Marconi LORAIN RHM800E50 User manual

I
I
I
I
I
~
I
I
I
I
I
~1
I
~
I
I
I
I
I
I
I
LORAIN@
MODEL
RHMSOOE50
RECTIFIER
SPEC. NO. 548502500

MARCONI@,
LORAIN@,
SUB-CYCLE@‘, and Vortex@
are trademarks of Marconi Communications Inc.
02000, Marconi Communications Inc.
.
.
.
.
-
--
--...
-._.
.-
..-.
COMMUNICATIONS AND CONTAINS CONFIDENTIAL AND
PROPRIETARY INFORMATION OWNED BY MARCONI
COMMUNICATIONS. ANY COPYING, USE OR DISCLOSURE
OF IT WITHOUT THE
WRlll-EN
PERMISSION OF MARCONI
COMMUNICATIONS IS STRICTLY PROHIBITED.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I

I
Section 2992
Issue July 2000

Section 2992
Issue July 2000
Marconi Page 2 of 2 I

R
ELTEC
Power Products
Section 5737
Issue
Bl,
September
9,1998
ADDENDUM
INSTALLER’S CONNECTIONS
INSTALLER’S INFORMATION NOTES
FOR
LORAIN@
RECTIFIERS
Remote voltage sensing lead connections should be made to the rectifier side of any
battery protective or disconnect devices present.
If a temperature compensation module is used to regulate rectifier output voltage, the
temperature compensation module battery connections should also be made to the recti-
fier side of any battery protective or disconnect devices present.
CAUTION
Turn
ofl
all
rectifirs
before
removing any leads
from
a previously installed
battery charge
tem-
perature compensation module.
Power Products
/
1122 F Street
I
Lorain.
Ohio 44052-2293
/
(440)
288-1122
In Canada:
RELTEC Canada
122 Edward St.
/
St. Thomas, Ontario N5P
122!
(519) 631-0780
In
Mexico:
Productos
RELTEC de Mexico S.A. de
C.V.
Apartado
Postal 77001 I Mexico 10
D.F.,
MX 11200
I(525)
576.6277
~&RELTEC@

LORAIN
PRODUCTS Section 5350
Issue Al, January
30,1992
ADDENDUM
PREPARATION FOR
SHUTDOWN
LORAIN
o
MODEL
RL
AND RHM
SERIES
RECllFlERS
This instruction manual contains various testing, adjustment, and maintenance procedures in which the rectifier
will be shutdown either before or during the procedure. Before
perforn+ng
any of these procedures the load sharing
lead if installed must be removed using the following procedure then reinstalled after the test or adjustment is made.
If the load sharing lead is not removed during these procedures there is a potential for service interruption.
CAVTION
Before
I-emoving
the
?-sctifmrfivm
swuicc.
pnnkions
should be made to insure
that
power
00
critical
&adsisMtintemtpted+andthataryextemalo&?iCzalwme
associated with the
recti$ier
ewe
disabled, if possible. If the extended
alaross
cannot be disabled at the
remote
location, the
appropriate
personne
I
dwaZd
be
notified
to disregard
wag
@ice
alarms
e.ztendedfmm
the rectifier
while
this procedure is in
progress.
If
the
load must be
mdUained
while the
r-e&&r
is
removed
frmn
service, the folIowing
considemtions
should be made:
a)
lf
the rectifier is operating in parallel with one or more additional rectifiers, can the remaining rectifier(s) power
the load? If not, the load must be shutdown or an alternate DC source must be used.
b)
tf a battery is to be used to provide load power during rectifier
;hutdown,
is the battery fully charged and
capable of powering the load for the time required to make the adjustment.
1)
Place the AC INPUT circuit breaker to the OFF position.
2)
Refer to
the
Power Data sheet for location of the load sharing lead
3)
Disconnect the load sharing lead from the terminal block and insulate exposed end.
4)
Restart the rectifier by referring to the rectifier instruction manual starting and stopping section.
5)
Perform the desired test, adjustment, or maintenance procedure in the rectifier instruction manual.
6)
When the test, adjustment, or maintenance procedure is complete place the AC INPUT circuit breaker to the
OFFposition.
7)
Reconnect the load sharing lead removed in en earlier step.
8)
Restart the rectifier by referring to the rectifier instruction manual starting and stopping section.
9)
This completes the procedure.
Page 1

I
Section 5350
I
LOrain
kdUCt5
I
1122 F Street I
Lorain,
Ohio 44052-2293
I(216)
288-1122
,n Canada :
RELTECCanada
122 Edward St. /St Thomas, Ontario
N5P
122
/
(519) 631-0780
I”
Mexico
:
Productos
brain
de Mexico
S.A
de C.V.
Apartado
Postal 77001
I
Mexico 10 D.F., MX 11200
I(9OS)
5768277
P
e
RELTEC”
R
Page 2
I
I
I

RELTEC
Section 4387
Power Products
Issue
Fl
, August 4.1997
LORAld
MODEL
RHM8OOE50
RECTIFIER
SPEC. NO. 548502500
CONTENTS.
_
_
.
_
_
.
_
_
. . . . . .
_
_
.
_
. . . . . . . . . .
PAGE
CONTENTS
(CONTD)
................
PAGE
1.
2.
3.
4.
5.
6.
DESCRIPTION
.........................
1
General
..............................
1
TESTAPPARATUS
.....................
2
INSTALLATION.
.......................
2
Electrical Connections.
..................
Alarm and Control Connections.
...........
Initial Startup and Checkout.
..............
4
OPERATION
..........................
3
StartingandStopping
...................
7
Controls and Indicators
..................
7
Metering.
.............................
8
Float Charging
.........................
8
EqualizeCharging
......................
8
Automatic
Rectller
Shutdown
.............
8
Ripple Regulator Circuit.
.................
9
Batteryless Operation
(
M
Option).
.........
9
Cooling Fans and Temperature Sensors
.....
9
Fuses
................................
9
Circuit Cards
..........................
9
ADJUSTMENTS
.......................
9
General
..............................
9
FloatVoltageAdjustment
.................
10
EqualizeVoltageAdjustment
..............
11
Current Limit Adjustment
.................
12
LowVoltageAlarmAdjustment
............
12
High Voltage Alarm Adjustment.
...........
13
LowCurrent
Ahrm
Adjustment
............
13
OvervoltageShutdownAdjustment
.........
14
LoadSharing Adjustment.
................
15
Ripple Regulator Adjustment.
.............
18
CIRCUIT DESCRIPTION
.................
16
General
..............................
18
AC Input Circuit
........................
16
PowerSupply Assembly
PSA-A8.
..........
17
PowerCircuit
..........................
17
Voltageand Current RegulationCircuitry.
....
17
Voltage Reference and Error Detection
......
17
Current Sensing and Current Regulation.
....
18
Pulse Generation and Phase
Control Circuits.
........................
18
Current Walk-in Circuit.
..................
21
Negative Load Sharing
Circuk
.............
21
Afarm
Circuits.
.........................
22
Ripple Regulator Circuit Card Al 1.
.........
23
Fuse Alarm Circuit
......................
23
Temperature Sensing Circuit
..............
23
7.
TROUBLESHOOTING
...................
24
General.
..............................
24
Fauit
Isolation Chart Use
.................
24
Testing Precautions
.....................
24
Repair and Replacement Information.
.......
24
TestProcedures.
.......................
31
8. MODEL DATA
.........................
37
APPENDIX
1. DESCRIPTION
General
1.1
These
LorafnG
Rectifiers operate from 60 Hz three
phase
input.
to maintain a battery in a fully charged condi-
tion while powering a
load.
The ModelRHMEWE50 Rec-
tifier can be operated from
480
VAC input power.
1.2 Float
Charokra;
This rectifier provides constant
outputvoltage; therefore, outputcurrentremains equal to
load current as
long
as load current does not exceed a
predetermined. adjustable value. This mode of operation
is known as float charging. Since, in normal operation,
Page 1

Section 4367
the battery is not required to furnish load
cunent,
it
remains in afulb charged condition.
1.3
Faualffe
Charainq
If a higher DC voltage is
required to equalize the charge on all battery cells. the
FLOAT/EQUALIZE
switch
can be operated
focally
to
obtain higher equalize charge
voftage.
The
equal&
function may also be controlled from a remote location if
desired.
Description
Power supply
Model
Variable Power
Supply
(O-60 VDC at 10 amps) or
eauivalent
1.4 Current
Limftins;
When an AC power failure
causes battery discharge. or
if
a DC overload occurs, an
output current limiting circuit prevents the increase of
output current above a predetermined
vafue.
stable from 15 ohms
)52
ohms; 50 KW
. .
I
DCAmmeter
ACAmmeter
I .
O-20 amps DC
1
O-60
amps AC
1.5 Parallelim~
This rectifier is equipped
wbh
an
automatic currentliittmg circuit
which
enables
patallel-
ing
with
any other battery charger which can be
adjusted to the same output voltage. In
addition.
a
forced load sharing circuit is furnished
which
ensures
pmportllnal sharing of load between paralleled
rectffi-
ers
with
compatible negative bus load
sharing
circuits
tien
interconnected
with
external load sharing wiring.
Table 2-1
Test Apparatus
1.6 Ovefvoltaoe
Shutdown: If
rectifier
output
Voltage
increases beyond a preset value while delivering greater
than 3% of rated output current, a circuit trips open the
AC
input
contactor
to disable rectifier output.
proper component cooling during operation. Tempera-
ture of the air entering the cabinet must not exceed
+wc
(+122’F).
2. TEST APPARATUS
2.1
Refer to Table 2-1 for a
lff
of tools and test
equfp-
ment that
is
suffffient
to
perform
any test or adjustment
procedure detailed
in
this
instructkm
manuaf.
3.5
Wiring:
All wiring and branch circuit protection
shoufd
follow
provisions of the current
edition
of the
National
Electtic
Code. Referenced to the 1996
edition
for
specific
requirements am:
3.
INSTALLATION
Article
240-6 Branch
Circuit
Rating
3.1
Equipment placement at the
central
office
loca-
tion should be given
consfderation,
as discussed in the
following paragraphs.
Table 310-16 (75°C) Ampacity of Power Conduc-
tors
mm
32
Wirtna
Considerations: Location of the
rectffier
should
be chosen to
mfniifze
required lead
lengtfts
for
both AC input and DC output. Optiium
equipment
per-
formance and cost effectiveness of thefktalfatffn can
bo
realized
by
proper
location Of
the
rectifier.
The
difiet
operateafnrm
AC
UoltW
Capabk
of
prodvdng
-.
perhaps
fatal.
electrical
shock.
Bejim
amlmem2ing
installation.
ensum
that AC and
DC
sources
an?
com@et&~
disconnected
or
disabled.
3.3
Mountino
Reouirementx
Thii
mctlfler
is
designed for floor mounting
onfy.
The Cabffet base con-
tains four mounting holes
which
accept
II2
inch
dff-
ter
bofts
for securing therectiier
in
fts
mounted
positlln.
Refer to the Power Data sheet for further information.
3.4
m
All
ventitatffn
open-
ings in
tfte
rectifier cabinet must
remain
unobstructed for
3.6
General: To gain access to input, output, and
control terminals,
loosen
the
captive
fasteners securing
the meter and control panels.
These
panels
pivot
open
on separate hinges.
lf
less
restricted
access to input
and output terminals is required, remove the Phillips
type screws securing two removable panels immedi-
ately above the meter and control panels.
Page 2

I
I
I
I
I
I
1
I
1
I
SI
I
I
I-
I
I
I
I
I
3.7
Input Connections: Connect the three phase AC
60 Hz, power leads at terminals
Li
. L2 and L3 on
con-
tactor
Kl at the
left
side of the rear panel.
3.8 Output Connections: Connect DC output leads to
output terminals +BAT. and -BAT at the right side of the
rearpanel.
3.9
Earth
Ground
(Green
Wire) Connections: A
frame ground lug (GND), located near contactor
Ki.
must be connected to an earth ground (green wire). Do
~connect
to power system neutral.
Alann
and Control Connections
WARNING
Polarity of the
uo1tage
se&g
leads is
critl-
cd.
when connecting
these
leads.
verifi
con-
nectlans
can?fully
to
assure
em-rect
polarity.
terminal
If+)
and
U-1
on
terminal board
TB3
OPERATION
3.10 Local or Remote
Voltaae
Sensing:
Terminals 1
(positive) and 2 (negative) on terminal board TB3 are
provided as
v&age
sensing
terminals.
These terminals
may be connected at the output of the rectiiier or
extended to sense
the
voltage at a remote location. To
achieve the most effective regulation of output voltage,
the sense leads should be
exiended
to the battery or
power board at which regulation is required.
The
high
w&age
shutdown
cfrndt
is
connected
acmss
the output
Idage
leads.
3.11
Load
Sharinq:
This rectifier is equipped
with
a
negative bus
load
sharing
circul
which enables
it
to
divide
the load in proportion to the
output
current
ratings
wlh
any
oMer
LORAIN
RL or RHM
Series
rectifier of
the same output
v&age
rating. When
both
rectifiers
have compatible load sharing circuits, a load sharing
connection
shoufd
be made between the load sharing
terminals of each rectifier. The load
sharfng
terminal of
this
rectifier
is located at terminal board TB3 terminal 3.
Refer.to
the Power Data Sheet for recommended
size
of
the load sharing lead and terminal
bkxk
capacity. For
proper operation. if is essential that each
rectffier
be
adjustedfor proper
output
voltageand load sharingloop
voltage. Refer to the ADJUSTMENT section for detailed
information.
3.12
Remote
Eaualize
Control: The equalize mode of
operation can be remotely controlled by providing a
Section 4367
closed circuit between terminals 4 and 5 of TB3. or by
providing
positive
battery voltage at terminal 4 only. An
open
circus
between these terminals or removal of posi-
tive battery voltage from terminal 4 restores
OpemtiOnaf
mode control to the FLOAT/EQUALIZE switch on the
rectifier front panel.
3.13 Phase Loss/Reduced Load Alarm: If for any rea-
son, rectifier experiences a high
ripple
condition caused
by an AC input phase loss an alarm is activated and the
rectifiers output
voltage
and current will be at a reduced
level. Extended alarm contacts are
acfiitad
to provide
closed loop circuits between terminals 26 to 27 and 29
to 30 of terminal block TB3. while open loop circuits are
provided between terminals 25 to 26 and 26 to 29 of ter-
minal
blodc
TB3. During
normal
operation closed loop
circuits are provided between terminals 25 to 26 and 26
to 29 of terminal block TB3. while open loop circuits are
provided between terminals 26 to 27 and 29
to
30 Of ter-
minal block TB3.
3.14
Rectaier
Fail
Alarm:
During normal
rectiiier
oper-
ation, posttiie battery is provided at
T83
terminal 12 to
provide an
exlemal
normal operation indication. If a
rectifier failure
condiikn
occurs,
positiie
battery is
removed
from
TB3 terminal 12 and applied to TB3 ter-
minal 10 to actuate external rectifier fail alarms. A recti-
fier failure condition includes the following operational
modes or alarm conditions:
a)
b)
C)
d)
e)
f)
9)
t-4
High voltage alarm
Lowvoltagealarm
Lowcurrenta!arm
Partial
load
current
limtt
operation
Fan fail alarm
Heatsink
over-temperature
alarm
Fuse alarm
Manual or automatic removal of AC power,
includingcommercialpowerfailure
condiiion
rf
closed loop actuated
almms
are desired
dfscon-
nect
and insulate
thejumper
lead
fmm
TB3
termi-
nalll.
C&sedlooprecti@erfailalarmisthen
provided
at
lB3
termfnals
IO
to
1 I during a
recti-
fierfkil
condftion.
Page 3

3.15
End Cell Switch Inhibit: A
positive
battery control
signal
fs
available at
TB3
terminal 13 to
inhtti
activation
of an automatically controlled end cell
switch
during nor-
mal rectifier operation. If a
low
current ahrm occurs in
the rectifier, this control signal is automatically removed
from
terminal 13.
3.16
fj&
A
positfve
battery
alarm
signal is present at
TS3
terminal 14 if rectifier shutdown results from a high
output voltage condition.
3.17
LCA:
A
poskfve
battery alarm signal is present at
IBS
terminal 15 during a
low
current alarm condition.
3.18
m
Positlive
battery to TB3 terminal 16 is nor-
mally supplied through a factory installed jumper wire
between
terminals
16 and 20.
Positive
battery at termi-
nal 16 of
TE3
is required for AC
input
power
contmf.
If
rectifier
startffg and stopping is required from a remote
location or automatic control
device.
disconnect and
insufate
the jumper wire at TB3 terminal 16. Connect
positffebattery to terminal 16 through the remote
switch
or control device.
3.18
Voftmeter
lndicatffa
O~tiin:
Connect terminals
17 and 16 of
TD3
with
a jumper wire if front panel
voft-
meter
indfff
of battery
voftage
is desired when
rectii
fier
fs
turned
off.
lf
voftmeter
indication
of zero
volts
is
desired
with
rectifier turned off, do not connect jumper
to
teninals
17
and
18.
330
Float
and
Eaualiza
Mode
Indiitkms:
When
mc-
tiier is operating in
ffoat
mode,
positive
battery
is
avafl-
able at
TB3
terminal 19. When the equalize mode is
selected,
positfive
battery is removed from TD3 terminal
19 and supplied at terminal 21.
3.21
O~tiinal
Auxifffw
Power
Surxrlv:
If. due to a pro-
longed AC input power
failure.
the associated battery
discharges to below 36 VDC, the
rectifier
will be unable
to restart. To
permit
restartiig
the
rectifiir
in
thff
went,
a customer-furnished
auxiliary
49
voft
power
supply
may
be connected to terminals 1 (+) and 2
(-)
of
auxiliary
power supply
tenfnal
bfodc
TM.
TBI
is located on
insfde
the rectifier cabinet on the rear wall. The
auxil-
lary
power supply must be
capabfs
of
supplyiig
IO
amperes.
. .
m
and
CheckoUt
322
This
mctffier
was completely tested and adjusted
by the manufacturer before
sh@ment:
however, the
installer should perform the following
initial
checks to
insure proper equipment operation after
installatfon
is
completed.
Page 4
a) Initial
Preoaration
1)
2)
3)
4)
Place the HVSD and POWER
switches on the front panel to the OFF
position.
Place
the
FLOATIEQUAL-
IZE
switch
to the FLOAT position.
Open the front access panels by loos-
ening the captive fasteners, then
locate battery disconnect link
52.
Remove this link
from
its
receptacle.
Check to insure
mat
all
fuses are
securely installed in their fuseholders.
Any tape and packing materials used
in the interior of the
rectifier
for ship-
ping purposes should be removed at
this time.
Connect all input. output, and control
wiring
in accordance
with
the Power
Data sheet. Refer to Paragraph 3.06
forfurther wiring information.
b)
lnltial
Startup Procedure
DANGER
Steps
1J
through
4)
must be
pelf-d
exactly
aspr-#st?ntedintheseinstluctions.
Thelecti-
fuzrmustbsstMedoffbatteqtochorgethe
filter capacitor8
before
installing
BATrERY
DISCGNNECT
Iink
s2.
Installing
the
discam-
nsct
link
b&m?
charging the
capafitors
con
result
in
permnal
ir$wy.
equipment
damclge.
andb&wn#zsesintherect@z
1)
If reference leads are extended to the
battery,
perfom
the
folfowfng
steps:
4
B)
C)
Remove the local sensing
leads from their storage termi-
nals on
circuft
card
A9.
Working
with
one lead at a
time, disconnect the extended
reference leads
from
terminals
1 and 2 of
TB3
on
circuit
card
A9.
Temporarity
insulate these
leads.
Connect
the
local sensing
leads to
TBS.
terminal 1
(+)

and
tenninal
2
(-).
Insure that
polarity is correct.
D)
Install the M option capacitor
assembly. Part No.
4251-014-
00. on the appropriate edge
connector of regulator and
alarm
circuit card A7. Refer to
Figure
3-l.
Insure that the external AC protective
device is pmperiy sized for
rectffier
input requirements. Close this device
to
apply
AC input power to the recti-
fier.
Section 4387
3)
Place the HVSD circuit breaker toggle
and the POWER rocker switch to the
ON
posltn.
The rectifier should
start, although the LOW CURRENT
ALARM and an extended
rectifier
fail
alarm
may be activated.
4) Wan
for the
vonmeter
on the rectifier
front panel to indicate 52
vofts.
At this
time, insert BATTERY DISCONNECT
link
S2.
5)
Place the POWER switch to
the
OFF
position.
lf
reference leads extended
to the battery or load are required,
p&on-n
the following steps. If internal
reference only is required, disregard
I
REGULATOR AND ALARM CIRCUIT CARD A,
0
HINGED END
CONTROL AND INDICATOR PANEL
(INTERIOR
SURFACE)
Figure
3-I.
Capacitor Assembly Connector Location
Page 5

Sectbn
4387
Steps a) through
c)
which follow, then
proceed with Step 6).
DANGER
If the
n?cti~
is
connected
to
a
battery,
uolt-
age is p-t at
the
local
and extended
refer-
ence&?Qds.
-clueinthefol&wing
steps that the
&ads
are not accidentally
shorted together
or
allowed
to
touch
cabinet
parts
of
ang
other
electriCal
tenniIIations.
AC
u&cl@?
copab&
Of
producing
sf2VW-e.
per-
haps
fiatal
electrical
shock
is present at input
contactor
Kz
E.cercise
caution that acciden-
tal
bodiZy
contact
1~6th
any
electrical
termina-
tirm
do&
not
occur
A)
B)
C)
Disconnect and temporarily
insulate the local reference
leads from TB3, terminals 1
and 2.
Working with one lead at a
time, connect the remote sens-
ing leads to
TB3,
terminal 1
(+)
and 2
(-).
Insure that
polarity
fs
COWSCt.
Remove the temporary
lnsula-
tion from the
local
reference
leads. and connect these leads
to the storage terminals on cir-
cuit card
A9.
6)
If the
rsctfffer
is used in charging a
battery, remove
the
M
option
caps&
tor assembly from
its
edge connector
on
regufator
and
afarm
circuit card
A?.
7)
Place the POWER
switch
to the ON
posbii.
The
rectffff
should start
and
defier
output voltage
wfthin
the
rengeof48t054VDC.
8)
Page 6
The
ftoat
output voltage of the
rectffffr
shoufd
be
chedmd
and
adjusted to
meet bad
condfins.
Unless other-
wise specified. the
rectiiier
has been
factory adjusted to pmvfde 52.08 VDC
during
float
operation.
This
is based
on a
float
charge of 2.17 volts per cell
for a
24cell
battery. When charging a
23cell
battery, or when a higher or
lower voltage per cell is desired. the
float output voltage can be changed
by adjusting the FLOAT ADJUST
potentiometer, accessible through a
hole
in
the front panel of the
rectllier.
Turn
the potentiometer adjustment
screw slowly
cfocfovise
or counter-
clocbwise
as necessary.
Voltage
should be monitored at the battery
while adjusting float output. The recti-
fier thereby compensates for distribu-
tion losses. and the battery remains
fully charged.
9)
Operate the rectifier
FLOATIEQUAL-
IZE switch to the
EQUALfZE
position
and note the
equalize
output voltage.
Unless otherwise
specffied.
the recti-
fier has been factory adjusted to pro-
vide 54 VDC during equalize charge
operation. This is based on an
squal-
ize charge of 2.25 vats per cell for a
24cell
battery. When charging a 23-
cell battery, or when a higher or lower
voltage per cell is desired, the
equaf-
ize output
voltage
can be
changed
by
adjusting the EQUALIZE ADJUST
potentiometer, accessible through a
hole in me front panel of the rectifier.
Turn
ms
potentiometer adjustment
screw
slowfy
&&vise
or
counter-
clod&se
as necessary.
voltage
should
be monitored at the battery
while adjusting
equafffe
output,
thereby allowing the rectifier to com-
pensate for distribution losses.
Return me
FLOAT/EOUALIZE
switch
to the FLOAT
pktlln.
10)
Chsctr
the rectifier current limit Cir-
cuitry by
loading
the
rectffer
to at
least
f20%
of the rated output of the
unit.
lf
the existing load is less than
rated bad. a resistive test bad may
be
connected
to me DC
OutpUt
termi-
nals of the rectifier. The
rectifier
should limit is output current at 110%
of rated output. If adjustment is
required, refer to Paragraph 5.66 of
this
manual. Remove the test load
after
chech
or adjustment.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I

11)
Before placing the
rectifier
into ser-
vice. refer to Table 3-l and note the
factory settings of the overvoltage
shutdown circuit and the high and
low
vobge
alarm circuit. If these factory
settings are acceptable, the rectifier
may be placed into service. If read-
justment of these circuits is required
to meet customer requirements, fol-
low
tie
appropriate adjustment proce-
dure referenced in Table 3-1 before
placing the rectifier into service.
Adjustment Factory
Setting
Adjustment
Procedure
Pam. No.
Overvoltage
Shutdown
55VDC
I
5.10
I
1
Hig;;Kt
1
57.6VDC
1
5.6
)
Low voltage
Alarm
47.15VDC
5.7
Table 3-l. Shutdown and Alarm Levels
4.
OPERATfON
4.1
Normal Start and
Stoo:
The
rectifier
may be
started or stopped locally by
pfacfng
the HVSD and
POWER controls to
the
ON or OFF
position,
respec-
tively.
4.2
Remote Start and
Stoo:
If remote starting and
stopping control is
.desired.
allow the HVSD and
POWER controls on the front panel to
remain
in fhe ON
position.
Applyins
or removing
positive
battery at
teimi-
nal
16 of
TB3
starts or stops the
rectifier.
respectively.
4.3
Startina
After AC Power Failure: The
rectifier
restarts automatically following commercial AC power
failure if the HVSD and POWER
conbuls
are in
the
ON
position and
positfive
battery is applied to TB3 terminal
16 at the time of power restoration.
Section 4367
rf
battery
voltage
dfscluuges
below 38
uolts
DC
dur-
ing
on
extended commercial
AC power
failure. the
rech@r
wfU
be
w-table
to
restart
automatically
unless an
autihy
power
supply
is
connected to
termfnal
block
TBI
(see
Pam
3.21).
If
an
cuuciliary
power
supply
is
a
connected to
TBI.
refer to Test
Procedure 9
in
Chapter 7.
Tl?OUBLESHOOTlNG.
for
a
starhlp
procedure in this
event
Controls and Indicators
4.4
The following controls and light
emining
diode
indicators control the operation and indicate the status
of the
rectffier.
All controls and indicators are located on
the
rectiiier
front panel unless otherwise noted.
a)
b)
c)
d)
*I
HVSD Circuit Breaker: This circuit breaker
operates in conjunction with the POWER
switch for starting and stopping the rectifier
and normally remains in the ON position.
The
circuit
breaker contains a trip coil which
is energized in case of a high output voltage
condition, thereby releasing the AC input
contactor which removes AC input power.
POWER Switch: This rocker switch. located
adjacent to the HVSD circuit breaker, is used
to start or stop the rectifier by
pfacfng
it to
the ON or OFF position, respectively.
BAlTERY DISCONNECT Link
52:
The dis-
connect link inserts into a mating receptacle
located at the upper right portion of the rear
panel inside the rectifier. Access is gained
by opening the meter and control panels.
The link serves as a convenient method for
connecting or disconnecting
me
battery to or
from the output circuits of the rectifier.
FLOAT/EQUALIZE Switch: When this switch
is
fn
the FLOAT position, sufficient voltage is
provided to maintain the battery in a fully
charged
con&ion
while supplying load
demands. When this switch is
pfaced
in the
EQUALIZE position. the rectifier output volt-
age is increased to
equaliie
me charge of all
battery cells. Refer to
Paa.
4.6.
POWER ON
IndicatoC:
Illuminates when the
AC input voltage is present and the HVSD
and POWER controls are placed in the ON
position.
Page 7

Section 4367
r)
9)
HIGH VOLTAGE ALARM Indicator:
lllumi-
nates when
the output voltage increases to a
predetermined adjustable high
voltage
alarm
value. The high voltage alarm circuit moni-
tors output voltage continuously; therefore,
thisalarmis operational even when the recti-
fier is turned off.
LOW VOLTAGE ALARM Indiitor: Illumi-
nates when the output voltage decreases to
a predetermined adjustable
low
voitage
alarm value. The low voltage
a&m
circuit
monitors output voltage continuously; there-
fore, this alarm is operational even when the
rectifier is turned off.
The LOW VOLTAGE ALARM
indicator
may
illumi-
nate
duirq
a battery recharge
condition
$the
recti-
/ier
operates in the
current
limiting
mode.
and
n?duces
output
udtage
lzccordfngly.
lx&
is
normal
opemtim.andthe&rmwiUextinguishasthebat-
tery
udtage
trl-es.
h) LOW CURRENT ALARM Indiitor: Illumi-
nates when the
rectffier
is operating and
supplying less than 0.5% of
tated
output cur-
rent or when the
rectnier
is turned off.
0
FUSE ALARM Indicator: Illuminates if one
or more fuses
Fl
thmugh F4 should open.
j)
FAN FAILURE ALARM
Indiftor:
fifumf-
nates
t
cooimg
fans El or
82
should
fail.
Matwinq
4.5 A DC
ammeter
and a DC
voftmeter
indicate
reck-
fier output current and voltage. respectively.
SimCe
the
voltmeter is connected acmss the reference leads, this
hater
indicates battery voltage if remote
Sensing
is
Used.
Float
cherpiaa
4.6 This
rectifier
provides
conetant
output voltage;
therefore, output current remains equal to
load
current
as long as load current does not exceed the current
liik
setting. This mode of operation is known as
float
charg-
ing. In normal operation. the
battery
is not required to
furnish toad current and remains in a
fully
charged con-
dition.
Page 6
NOTE
IJ
the current
demand
by the
load
exceeds the cur-
rent limit setting. the
battery
is required
tofurnish
the
dtQI&ertce
and subsequently begins discharg-
ing.
Equalize
CharajQg
4.7
Higher charging voltage is sometimes required to
equalize the charge of all battery cells, or to recharge
the battery as quickly as possble
foflowing
commercial
AC power failure. To obtain this voltage, operate the
FLOAT/EQUALIZE
swkch
to
EQUALlZE
positffn.
To
restore usual float operation, operate the
switch
to the
FLOAT position.
4.6
The equalize function of the
rectifier
can
also be
initiated
from
a remote location.
if
desired. (Refer to
Power Data Sheet.) When the
equalffe
function
is con-
trolled remotely, the FLOAT/EQUALIZE switch on the
rectlier
is disabled.
W-G
Do not supply
eqialize
voltage
for
a
longer
period than
necesory.
I’mlonged
higher
charya
udtage
wiII
oerchaqw
the
battery
cells and reduce battery life.
4.9 Occurrence of any of the following
condiiions
results inautomaticrectifiershutdown:
a) Operation
of any fuse
br
the rectifier, other
than
fan
fuses F5
and
F6
b)
Overvoltageconditionatrectifier output
If condition a) occurs, indicator FUSE ALARM illumi-
nates but all other operating controls remain in their nor-
mal positions.
Correctfon
of the failure
condiikm
and
replacement of the opened fuses allows the rectifier to
restart.
ff
condition b) occurs. the rectifier will restart autornati-
tally
after twenty seconds. If a second HVSD occurs
within
a 5 minute period, the rectifier will shut down and
hip the HVSD circuit breaker located on the fmnt door.
Once the failure has been corrected, placing the
circuit
breaker toggle to the ON
position
shouM
restart the
rec-
tffier.
lf
the rectifier can operate for a
period
of
5 min-
utes
wfthout
a HVSD the circuit will reset and be ready
for the next HVSD event.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I

I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
Section 4387
after removal of the lower panel at the front of the
recti-
4.10 This rectifier contains a circuit which permits
fier.
selective overvoltage shutdown when two or more recti-
fiers are operated in parallel. The circuit allows opera-
tion of the overvoltage shutdown circuit only in the
rectffier
which causes the
overvoftage
condiiin.
&~de
Reaulator
Circuif
4.11 This
rectiiier
is equipped with a ripple regulator
circuit. located on cinutt card Al
1,
which continuously
monitors the ripple current through the rectifier DC out-
put filter
capackors.
In the event of a high ripple current
condition caused by the loss of an AC input phase, the
ripple regulator circuit senses the high
ripple
through
the capacitors and provides a signal to the rectifier regu-
Table
4-l.
Fuse Types and Sizes
lation
circukry
whichreducesrectifieroutputvoltageand
current. This permits the
rsctiiier
to continue operating
at a
reduced
capacity until such
tkne
as the phase loss
is corrected. External alarms are also actttated refer to C.
wcuft
Cards
Paragraph 3.14 for details.
&~ttervless
Operation
I
M
Ontiop
4.15 Any of the circuit cards listed in Table 4-2 can
easily be replaced as individual assemblies
if
the need
arises.
4.12 If
rectifier
operation off battery is required, a
capacitor assembly, Part No. 425101400, must be
r
installed on
circuit
card A7 to
stabilbe
rectifier output
Circuit Card Description
voltage. See Figure 4-1.
Al-A6 (433401600)
1
SCR Firing Circuit
Card
Coolina
sense
A7 (486508700)
Regulator
8
Alarm Card
4.13 The
rectifier
is equipped
with
cooling fans and
temperature sensors mounted on
heatsink
assemblies
at the
bottom
of the cabinet. The
cooling
fans circulate
air across the heatsinks to cool power semiconductors
while the temperature sensors monitor
heatsink
tem-
perature.
lf
air
flow
ceases or
il
heatsink
temperature
reaches
+85’C
(+18X=).
output current of the
ractffllr
is reduced to approximately 88% of the full
load
rating,
and an external rectifier fail alarm is activated, if con-
nected. In addition.
if
a cooling fan has failed, a
red
FAN
FAILURE indicator will illuminate. When the tempera-
ture decreases or fans have been repaired, the rectifier
returns to full load
capability
and the external
rsctffiir
fail alarm is canceled.
Etmss
A8 (486562200)
A9 (433852700)
Power Supply Card
Alarm Interface Assy
1
All (486569800) I
Riiple
Reaulator
Card
I
1
A12. Al3
(433837100)
I
Fan Failure
Ahrm
1
A14.15 (425702200)
1~
~~~~
LED Alarm Card
I
Al6 (433800209)
HVSD
Resart
Circuit
1
Table 4-2. Replaceable Circuit Cards
5. ADJUSTMENTS
4.14 Table 4-l lists the rating and types for all the
5.1 Various
adjustment potentiometers are
fuses used in the
rectkier.
Fuses should be replaced
accessible on the control and indicator panel at Regula-
with
the type and size listed, or equivalent. To gain
tor and
Alarm
Circuk
A7 and Ripple Regulator Circuit
access to all fuses except
F5
and
F6,
open the meter
All. These potentiometers are factory adjusted and
and control panels. Fuses
F5
and
F6
are accessible
readjustment is not
normally
required.
Page 9

Section 4387
HINGED END
r
OFPANEL
I
I
I
1
li
I
I
I
w
MOUNTING LOCATION OFMOUNTING LOCATION OF
zi
=I
CAFAClTORASSEMBLYCAI’ACITORASSEMBLY
425101400425101400
3
zl
0
00
0
CONTROL AND INDICATOR PANELCONTROL AND INDICATOR PANEL
(INTERIOR SURFACE)(INTERIOR SURFACE)
>
REGULATOR AND ALARM CIRCUIT CARD
A7 C
0,
Figure 4-1. Capacitor Assembly Connector Location
small
fncremsnts.
Before adjustments are made, verify
that
lhe
battery is fully charged.
I
Adjustment of this
recti@r
should
only
be
attempted
bg
trained
semice
pelwmnel.
a)
A&smentmu.5i&offangesmbeyondlimits
statedint&eFmuerDataSheetisnotmcom-
mended.
To obtain float output
voftage.
place the
FLOATEQUALIZEswitchintheFLOAT
posf-
tion.
I
b)
52 Potentiometer FLOAT ADJUST is accessible
thmugh
a
hole
on the
front
panel of the rectifier.
Thtt
potentiometer sets the value of the
float
output
voitage.
Unless
othetwise
specified,
the float voltage
ts
fadory
adjusted to 52.08 VDC (24 cells at
2.17Vkell).
The
potentfomstsr
settfng.
if changed,
shoufd
be dons in
C)
To increase float
voftags,
adjust potentiome-
ter FLOAT ADJUST slowly
clodwise.
To
decrease float
voftage.
adjust potentiometer
I
slowly
countemlockwiss.
When the ssttiig of potentiometer FLOAT
I
ADJUST has been changed.
allow
battery
voltage to stabilize at its new value. then
note whether this
value
is as desired.
I
I
I
I
Page 10
I
I

I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
HINGED END
0
REGULATORANDALARM CIRCUITCARDA7
0
FACTORY ADJUST ONLY
-:
LOAD SHARING ADJ (R28)
-z
OVERVOLTAGE
SWTDOWN
ADJ
(W32--j
ADJUSTMENT POTENllOMETERS
HIGHVOLTAGEALARMADJ
(R39)-c
z
(ON OTHER SIDE OF CIRCUIT CARD)
LOW CVRRENT ALARM ADJ (RY))
-+
_
LOW VOLTAGE ALARM ADJ
(R39)
-r”
Y
1
=I
00
CONTROLANDINDICATORPANEL
(INTERIOR SURFACE)
0
Figure
5-l
Regulator and Alarm Circuit Card Adjustment Potentiometer Locations
d)
Repeat Steps
b)
and
c)
as
necessaly
to
age. Unless otherwise specified. the equalize voltage
obtain the required float voltage.
has been factory adjusted to 54 VDC (24 cells at
2.25W
cell). The potentiometer
setting.
if
changed, should be
m.m
done in small increments.
whentht?Jldatvdtageisadfusted.theequrdize
voltage wilt be
a&ad.
It is recommended that the
equalize
voltage be checked
and
$
necessary.
a)
To obtain equalize output voltage, place the
FLOAT/EQUALIZE switch in the EQUALIZE
posttion.
b)
Allow DC output voltage to stabilize at its
new value.
5.3 Potentiometer EQUALlZE ADJUST is accessible
through a hole on the
front
panel of the rectifier.
This
potentiometer sets the value of the equalize output
volt-
c)
To increase equalize voltage, adjust
potenti-
ometer
EQUALIZE ADJUST clockwise. To
decrease, adjust potentiometer
counter-
clodwise.
Page
11

sdiin
4387
d) Repeat steps b) and c) as necessary to
obtain desired equalize voltage.
5.4
The value at which the current
limif
circuit
pm-
vents
turtfter
increase of output current is set by
potenti.
ometer CURRENT LIMIT ADJUST accessible through a
hole on
the
front panel of the rectifier.
Unless otherwise
spaclied, the rectifier is factory adjusted to limit current
at 110% of rated load. To change the current
limit
set-
ting, observe the following procedure:
WARNING
Thisrecti@erisnot
ratedfotcontinuouedu@
abowellO%
of
rated current. Loads
ofup to
125%
may
bs
tolerated for short
periods
of
tim~lt?.&~hen
mcharginga
di.%hQrpedbQt-
[email protected]~~Longedope~t[onwerllO%badloaday
overheat
the
recti@8r
and
cause
permanent
dQQIQgetQSQ~CQQtpQQeQts.
4
b)
a
If
the load on the rectifier is not greater than
the desired current limit setting, a
resistive
test load
should
be used to insure the
amount
of load exceeds the desired
oufpuf
current
limit
s8ttt”g.
To
decrease
the current
limit
setting, adjust
potentiometer CURRENT LIMIT ADJUST
counterckxkwise
until the output
cutrant
decreases to the desired
lknft.
To increase the
cUf~aht
liml
setting,
adjust
potentiometer CURRENT
LIMlT
ADJUST
clockwfsa
until
the output current increases
to the
desired
liift.
Low
Wtsae
Alarm
Adiuetmenl
5.5
The
low
voltage alarm adjustment potentiometer
R36.
located
on Regulator and Alarm circuit
card
A7.
sets the value
af
which
light
emttting
diode
LOW VOLT-
AGE ALARM illuminates and an external alarm is acti-
vated,
if
connected. Unless otherwise specified. the km
voftage
alamt
is
factory adjusted for 47.15 VDC. To
readjust
tftii
limit.
observe Me following procedure:
8)
b)
Page 12
Turn off the rectifier by operating the
POWER
switch
to the OFF
poskion.
Open the mater and control panels by loos-
ening the
captive
fasteners. Disconnect the
rectifier from battery by removing the BAT-
TERY DISCONNECT link.
jMNGER
Connect an adjustable DC supply capable of
supplying
60 volts DC to the positive output
terminal (+) and
either
terminal of fuse
Fl
(-
), observing proper polarity.
Adjust potentiometer R36 fully counterclock-
wise.
Refer to Figure 5-1 for location.
Turn on the external DC supply and adjust
output
voftage
to the desired low
voltage
alarm value.
lh?fluer
cQpwftors
chwge
slowly
when
the
t?Yier-
n~IDC+upplyl~bmedon.
AUmqpmximatelg
40
seconds to
elqme
beJbreflnd
supply
adjust-
ment
to
the
desired low
uoltoge
okvm
uolue.
f)
9)
W
0
i)
Slowly
adjust potentiometer
R38
clockwise
until light emitting diode LOW VOLTAGE
ALARM on the front panel illuminates.
As a check. Increase the output voltage of
the external DC supply; light
emftting
diode
LOW VOLTAGE ALARMshould extinguish.
Slowly
decrease
the
voltage
until
tight
emit-
ting
die
LOW VOLTAGE ALARM illumi-
nates. Repeat
Steps
f)
and g). if necessary.
until the
ahrm
is
activated
at
the
desired
voltage.
Adjust power supply output voltage to
exactly the same value of battery voltage at
the rectifier output terminals. These
voft-
ages should be measured
wfth
a digital mul-
tiieter.
With power supply output voftage pmperfy
adjusted,
insert
the BATTERY DISCON-
NECT link.
Turn off the
external
DC power supply,
then
disconnect the test leads.
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I

I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
k)
Close the meter and control panels, then
start the rectifier by placing the POWER
switch to the ON position.
Hiah
Voltaae
Alarm Adiustment
5.6 The high voltage
alan
adjustment potentiometer
R39,
located on Regulator and
Alarm
Circuit card
A7.
sets the value at which light emitting diode HIGH VOLT-
AGE ALARM illuminates and an external
alarm
is acti-
vated,
if
connected. Unless otherwise specified, the
high
vottage
alam, is factory
adfsted
for 57.6 VDC. To
readjust this limit, observe the following procedure:
4
b)
Turn off the
rectiiier
by operating the
POWER
switch
to the OFF position.
Open the meter
and
contml
panels by loos.
ening the
captive
fastenets.
Disconnect the
rectifier
from
battery by removing the
SAT-
TERY DISCONNECT link.
DANGER
Rxl?rcisl?
extreme
caution
when performing
step
cl.
Easlwdous
DC
sortage
is
present
at
the
DC
output
terminals.
d
d)
e)
Connect an adjustable DC supply capable of
supplying
60
volts DC to
me
poslive
output
terminal (+) and either terminal of fuse
Fl
(-).
obsenring
proper polarity.
Adjust potentiometer R39
fuliy
clockwise.
Refer to Figure
5-l
for location.
Turn on the
external
DC supply and adjust
output voltage to the desired high
voltage
alan
value.
NOTE
TheJilter
capacitors charge
slowly
when the
exter-
nal
DC
supply
is
turned
on. Allow
qprmdmate4(
40
seconds to
el@se
before
~01al
supply
adjust-
ment to the desired high
uoltage
alarm
ualue.
f)
a
Slowly adjust potentiometer R39 counter-
clockwise until light
emkting
diode HIGH
VOLTAGE ALARM on the front panel illumi-
nates.
As a check, decrease the output
voltage
of
the external DC supply; light
emktttg
diode
HIGH VOLTAGE ALARM should extinguish.
h)
0
i)
W
Section 4387
Slowly increase the
vottage
until light emit-
ting diode HIGH VOLTAGE ALARM illumi-
nates. Repeat Steps
f)
and g). if necessary,
until the atam, is activated at the proper
vok-
age.
Adjust power
suppN
output voltage to
exactly the same value of battery voltage at
the
rectifier
output terminals. These volt-
ages should be measured with a digital mul-
timeter.
With power supply output voltage property
adjusted, inset-l the
BATTERY
DISCON-
NECT link.
Turn
off the external DC power supply, then
disconnect the test leads.
Close the meter and control panels,
then
start the rectifier by placing the POWER
swftdt
to the ON
poskion.
J
cw
Current Alarm
Adiustment
5.7
The
low
current alarm adjustment potentiometer
R50.
located on
Regutator
and Alarm
Circuk
card
A7.
sets the value at which light
emtttfmg
diode LOW CUR-
RENT ALARM illuminates and an external low current
alarm is activated, if connected.
Unless otherwise
specified, the low current alarm
adjusbnent
is factory
set to provide an
atann
when
rectiiiar
output decreases
below 0.5% of rated cunent. To readjust the low current
alarm,observe the followingprocedure:
DANOER
This
@ustment
procedure is performed with
therec@eroperatiqinatestmo&.
ACvolt-
ages
ecrpabk
of
voduchf
seuere.
perhaps
fatal
ehxtrical
shock
am
p-t
at
cont~~tor
KZ
and in other
podons
of the
circuit
when
the
n?ct!fier
is
opemting.
Exercise
caution
that
accidentti
contact
with any electrical
terminations
does
Iwt
occur.
a)
b)
Turn off the
recteier
by operating the
POWER
switch
to the OFF position. Open
the meter and control panels.
If remote sensing is used in the rectifier, dis-
connect and temporarily insulate the remote
sensing leads. These leads are connected
at TS3 terminals 1 and 2.
Page 13
Table of contents
Popular Industrial Electrical manuals by other brands

ABB
ABB TMAX XT XT2 THERMOMAGNETIC Disassembly instructions

CHINT
CHINT NCH8 Series User instruction

Murata
Murata GRM0225C1E7R9CA03 Series Reference sheet

Honeywell
Honeywell 031102 Mounting and Connection Instructions

Murata
Murata GRM155R60J274KE01 Series Reference sheet

Murata
Murata GRM1885C2A621JA01 Series Reference sheet

Murata
Murata GRT31CR61A106KE01 Series Reference sheet

Murata
Murata GRM1555C1E2R0BA01 Series Reference sheet

BECKWITH ELECTRIC
BECKWITH ELECTRIC M-0195 Instruction book

Murata
Murata GRM188C81A106MA73 Series Reference sheet

ETT
ETT DESHU SM/HPE+ Technical instructions for Installation

Eaton
Eaton MSC-D Series Instruction leaflet