6
Temperature display
Display
At the power up the unit shows “---” during 3 seconds approximately during which it performs a self check, then the current value
according to the configuration set appears. If the SIM is different from 0 it’s possible to display the instantaneous value by pressing
+ . The unit permanently stores the minimum and maximum values measured during the normal operation. The stored values are
displayed by respectively pressing button or and cleared by pressing button for 1 second.
If the readout exceeds the limits then “OR” is displayed, while in case of probe failure “PF” appears.
Configuration (setup)
Access to the configuration of the unit takes place through the following sequence: switch of the unit (unplug the power cord of the chiller),
keep buttons + pressed then switch on unit again. Scroll through the parameter list with or until you get the desired one, then
get its value displayed with and change it with + or + . Exit from the setup takes place by letting the keypad untouched for
10 seconds.
Param. Value default
SCL Readout scale 01 =°C 02 = °F 01
ACC Resolution 01=1, 02=0.l, 3=max resolution 03
TYP Type of sensor 0, 1 00
LOR Minimum range -199..999 -50
HOR Maximum range -199..999 150
SIM Display induction slowdown 0..100 00
LAD Zero calibration -- -1.0
HAD span calibration -- -1.0
Wiring diagram