D. Electric Heat. Remove the metal shipping plate from the electric heat assembly
mounted on top of the cabinet. Reference the tag afxed to the shipping plate on top
of the cabinet for directions, and shown in Figure 6.
Figure 6. Tag for Plate Removal Attached to Protective Plate on Electric Resistance
Heat Element at Top of the Scholar QV™ Cabinet.
ATTENTION: “INSTALLER”
REMOVE PROTECTIVE SHIPPING PLATE OVER ELECTRIC HEATER BEFORE
CONNECTING POWER TO UNIT. CHECK FOR DAMAGE.
E. Freeblow Plenum/Ducted Plenum. Install plenum to top of cabinet after shipping
plate has been removed from electric heater (if appropriate). Instructions are includ-
ed with plenum or see Appendix C at end of manual.
The air distribution system which is eld supplied and installed downstream of the
specied ducted plenum must be engineered to assure sufcient air ow, even
under adverse conditions, such as dirty lters. The information provided in Figure 1,
Appendix A should be used to design the air distribution system duct size leaving the
Scholar QV™ heat pump or air conditioner, keeping the external static pressure to a
minimum.
Applications using duct work should be designed and installed in accordance with the
current edition of the National Fire Protection Association codes and standards 90A
and 90B. The duct system must be engineered to insure sufcient air ow through
the unit to prevent over-heating of the heater element. This includes proper supply
duct sizing, sufcient quantity of supply registers, adequate return and lter area.
Ductwork must be of correct material and must be properly insulated. The duct work
must be constructed of galvanized steel with a minimum thickness of .019. Ductwork
must be rmly attached, secured and sealed to prevent air leakage. Do not use duct
liner on inside of supply duct within four feet of the unit.
NOTE: Follow local codes and standards when designing duct runs to deliver the
required airow. Minimize noise and excessive pressure drops caused by duct aspect
ratio changes, bends, dampers and outlet grilles in duct runs.
Galvanized metal duct extensions should be used to simplify connections to ductwork
and grilles. Use fabric boots to prevent the transmission of vibration through the duct
system. The fabric must be U.L. rated to a minimum of 197°F.
F. Install the outdoor louver/collar assembly to the outdoor side of the wall opening. The
louver/collar assembly may be fastened to the air box (or air box extension) as
described in the instructions for outdoor louvers/collars. The louver must be installed
with the blades pointing downward on the outside and the louver and the collar must
be water sealed to the outside wall surface with the appropriate caulking material.
See the instructions that come with the outdoor louver for installation details or see
Appendix F at the end of this manual.
G. Weather Panels are eld supplied and do not come with the Scholar QV™ heat pump
or air conditioner. If a weather panel covers the wall opening described in Figure 2,
remove the weather panel prior to installing the unit into the wall opening.