Condensing Boiler 37/5/99
INTRODUCTION
These Instructions cover a range of lightweight,
wall hung, gasfired, condensing boilers. The
flue system is roomsealed and fan assisted on
the flue side. The ignition system is fully
automatic.
There are several models with different outputs
- see table for details. An internal programmer
kit is available as an option.
The boiler casing is of white enamelled mild
steel.
The boilers are suitable for connection to open
vented or sealed systems. These systems may
be pumped central heating or pumped central
heating combined with a pumped indirect
domestic hot water circuit. Gravity circuits must
NOT be used.
Adequate arrangements for completely
draining the system, by provision of drain
cocks MUST be provided.
Gas Safety (Installation and Use)
Regulations, 1984 (as amended).
It is the law that all gas appliances are installed
by a competent person (e.g. a CORGI
registered operative) in accordance with the
above Regulations. Failure to install appliances
correctly could lead to prosecution.
It is in your own interest, and that of safety, to
ensure that the law is complied with. The
installation of the boiler MUST also be in
accordance with the current I.E.E.. Wiring
Regulations, the Local Building Regulations,
Building Standards (Scotland), the Bye Laws of
the Local Water Undertaking, any relevant
requirements of the Local Authority, and Health
and Safety document No 635, "Electricity at
Work Regulations 1989".
Detailed recommendations are contained in the
following British Standard Codes of Practice.
Codes of Practice.
BS.6798 Installation of gas fired hot water
boilers of rated input not exceeding 60kW.
BS.5449:1 Forced circulation hot water
systems (small bore and microbore domestic
central heating systems).
BS.5546 Installation of gas hot water supplies
for domestic purpose (2nd Family Gases).
BS.5440:1 Flues (for gas appliances of rated
input not exceeding 60kW).
BS.5440:2 Air supply (for gas appliances of
rated input not exceeding 60kW).
BS 6891 Specification for installation of low
pressure gas pipework.
BS 7074:1 Application, selection and
installation of expansion vessels and ancillary
equipment for sealed water systems.
IMPORTANT. It is important that no external
control devices are directly connected to this
appliance - unless covered by these
'Installation and Servicing Instructions' or
otherwise recommended by the manufacturer.
If in doubt please enquire.
Any direct connection of a control device not
recommended by the manufacturer could
infringe the Gas Safety (Installation & Use)
Regulations, the above regulations and the
normal appliance warranty.
Manufacturer's notes must NOT be taken, in
any way, as overriding statutory obligations.
LOCATION OF BOILER
The boiler MUST be installed on a flat and
vertical non-combustible wall, capable of
adequately supporting the weight of the boiler
and any ancillary equipment.
THE BOILER IS NOT SUITABLE FOR
EXTERNAL INSTALLATION.
IMPORTANT NOTICE.
If the boiler is to be fitted in a timber framed
building it should be fitted in accordance with
the British Gas publication `Guide for Gas
Installations in Timber Frame Housing',
reference DM2. If in doubt, advice must be
sought from the Local Gas Region of British
Gas.
The boiler may be installed in any room or
internal space, although particular attention is
drawn to the requirements of the current I.E.E.
Wiring regulations and, in Scotland, the
electrical provisions of the Building Regulations
applicable to Scotland with respect to the
installation of the boiler in a room or internal
space containing a bath or shower.