 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 945 112 0.15 925 122 0.16 885 132 0.18 845 140 0.19 800 148 0.20
10 kW
TAP 4 (HEAT)* 945 112 0.15 925 122 0.16 885 132 0.18 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 1050 141 0.19 1020 151 0.20 980 161 0.22 940 170 0.23 900 179 0.24
*MCE4-11-361*P
TAP 1 (FAN) 680 61 0.08 630 68 0.09 575 74 0.10 525 79 0.11 460 86 0.12
TAP 2 (COOL)†1235 260 0.35 1200 272 0.36 1166 284 0.38 1135 295 0.40 1100 305 0.41
TAP 3 (COOL) 1315 304 0.41 1280 316 0.42 1250 330 0.44 1215 342 0.46 1180 354 0.47
0 kW
TAP 4 (HEAT)* 1235 260 0.35 1200 272 0.36 1166 284 0.38 1135 295 0.40 1100 305 0.41
TAP 5 (HEAT) 1315 304 0.41 1280 316 0.42 1250 330 0.44 1215 342 0.46 1180 354 0.47
5 kW
TAP 4 (HEAT)* 740 75 0.10 695 82 0.11 640 90 0.12 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 815 92 0.12 785 100 0.13 745 108 0.14 700 115 0.15 650 122 0.16
7 kW
TAP 4 (HEAT)* 815 92 0.12 785 100 0.13 745 108 0.14 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 910 117 0.16 880 126 0.17 840 135 0.18 800 143 0.19 750 150 0.20
10 kW
TAP 4 (HEAT)* 1010 143 0.19 980 155 0.21 945 166 0.22 N/A N/A N/A N/A N/A N/A
TAP 5 (HEAT) 1085 175 0.23 1065 187 0.25 1030 198 0.27 995 209 0.28 950 219 0.29
N/A: Do not operate unit using this blower speed at this external static pressure.
† As shipped speed for Cooling operation. Blower speed must be eld adjusted to Speed Tap 3 for higher duct static applications.
* As shipped speed for Heating operation. Blower speed must be eld adjusted to Speed Tap 5 for higher duct static applications.
Table 3. Blower Performance (208V or 230V)

Page 8 of 14 507860-01Issue 1927
Air Filter
All indoor return air must be ltered. A washable lter is
furnished with the unit, located in the return air compartment.
If the optional front return opening is used and a duct is
installed, provisions must be made to accommodate lter
servicing. If a lter is installed at a separate central return
location, then the factory furnished lter must be removed
from the unit.
The lter should be cleaned at least three times during
each of the heating and cooling seasons, or more
frequently if unusual conditions are encountered. To clean
the washable lter, shake lter to remove excess dirt and/
or use a vacuum cleaner. Wash lter in soap or detergent
water and replace after lter is dry. It is not necessary to oil
the lter after washing.
The washable lter may be replaced with a disposable
lter. Table 4 lists lter sizes that t the unit.
Model Number Filter Size
(in.)
*MCE4-11-09*
*MCE4-11-12*
*MCE4-11-18*
18 x 20 x 1
*MCE4-11-24* 20 x 22 x 1
*MCE4-11-30* 22 x 24 x 1
*MCE4-11-36* 22 x 28 x 1
Table 4. Filter Sizes
If an installation is made in which it is more desirable to
mount the lter exterior to the unit, in the return duct work
or elsewhere, the washable lter can be used or replaced
with a disposable lter. If a disposable lter is used, use the
information provided in Table 5 when sizing the disposable
lter.
Model Number Filter Area
(in2)
*MCE4-11-09*
*MCE4-11-12* 250
0MCE4-11-18*
3MCE4-11-18*
5MCE4-11-18*
310
7MCE4-11-18*
10MCE4-11-18* 380
*MCE4-11-24* 420
*MCE4-11-30* 480
*MCE4-11-36* 575
Table 5. Minimum Required Surface Area for
Disposable Filters
Condensate Drain
Provisions must be made to properly drain the indoor and
outdoor drain pans of this appliance.
Indoor drain and outdoor drain connection: 3/4” NPT to
3/4” PVC tting (schedule 40 minimum). Both drains must
be trapped as shown in Figure 6. The drain line should
pitch gradually downward at least 1” per 10’ of horizontal
run to an open drain.
If local codes require the use of metal condensate lines,
do not thread metal ttings into the unit drain pans. Thread
a PVC tting into the unit drain pans and make the eld
connection to the PVC tting.
NOTE: MCE units are designed with a redundant drain
system to handle condensate without the need for a
secondary or emergency drain pan. Should the indoor
coil condensate drain system fail, all water is contained
within the unit and the ow is directed into the unit base
pan. From there it will drain into the condensate riser.
If for some reason the water cannot drain into the main
condensate riser, all water is contained in the unit, and the
design will allow drainage out through the wall sleeve and
louver assembly to the outside of the building.
Use thread sealant on the threaded ttings. Install
threaded ttings by hand only. Do not over torque the
ttings.
Do not thread metal condensate ttings to unit drain
pans.
CAUTION
Figure 6. Condensate Drain Installation

507860-01 Issue 1927 Page 9 of 14
Outdoor Ventilation Air
Units are tted with a panel that seals the return air
compartment at the outdoor air duct. Installers can choose
to remove the factory-installed panel and use the provided
auxiliary panel if introduction of outdoor air is desired.
NOTE: If outdoor ventilation air is introduced, the quantity
of air and conditions of this air must be accounted for in the
load calculations for the unit installation.
The auxiliary panel includes nine knockouts to congure
air ow to installation requirements. Use Table 6 and
Figure 7 to determine which knockouts to remove from the
auxiliary panel in order to achieve the desired air ow. Use
a at head screw driver to remove the knockouts. Set the
factory-installed panel aside for possible future changes.
Outdoor Ventilation Air
(CFM)
*MCE4-11-09*
*MCE4-11-12*
*MCE4-11-18*
*MCE4-11-24*
*MCE4-11-30*
*MCE4-11-36*
Nominal
Indoor Airow 350 400 650 800 1000 1200
Number of Openings
#1 Only 6 7 14 17 19 23
#1 and #2 10 12 21 23 26 30
#1 thru #3 17 19 25 28 30 34
#1 thru #4 23 25 31 37 39 45
#1 thru #5 29 31 40 45 50 56
#1 thru #6 35 37 48 55 60 68
#1 thru #7 40 43 56 66 72 81
#1 thru #8 45 50 68 76 86 96
#1 thru #9 50 54 80 92 98 110
Table 6.
The location of fresh air capable models must conform to
the requirements of National Fire Protection Association
NFPA No. 54 in regards to proximity of forced air inlets
to ue gas terminals. Improper installation could result
in personal injury or death.
WARNING
Thermostat
The room thermostat should be located on an inside
wall where it will not be subject to drafts, sun exposure,
or heat from electrical xtures or appliances. Follow
manufacturer’s instructions enclosed with the thermostat
for general installation procedures. Color-coded insulated
wires (#18 AWG) should be used to connect the thermostat
to the unit.
Figure 7. Auxiliary and Factory Panel for Outdoor Air
Duct
Factory panel
Outdoor
Air Duct
Auxillary panel
with knockouts
1
2
3
4
5
6
7
8
9
Electrical Connections
All wiring must be done in accordance with the National
Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition);
Canadian Electrical Code CSA C22.2 Part 1 (latest edition);
or local codes, where they prevail. Any alteration of internal
wiring will void certication and warranty.
Units are factory wired for a 230 volt power supply. If power
supply is 208 volts, it will be necessary to change a wire
connection on unit transformer from 240 volt terminal to
208 volt terminal as shown on the wiring diagram.
Use wiring with a temperature limitation of 75°F minimum.
Run the 208 or 230 volt, single phase, 60 hertz electric
power supply through a fused disconnect switch to the
control box of the unit and connect as shown in the unit’s
wiring diagram.
The unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the
National Electrical Code ANSI/NFPA No. 70 (latest edition)
or CSA C22.2 Part 1 (latest edition).
Power supply to the unit must be NEC Class 1 and must
comply with all applicable codes. A fused disconnect switch
should be eld provided for the unit. The switch must be
separate from all other circuits. If any of the wire supplied
with the unit must be replaced, replacement wire must be
of the type shown on the wiring diagram. Electrical wiring
must be sized to minimum circuit ampacity marked on the
unit. Use copper conductors only. Each unit must be
wired with a separate branch circuit and be properly fused.

Page 10 of 14 507860-01Issue 1927
Maintenance
Disconnect all electrical power to the unit before
conducting any maintenance procedures. Failure to
disconnect the power could result in personal injury or
death.
WARNING
Periodic inspection and maintenance normally consists of
changing or cleaning lters and (under some conditions)
cleaning the coils.
Filter
Inspect the lter once a month. Replace disposable lter or
clean the washable lter as necessary (a minimum of three
times each heating or cooling season is recommended).
Do not replace washable lter with a disposable lter
unless an installation was made in which the lter was
mounted exterior to the unit (see Air Filter section).
To clean the washable lter, shake lter to remove excess
dirt and/or use a vacuum cleaner. Wash lter in soap or
detergent water and replace after lter is dry. It is not
necessary to oil the lter after washing.
Motors
The indoor and outdoor fan motors are permanently
lubricated and require no maintenance.
Outdoor Coil
Foreign material should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep the coil
clean. To clean the coil, remove the lower access panel
and blow out debris by using compressed air or water. Be
sure power to unit is shut o before using water to
clean the coil.
Care should be used when cleaning the coils so that
the coil ns are not damaged.
Outdoor Base Drain
Foreign material should not be allowed to clog the drain
hole. Inspect and clear drain opening.
Operation
Sequence of Operation
Upon initial “power up” to unit, there is a 3-minute time delay
to the compressor contactor (R to Y). Any 24V interrupt (R,
C) to the defrost control will initiate the 3-minute delay to
the contactor.
Cooling
When the thermostat is in the cooling mode, the O circuit
is powered which energizes the reversing valve. Upon
cooling demand, the thermostat closes circuit R to Y and
G. Closing R to Y closes the unit contactor, starting the
compressor and outdoor fan, and signaling the indoor
blower to run at cooling speed. Upon satisfying cooling
demand, the thermostat will open the above circuits and
open the main contactor, stopping the compressor and
outdoor fan. The unit is equipped with a blower OFF delay;
the blower will continue to operate for a xed 90 seconds
after the thermostat is satised.
Heating
Upon heating demand, the thermostat closes circuit R to
W. On units supplied with heat strips, the sequencers are
then energized and bring on the auxiliary electric heat.
Units with no factory heat installed contain an auxiliary
heat relay that will close, energizing the 24VAC output.
This output can be used to control (not power) an auxiliary
heat source. The W signal from the thermostat brings the
indoor blower on at electric heat speed. Upon satisfying
heating demand, the thermostat opens the above circuits
and stops unit operation.
The unit is equipped with a blower OFF delay; the blower
will continue to operate for a xed 120 seconds (electric
heat) after the thermostat is satised.
NOTE: The 7.2 and 10 kW heats strips oer a W1 and
W2 thermostat connection. Taking advantage of the two
heat strip circuits requires a 3-stage thermostat (Y for heat
pump, W1 for electric heat stage 1, and W2 for electric
heat stage 2). If a 2-stage thermostat is used, “pigtail” W1
and W2 wires together when connecting the thermostat
wires at the unit.

507860-01 Issue 1927 Page 11 of 14
Accessory Nomenclature
Magic-Pak Unit
*MCE4-11-091*P
*MCE4-11-121*P
*MCE4-11-181*P
*MCE4-11-241*P
*MCE4-11-301*P
*MCE4-11-361*P
Polypropylene Louvers
Polypropylene Louver Kit - White (29” Height ) ALVRPWHT-1 ••••
Polypropylene Louver Kit - White (33” Height) ALVRPWHT-2 •••••
Polypropylene Louver Kit - Sandstone (29” Height) ALVRPSAN-1 • • • •
Polypropylene Louver Kit - Sandstone (33” Height) ALVRPSAN-2 • • • • •
Polypropylene Louver Kit - Beige (29” Height) ALVRPBGE-1 • • • •
Polypropylene Louver Kit - Beige (33” Height) ALVRPBGE-2 • • • • •
Polypropylene Louver Kit - Taupestone (29” Height) ALVRPTPST-1 • • • •
Polypropylene Louver Kit - Taupestone (33” Height) ALVRPTPST-2 • • • • •
Aluminum Louvers
Extruded Aluminum Louver Kit (29” Height) ALVRAL-1 • • • •
Extruded Aluminum Louver Kit - Custom Color (29” Height) ALVRAL-1P • • • •
Extruded Aluminum Louver Kit (33” Height) ALVRAL-2 • • • • •
Extruded Aluminum Louver Kit - Custom Color (33” Height) ALVRAL-2P • • • • •
Extruded Aluminum Louver Kit (45” Height) ALVRAL-3 • • • •
Extruded Aluminum Louver Kit - Custom Color (45” Height) ALVRAL-3P • • • •
Extruded Aluminum Louver Kit (45” Height) ALVRAL-4 • •
Extruded Aluminum Louver Kit - Custom Color (45” Height) ALVRAL-4P • •
Impact Rated Louvers
Extruded Aluminum Louver Kit - Impact Rated (29” Height) ALVRALC-1 • • • •
Extruded Aluminum Louver Kit - Impact Rated / Custom Color (29” Height) ALVRALC-1P • • • •
Extruded Aluminum Louver Kit - Impact Rated (33” Height) ALVRALC-2 • • • • •
Extruded Aluminum Louver Kit - Impact Rated / Custom Color (33” Height) ALVRALC-2P • • • • •
Extruded Aluminum Louver Kit - Impact Rated (45” Height) ALVRALC-3 • • • •
Extruded Aluminum Louver Kit - Impact Rated / Custom Color (45” Height) ALVRALC-3P • • • •
Extruded Aluminum Louver Kit - Impact Rated (45” Height) ALVRALC-4 • •
Extruded Aluminum Louver Kit - Impact Rated / Custom Color (45” Height) ALVRALC-4P • •
Table 7. Accessories
Accessories

Page 12 of 14 507860-01Issue 1927
Maximum Wall
Thickness
C
A1
B
D
E
29 1/8
Required Wall Opening
29
Figure 8.
Wall Sleeve Nomenclature
Magic-Pak Unit Dimensions (in)
*MCE4-11-091*P
*MCE4-11-121*P
*MCE4-11-181*P
*MCE4-11-241*P
*MCE4-11-301*P
*MCE4-11-361*P
A B C D E
6” Wall Sleeve Kit
for 29” Louver ASLEEVE6-1 • • • • 6 29 16 16-5/8 29-1/8
for 33” Louver ASLEEVE6-2 • • • • • 6 32-3/4 16 16-5/8 32-7/8
for 45” Louver ASLEEVE6-5 • • • • • • 6 45 16 16-5/8 45-1/8
8” Wall Sleeve Kit
for 29” Louver ASLEEVE8-1 • • • • 8 29 16 16-5/8 29-1/8
for 33” Louver ASLEEVE8-2 • • • • • 8 32-3/4 16 16-5/8 32-7/8
for 45” Louver ASLEEVE8-5 • • • • • • 8 45 16 16-5/8 45-1/8
10” Wall Sleeve Kit
for 29” Louver ASLEEVE10-1 • • • • 10 29 16 16-5/8 29-1/8
for 33” Louver ASLEEVE10-2 • • • • • 10 32-3/4 16 16-5/8 32-7/8
for 45” Louver ASLEEVE10-5 • • • • • • 10 45 16 16-5/8 45-1/8
12” Wall Sleeve Kit
for 29” Louver ASLEEVE12-1 • • • • 12 29 16 16-5/8 29-1/8
for 33” Louver ASLEEVE12-2 • • • • • 12 32-3/4 16 16-5/8 32-7/8
for 45” Louver ASLEEVE12-5 • • • • • • 12 45 16 16-5/8 45-1/8
Thru-The-Wall-Sleeve-Kit ASLEEVE-3 • • • N/A 45 16 16-5/8 45-1/8
Table 8. Wall Sleeves
The unit must be installed with approved wall sleeve and grille accessories for safe operation. Improper installations
could result in property damage, personal injury, or death.
WARNING

507860-01 Issue 1927 Page 13 of 14
Figure 9. Connection Diagram - MCE Without Electric Heater
# 538012-01
Wiring Diagrams

Page 14 of 14 507860-01Issue 1927
Figure 10. Connection Diagram - MCE With Factory Installed Electric Heater
# 538013-01
This manual suits for next models
6
Table of contents
Popular Control Unit manuals by other brands

Coreline
Coreline Fig.223 Wafer Installation, operation & maintenance manual

GEMAR Lumitec
GEMAR Lumitec IRIDIUM 113886 user manual

Shure
Shure A15LA user guide

Crane
Crane CPV36M Series user manual

Honeywell
Honeywell NOTIFIER SCS Series Operation and installation manual

Harman
Harman AMX HPX-AV102-USB-R quick start guide