
10 Classic Manual 4/2012 rev. 4
while providing high pressure, loss of charge protection with an integral defrost function. Upon a
call for mechanical cooling or heating, the controller will energize the compressor when a 24 VAC
signal is applied to the “Y” terminal provided that all time delays and fault conditions are satisfied. It
will energize the indoor blower when a 24 VAC signal is applied to the “G” terminal. The reversing
valve will be energized when a 24 VAC signal is applied to the “O” terminal. Electric heat (EH) will
be energized when a 24 VAC signal is applied to the “W2” terminal. The control will monitor the
status of the loss of charge switch and the high pressure switch. If either of these inputs recognize
a fault, the compressor will turn off and the anti-short cycle delay will be initiated. If any of these
faults occur twice within a one hour period, the control will lock the compressor out until the power
is reset manually. Note: 24 VAC power must be continuously applied to “R” and “C”.
The board will also monitor the defrost sensor. If the defrost sensor senses a temperature of 32°F while
in the heat mode, it will initiate a pin selectable 30, 60, or 90 minute delay period. (Factory set at 60
minutes). If the sensor is still calling for defrost at the end of this delay period, it will de-energize
the outdoor fan and energize the reversing valve through the RV terminals. The defrost cycle will
terminate on time or temperature. It will have a maximum defrost run time of 10 minutes, however,
if the defrost sensor registers a temperature of 50°F or higher before the 10 minute maximum run
time, the defrost cycle will terminate. The EH terminals will also be energized during a defrost cycle
if the EHDD (Electric Heat During Defrost) jumper is in the “Yes” position.
The board also provides the ability to vary the speed of the indoor blower motor (electronically
commutated motors excepted) and to select the number of seconds the blower will run after the
compressor has turned off (Post Purge). The user can select whether the compressor and electric heat
operate simultaneously (the S-Circuit) and if electric heat operates during the defrost mode (EHDD).
The board can control the operation of a two position motorized damper to provide fresh air for
ventilation (DRO/DRC). In conjunction with an optional temperature sensor, the board will modulate
the speed of the outdoor fan motor to allow cooling during low ambient temperatures.
LED’s indicate power, operating status and high pressure or loss or charge lockout.
Functions
Lockout Protection
If either of the fault conditions (LPS or HPS) occurs twice within one hour, the control board will
enter into and indicate the lockout mode. In the lockout mode, the compressor is turned off. If there
is a call for indoor air flow “G”, the blower remains energized, the alarm output is energized and the
red LED will blink to indicate which fault has occurred. When the lockout condition is cleared, the
unit will reset if the thermostat is turned “Off” and back to “On” or when the power to the heat pump
is reset. With the control board, the user can select either normally closed or normally open contacts.
The heat pump is factory wired to be normally open.
Delay on Break
The board has an integral three minute delay on break (anti-short cycle) timer. This timer initiates
every time the compressor turns off to prevent a short cycle condition.
Loss of Charge (LPS) By-Pass Timer
The control includes a fixed, three minute Loss of Charge Switch (LPS) bypass timer. If the Loss of
Charge Switch is open on initial power up or while the compressor is running, the control will ignore
the fault for three minutes. If the fault still exists after three minutes, the control will de-energize the
compressor, register a loss of charge fault, and initiate the three minute anti-short cycle timer.