Installation and Startup Guide
This document covers the installation of iR-ETN, for the detailed specifications and operation, please
refer to Datasheet, Brochure and Remote I/O User Manual. Please read all warnings, precautions, and
instructions on the device carefully before use.
Install Environment:
Electrical
Environment
The product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the units are installed correctly and that the operating limits
are followed.
(2) Avoid installing units in environments where severe mechanical vibration or
shocks are present.
(3) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts, or where acid gas, such as SO2 exists.
(4) Relative Humidity: 10% ~ 90% (non-condensing)
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the unit on a stable surface during installation. Dropping it or letting it fall may
cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 *1
(2) Warranty Statement *1
(3) iR-ETN *1
(4) Power Connector *1
(5) Spare Clips *2
Installation Instructions
Clip assembly: Insert one side of the clip into the hole on the
case. Press down firmly in the direction shown in the figure
on the right until hearing the clip
snap into the case.
Clip removal: Insert a flathead
screwdriver into the gap on the clip
and then lift up the screwdriver.
Placing a finger on the clip when
lifting the screwdriver can prevent
the clip from jumping away. The clip
can also be removed directly by
hand.
Rail mounting: DIN rail 35mm.
Panel mounting: Use two M4 or #8 panhead screws, mounting hole size is 4.6mm
Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider
the heat from other devices inside the enclosure. The ambient temperature around the unit must be 0
~ 55°C
NOTE: Please do not touch any of the connectors when the unit is powered up and running.
Power Connections
Power Connector Specifications:
Wire AWG: 28~12
Operating Temperature: -40°C ~+105°C
Screw Torque: 3.47 lbf-in (max.)
NOTE: Connect positive DC line to the ‘+’
terminal and the DC ground to the ‘-’ terminal.
Communication Connections
RJ-45
Name
Description
1
TD+
Transmit+
2
TD-
Transmit-
3
RD+
Receive+
4
….
5
….
6
RD-
Receive-
7
….
8
….
Case
iR-ETN series
Installation Instruction
3
5
4
1
2
LED Indicators
L.V LED
L.V LED State
Description
OFF
24V power normal
Blinking
Detect 24V power
ON
24V power error
ENET-RUN/ERR LED
Run LED
Err LED
Description
OFF
OFF
Power off or no power
Blinking
OFF
Modbus TCP communicating
ON
OFF
The device is in the OPERATIONAL state
OFF
ON
Hardware error, communication fault
ON
Blinking
Reset button is triggered
RJ45
Speed LED
OFF
Operating as a 10-Mbps connection
Green ON
Operating as a 100-Mbps connection
LINK /ACT LED
OFF
No link is established.
Blinking
There is activity on this port.
Reset Button
Press and hold the reset button for more than 2 seconds after the unit starts running properly,
and wait until ENET ERR LED blinks. The default parameters are shown below, the settings will
take effect after cold reset.
Item
Description
Default
1
IP Address
192.168.0.212
2
Netmask
255.255.255.0
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Power
Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be
powered by DC power only, voltage range: 24VDC (-15%/+20%), compatible with most
controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Fusing Require-
ments
If the Power LED does not light up immediately after power up, remove power. A resettable
fuse will protect against overcurrent faults in DC circuit and the resetting will take place after a
period of time. Check wiring for proper connections and try to power up again.
High Voltage
A resettable fuse will prevent damage for overcurrent condition however it isn’t guaranteed.
DC voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using the product.
Supply Voltage
Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.
Wire Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the
impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency
dissipation. Typical values to use are 1M Ohm and 4700pF
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and
thereby create an unsafe condition. Furthermore, electrical interference in an operator
interface can lead to equipment start-up, which could result in property damage and/or
physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this
potential safety hazard exists and take appropriate precautions. Although the specific design
steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended Control Standards.
Programming
Considerations
Checks should be placed in the controller to ensure that all writable registers that control
critical parts of plant or machinery have limit checks built into the program, with an out-of-limit
safe shut down procedure to ensure safety of personnel.
DANGER
CAUTION
6
7
IO RUN/ERR LED
RUN LED
ERR LED
Description
OFF
OFF
Power off or no power
Blinking
OFF
IO initiating
Blinking
ON
IO initiation error
ON
OFF
IO working
ON
Blinking
IO module alarm
ON
ON
IO communication fault
Limi
ted Warranty
A copy of the Warranty and Limitation of Liability is contained in the product box. It can
also be found on the Maple Systems website.
1010-1098_rev00_190520

Popular Computer Hardware manuals by other brands

Exsys EX-1012 manual

Exsys

Exsys EX-1012 manual

EMAC PRIMER instruction manual

EMAC

EMAC PRIMER instruction manual

MF DIGITAL Scribe SA series Quick connect guide

MF DIGITAL

MF DIGITAL Scribe SA series Quick connect guide

IBM TSO/E REXX user guide

IBM

IBM TSO/E REXX user guide

Inverto airscreen 5815 IDLA-DONO1-ANDOC-OGW quick guide

Inverto

Inverto airscreen 5815 IDLA-DONO1-ANDOC-OGW quick guide

INNOVASUB DPX-101 user manual

INNOVASUB

INNOVASUB DPX-101 user manual

Smartrise SRU Programming instructions

Smartrise

Smartrise SRU Programming instructions

Axel Falcon 50 FM operating manual

Axel

Axel Falcon 50 FM operating manual

TANDBERG D5018501 Hardware user manual

TANDBERG

TANDBERG D5018501 Hardware user manual

NXP Semiconductors freescale TRK-S12ZVHY64 quick start guide

NXP Semiconductors

NXP Semiconductors freescale TRK-S12ZVHY64 quick start guide

ekwb ASUS Z9PE-D8 manual

ekwb

ekwb ASUS Z9PE-D8 manual

Thermaltake TH360 ARGB Sync installation guide

Thermaltake

Thermaltake TH360 ARGB Sync installation guide

Behringer EXPANSION CARD X-DANTE quick start guide

Behringer

Behringer EXPANSION CARD X-DANTE quick start guide

Wincomm WPC-765 user manual

Wincomm

Wincomm WPC-765 user manual

Allied Telesis AT-SPZX80 specification

Allied Telesis

Allied Telesis AT-SPZX80 specification

Linear Technology LTC3718 quick start guide

Linear Technology

Linear Technology LTC3718 quick start guide

STMicroelectronics ST62GP-EMU2 HDS2 Series user manual

STMicroelectronics

STMicroelectronics ST62GP-EMU2 HDS2 Series user manual

Alphacool EISBLOCK AURORA ACETAL GPX-N RTX 3090/3080 manual

Alphacool

Alphacool EISBLOCK AURORA ACETAL GPX-N RTX 3090/3080 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.