Maximum Controls MAX SUPER ARM 2300 Installation instructions

Installation and Owners manual for
max arm
max super arm 2300
Actuator Arms
www.max.us.com
4009963
Residential / Commercial
Linear Gate Operators
CONFORMS TO UL STD 325
UL CLASS - I, II, III, IV
CERTIFIED TO CAN/CSA STD
C22.2 NO. 247
SAFETY SENSORS REQUIRED
closeopen
JOG GATE
OPEN / CLOSE
RESET ALARM
Max Arm
Control
Box
Max Arm
Max super Arm 2300
Version 11a


1
UL 325 2018 MAX Arm and MAX Super Arm V11a
table of contents
© 2018 Maximum Controls LLC.
All rights reserved. No part of this manual may be reproduced in any
means: graphics, electronics or mechanical, including photocopying
without the expressed written permission of the publisher. Materials
components and specifications are subject to change without notice.
step-by-step installation
Mount Arm
Mount Control Box
AC Input Power ONLY
Wiring Arm to DSP Board
Gound Control Box
Settings: Gate/ID Plug/Operator
Select Actuator Type & Gate Length
Limit Switch Adjustments
Entrapment Protection Locations (List of Sensors)
Entrapment Protection Wiring (Test Photo CLS NC Sensor)
Adjust ERD Reverse Sensor
Loops & Loop Detectors
DSP Controller Board Settings
Wiring Opening Device Options
UL Sensor Learn Mode
DIP-Switch Settings
Dual Gate Operators
11
11
12
13
13
14
14
15-18
19
20
21
21
22
22
23
23
24
mounting max arm
Release Drive Rod
Brackets
Mounting Arm
Pull Open Dimensions
Push Open Dimensions
25
25
26
27
27
mounting max super arm 2300
Release Drive Rod
Brackets
Mounting Arm
Pull Open Dimensions
Push Open Dimensions
28
28
29
30
30
specifications
Actuator Arms & Control Box 2
solar power
Solar Installation 34
manually release gate
Manually Release Gate 43
additional features
MAX Open / Fire Dept Inputs
Gate Tamper
Gate Disable
Open / Stop / Close Inputs
Programming
Close to Lock
31
31
31
32
32
33
troubleshooting
OBD Port Black Box
Test Photo Close NC Sensor
Gate Cycling Troubleshooting
DSP Board Troubleshooting
35
35
36
37-38
common sensor wiring
Omron E3K-R10K4
EMX IRB-RET
EMX IRB-MON (Single Gate)
EMX IRB-MON (Dual Gates)
Miller R-Band Wireless
39
39
40
41
42
gate safety and requirements
Important
Gate Construction Information
General Requirements
UL 325 Compliant Installation Requirements
Important Safety Imformation
UL 325 Model Classifications
Gate Safety Installation
Intended Use of Swing Gate Operator
3
3
3
4-5
6
7
8-9
10
15
14
16
13
12
11
10
9
8
7
6
5
4
3
2
1

2
UL 325 2018 MAX Arm and MAX Super Arm V11a
specifications
max super arm 2300
7.3”
Min = 37”
4.5”
Power supply.....24 VDC
Max speed..... .7 in/sec
Max stroke length.....19.8in
Max traction and pressure force per leaf.....4500 N
Rated torque per leaf.....1500 N
Max power consumption per gate.....245 W
Max current consumption per gate.....1.2 A
Power consumption per gate.....115 W
Current consumption per gate.....0.6 A
Max gate weight per gate..... 2425 lbs
With max. 59 inches gate width, single gate.
Max gate length.....275.5 inches
With max 882 lbs - single gate
and max 661 lbs - per gate, dual gates.
Operating Temperatures.....-25°C ~+70°C
9.25”
Max = 54.75”
control box
13.5” 5.75”
17”
JOG GATE
OPEN / CLOSE
RESET ALARM
115VAC
3A max
7A
FUSE
POWER
On
Off
WARNING: For continued protection
against fire, replace only with the
same type and rating of fuse.
AVERTISSEMENT: pour ne pas compromettre la
protection contre les risques d’incendie, utiliser un
fusible de mêmes type et caractéristiques nominales.
Select Input Voltage
115VAC or 230VAC
(AC)
POWER IN
115V
SAFETYCENTEREXIT
J3
J2
J4 J5
EXIT PWR
ALARM
POWER /
SOLAR IN
BATTERY
INPUT
OPENING CLOSING
MOTOR 2MOTOR 1
ERD
OBD PORT
BLACK BOX
PROGRAMMING
SOLAR MODE
MOTOR
OVER
LOAD
ERD
MOTOR
OVER
LOAD MIN MAX
OFF
MAX
SENSE MAX
SENSE
BATTERY
BACKUP MODE
ERD SENSITIVITY
MOTION CONTROL
OPEN
CLOSING GATE SPEED
MOTOR 2
LIMITS
MAG
LOCK
UL
ENTRAP
STOP CLOSE
CLOSE
TIMER
MAGLOCK
DELAY
JOG
BATTERY
TEST
BATTERY
INPUT
ERROR
BATTERY
IN USE
POWER
REPLACE
BATTERY
LEAVE
CLOSED
LEAVE
OPEN OPEN
1 TIME
BATTERY VOLTAGE
EF1/2
RESET
ID
PLUG
MODULE
PORT
GATE OPEN
GND
OPEN ONLY NC
OPEN ONLY 10K
PHOTO CLS NC
OPEN / CLS NC
GND
12VDC OUT
GND
GND
GND
GND
GND
JOG CLOSE
JOG OPEN
TAMPER IN
TAMPER NO
GATE DISABLE
KEYPAD/CARD
GND
GND
MAX OPEN
FIRE DEPT
RADIO GND
RADIO SIGNAL
STRIKE
CLOSE
COM
COM
STOP
OPEN
CLS ONLY 10K
OPEN / CLS 10K
12VDC OUT
NO
COM
NC
COM
GATE CLOSED
LIMIT 1
GND
LIMIT 2
MOTOR 1
LIMITS
MOTOR 1
MOTOR 2
LIMIT 1
GND
LIMIT 2
LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
ID PLUG
ERROR
24VDC OUTPUT
12VDC OUTPUT
GND
GND
GND
LOOP
LOOP PWR
LOOP
CENTER
SAFETY
OFF
SINGLE
OPEN
ON/OFF
BATTERY
CLOSE
DUAL
ON
ANTI-
TAILGATE
PUSH
OPEN PULL
OPEN
GATE
OFF
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
MIN MIN
MAX MAX
ON
OFF 2.5 sec
1.5 sec
FAULTS
OPERATOR
DSP ARM CONTROLLER
OFF
EXIT LOOP
16
MIN
16
MIN
3
1
14 12
9
73
1
14 12
9
7
UL SENSOR 10K UL SENSOR N.C.
MODE A MODE B
PROGRAM
MOTOR 1
INPUTS
[+]
[
-
]
[+]
[
-
]
MOTOR 2
INPUTS
MAXIMUM CONTROLS
DSP ARM CONTROLLER
Class of 0peration.....UL 325 Class I, II, III, IV
Type of gate.....Vehicular swing gate only
Input AC power/amps.....
Switchable: 115VAC / 6 amp, 1 phase
or 230VAC / 2 amp, 1 phase
Power output.....24 VDC
Operating temperature.....-4°F to 158°F (-20°C to 70°C)
Cycles per hour AC input power.....Continuous
Battery back-up cycles.....
(7 Amp/Hr batteries fully charged).....Approx 450 cycles
Entrapment protection.....
- UL 325 Type A Inherent (ERD sensor)
- Inputs for NORMALLY CLOSED (N.C.) or 10K Type
UL 325 Type B1 (photo cell) and Type B2 (sensing edge)
MONITORED when used.
max arm
7.35”
4.5”
Min = 39” (+/-.39“)
Power supply.....24 VDC
Peak thrust.....4500 N
Nominal thrust.....4000 N
Max Stroke length.....21.2 in
Maximum operating current.....7.5 A for max 10 sec
Max Absorbed Power.....144 W
Maximum input power.....6 A
Max gate weight per gate.....882 lbs
Max gate length per gate.....157.4 in
Operating Temperatures.....-20°C ~+50°C
4.5”
Max = 60.3” (+/-.39“)
8ft 12ft 16ft 18ft
Max Weight/
Length
1600 lbs
1200 lbs
800 lbs
600 lbs
8ft 12ft 16ft 20ft
2300 lbs
2000 lbs
1800 lbs
1500 lbs
Max Weight/
Length

3
UL 325 2018 MAX Arm and MAX Super Arm V11a
Vehicular gates should be installed in accordance with ASTM F2200: Standard Specification for Automated Vehicular Gate Construction. For a copy, contact
ASTM directly at 610-832-9585 or www.astm.org.
GATE CONSTRUCTION INFORMATION
BEFORE attempting to install, operate or maintain the operator, you must read and fully understand this manual and follow ALL safety instructions.
DO NOT attempt repair or service of your gate operator unless you are an Authorized Service Technician.
important
Gates shall be constructed in accordance with the provisions given for the appropriate gate type listed, refer to ASTM F2200 for additional gate types.
Gates shall be designed, constructed and installed to not fall over more than 45 degrees from the vertical plane, when a gate is detached from the supporting
hardware.
Gates shall have smooth bottom edges, with vertical bottom edged protrusions not exceeding 0.50 inches (12.7 mm) when other than the exceptions listed in
ASTM F2200.
The minimum height for barbed tape shall not be less than 8feet (2.44 m) above grade and for barbed wire shall not be less than 6 feet (1.83 m) above grade.
An existing gate latch shall be disabled when a manually operated gate is retrofitted with a powered gate operator.
A gate latch shall not be installed on an automatically operated gate.
Protrusions shall not be permitted on any gate, refer to ASTM F2200 for Exceptions.
Gates shall be designed, constructed and installed such that their movement shall not be initiated by gravity when an automatic operator is disconnected, in
accordance with the following.
Vehicular horizontal slide gate. Shall not result in continuous, unimpeded movement in either lineal direction of its travel.
Vehicular horizontal swing gate. Shall not result in continuous, unimpeded movement in either direction along the arc of its path of travel.
For pedestrian access in the vicinity of an automated vehicular gate, a separate pedestrian gate shall be provided. The pedestrian gate shall be installed in a
location such that a pedestrian shall not come in contact with a moving vehicular access gate. A pedestrian gate shall not be incorporated into an automated
vehicular gate panel.
Any existing automated gate, when the operator requires replacement, shall be upgraded to conform to the provisions of this specification in effect at that time.
Vehicular horizontal slide gate:
All weight bearing exposed rollers 8feet (2.44 m), or less, above grade shall be guarded or covered.
All openings shall be designed, guarded, or screened from the bottom of the gate to the top of the gate or a minimum of 72 in. (1.83 m) above grade, whichever
is less, to prevent a 2 1⁄4 in. (57 mm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that
the gate covers in the open position. The gate panel shall include the entire section of the moving gate,including any back frame or counterbalance portion of
the gate.
A gap, measured in the horizontal plane parallel to the roadway, between a fixed stationary object nearest the roadway, (such as a gate support post) and the
gate frame when the gate is in either the fully open position or the fully closed position, shall not exceed 2 1/4 inches (57 mm), refer to ASTM F2200 for
Exception.
Positive stops shall be required to limit travel to the designed fully open and fully closed positions. These stops shall be installed at either the top of the gate, or
at the bottom of the gate where such stops shall horizontally or vertically project no more than is required to perform their intended function.
All gates shall be designed with sufficient lateral stability to assure that the gate will enter a receiver guide, refer to ASTM F2200 for panel types.
The following provisions shall apply to Class IV vehicular horizontal slide gates:
All weight bearing exposed rollers 8feet (2.44 m), or less, above grade shall be guarded or covered.
Positive stops shall be required to limit travel to the designed fully open and fully closed positions. These stops shall be installed at either the top of the gate, or
at the bottom of the gate where such stops shall horizontally or vertically project no more than is required to perform their intended function.
Vehicular horizontal swing gate:
Gates shall be designed, constructed and installed so as not to create an entrapment area between the gate and the supporting structure or other fixed object
when the gate moves toward the fully open position.
The width of an object (such as a wall, pillar or column) covered by a swing gate when in the open position shall not exceed 4 inches (102 mm), measured
from the center line of the pivot point of the gate, refer to ASTM F2200 for exception.
The distance between a fixed object such as a wall, pillar or column, and a swing gate when in the open position shall not be less than 16 inches (406 mm),
refer to ASTM F2200 for exception.
ONLY Class IV vehicular horizontal swing gates shall be designed, constructed and installed in accordance with security related parameters specific to the
application.
GENERAL REQUIREMENTS

4
UL 325 2018 MAX Arm and MAX Super Arm V11a
ul 325 compliant installation
requirements
a) Install the gate operator only when:
a) N’installez l’ouvre-barrière que si :
1) The operator is appropriate for the construction of the gate and the usage Class of the gate,
1) l’ouvre-barrière est approprié pour la structure et la classe d’utilisation de la barrière;
2) All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 1.83 m (6 ft) above the ground
to prevent a 57.2 mm (2-1/4 inch) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the
adjacent fence that the gate covers in the open position,
2) toutes les ouvertures de la barrière coulissante sont protégées ou grillagées du bas de la porte jusqu’à unminimum de 1,83 m (6 pi) du sol
si bien qu’une sphère de 57,2 mm (2 1/4 po) de diamètre ne peut passer par une ouverture au niveau de la barrière et de la portion de la
clôture adjacente que la barrière couvre en position ouverte;
3) All exposed pinch points are eliminated or guarded, and
3) tous les points de pincement sont éliminés ou protégés;
4) Guarding is supplied for exposed rollers.
4) des protections sont fournies pour les galets exposés.
b) The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The
pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the
vehicular gate during the entire path of travel of the vehicular gate.
b) L’ouvre-barrière est destiné à n’être installé que sur des barrières utilisées pour les véhicules. Il faut fournir une autre voie d’accès aux
piétons. La voie d’accès pour les piétons doit être conçue pour favoriser le passage des piétons. Placez la barrière de sorte que personne ne
puisse entrer en contact avec la barrière pour les véhicules sur l’ensemble de sa trajectoire.
c) The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and
closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.
c) Pour réduire les risques de coincement lors de l’ouverture et de la fermeture, la barrière doit être installée dans un endroit où la barrière et
les structures avoisinantes sont suffisamment éloignées l’une de l’autre. Les barriers battantes ne doivent pas ouvrir dans une zone d’accès
public.
d) The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not over-tighten the
operator clutch or pressure relief valve to compensate for a damaged gate.
d) La barrière doit être bien installée et fonctionner librement dans les deux directions avant d’entreprendre l’installation de l’ouvre-barrière.
Ne serrez pas trop l’embrayage ou la soupape de surpression de l’ouvre-barrière pour compenser une barrière endommagée.
e) For gate operators utilizing Type D protection:
e) Pour les ouvre-barrières qui utilisent des protections de type D :
1) The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving,
1) les commandes de l’ouvre-barrière doivent être placées de sorte que l’utilisateur voit l’ensemble de la zone de la barrière lorsque cette
dernière est en mouvement;
2) The placard as required by 62.1.6 shall be placed adjacent to the controls,
2) l’étiquette requise selon la clause 62.1.6 doit être placée à côté des commandes;
3) An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed, and
3) un dispositif de fermeture automatique (comme une minuterie, une boucle de détection ou un dispositif similaire) ne doit pas être utilisé;
4) No other activation device shall be connected.
4) aucun autre appareil d’activation ne doit être connecté.
f) Controls intended for user activation must be located at least 1.83 m (6 ft) away from any moving part of the gate and where the user is
prevented from reaching over, under, around or through the gate to operate the controls.
f) Les commandes destinées à l’activation par l’utilisateur doivent être situées à au moins 1,83 m (6 pi) des pieces mobiles de la barrière et à
un endroit où l’utilisateur ne peut pas atteindre les commandes par le dessus, par le dessous, par les côtés et au travers de la barrière.
Exception: Emergency access controls only accessible by authorized personnel (e.g. fire, police, EMS) may be placed at any location in the
line-of-sight of the gate.
Exception : Les commandes d’accès d’urgence accessibles au personnel autorisé seulement (p. ex. pompier, policier, SMU) peuvent être
placées à tout endroit dans le champ de visibilité de la barrière.

5
UL 325 2018 MAX Arm and MAX Super Arm V11a
ul 325 compliant installation
requirements continued
g) The Stop and/or Reset button must be located in the lineof-sight of the gate. Activation of the reset control shall not cause the operator to
start.
g) Le bouton d’arrêt, le bouton de réenclenchement ou ces deux boutons doivent être situés dans le champ de visibilité de la barrière.
L’activation des commandes de réenclenchement ne doit pas mettre en marche l’ouvrebarrière.
h) A minimum of two (2) WARNING SIGNS shall be installed, in the area of the gate. Each placard is to be visible by persons located on the
side of the gate on which the placard is installed. Also see 62.1.1.
h) Au moins deux panneaux de mise en garde doivent être installés dans la zone de la barrière. Chaque étiquette doit être visible des
personnes situées de chaque côté de la barrière sur laquelle l’étiquette est installée. Voir aussi la clause 62.1.1.
i) For gate operators utilizing a non-contact sensor in accordance with 32.1.1:
i) Pour les ouvre-barrières qui fonctionnent avec des capteurs sans contact conformément à la clause 32.1.1 :
1) See instructions on the placement of non-contact sensors for each Type of application,
1) Voir les instructions sur le positionnement des capteurs sans contact pour chaque type d’utilisation.
2) Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle, trips the sensor while the gate is still moving, and
2) Des précautions doivent être prises pour réduire les risques de déclenchement inutile, comme lorsqu’un véhicule déclenche le capteur alors
que la barrière est encore en mouvement.
3) One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter reachable by a
moving gate or barrier.
3) Un capteur sans contact ou plus doit être situé où il existe un risque de coincement ou d’obstruction, comme dans l’espace que peut
occuper la barrière lorsqu’elle est en mouvement.
j) For a gate operator utilizing a contact sensor in accordance with 32.1.1:
j) Pour les ouvre-barrières qui fonctionnent avec des capteurs de contact conformément à la clause 32.1.1 :
1) One or more contact sensors shall be located where the risk of entrapment or obstruction exists, such as at the leading edge, trailing edge,
and postmounted both inside and outside of a vehicular horizontal slide gate.
1) Au moins un capteur de contact doit être situé où il existe un risque de coincement ou d’obstruction, comme sur le bord d’ouverture, sur le
bord de fermeture et sur les poteaux montés sur l’intérieur ou l’extérieur d’une barrière coulissante pour véhicules.
2) One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
2) Au moins un capteur de contact doit être situé sur le bord inférieur d’une barrière levante pour véhicules.
3) One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
3) Au moins un capteur de contact doit être situé au point de pincement d’une barrière à pivot vertical pour véhicules.
4) A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor and the gate operator is
not subjected to mechanical damage.
4) Un capteur de contact doit être installé et câblé de sorte à éviter que la communication entre le capteur et l’ouvrebarrière soit gênée par des
dommages mécaniques.
5) A wireless device such as one that transmits radio frequency (RF) signals to the gate operator for entrapment protection functions shall be
located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruc-
tion. A wireless device shall function under the intended end-use conditions.
5) Un dispositif sans fil, comme un appareil qui transmet des signaux de radiofréquence (RF) à l’ouvre-barrière pour prévenir le coincement,
doit être situé à un endroit où la transmission des signaux ne sera pas obstruée ou gênée par des structures, des arbres ou d’autres obstacles
similaires. Un dispositif sans fil doit fonctionner selon les conditions d’utilisation finale prévues.
6) One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom edge of a
swing gate is greater than 152 mm (6 inches) but less than 406 mm (16 inches) above the ground at any point in its arc of travel, one or more
contact sensors shall be located on the bottom edge.
6) Au moins un capteur de contact doit être situé sur les bords d’ouverture intérieur et extérieur d’une barrière battante. De plus, si le dessous
d’une barrière battante est situé à plus de 152 mm (6 po) mais à moins de 406 mm (16 po) du sol à l’un des points de sa trajectoire, au moins
un capteur de contact doit être situé sur le bord inférieur.
7) One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).
7) Au moins un capteur de contact doit être situé sur le bord inférieur d’une barrière verticale (bras).

6
UL 325 2018 MAX Arm and MAX Super Arm V11a
IMPORTANT SAFETY INSTRUCTIONS WARNING – To reduce the risk of injury or death:
INSTRUCTIONS DE SÉCURITÉ IMPORTANTES AVERTISSEMENT – Pour réduire les risques de blessures et de mort :
1. READ AND FOLLOW ALL INSTRUCTIONS.
1. LISEZ ET SUIVEZ TOUTES LES INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
2. Ne laissez jamais les enfants manoeuvrer les commandes de la barrière ou jouer avec celles-ci. Laissez la télécommande hors de la portée
des enfants.
3. Always keep people and objects away from the gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
3. Tenez toujours à l’écart de la barrière toute personne ou tout objet avoisinant. IL NE FAUT JAMAIS PASSER DANS LA TRAJECTOIRE D’UNE
BARRIÈRE EN MOUVEMENT.
4. Test the gate operator monthly. The gate MUST reverse on contact with a rigid object or stop when an object activates the non-contact
sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can
increase the risk of injury or death.
4. Vérifiez le fonctionnement de l’ouvre-barrière une fois par mois. Le sens de la course DOIT s’inverser lorsque la barrière entre en contact
avec un objet dur ou la barrière DOIT s’arrêter lorsqu’un objet active les capteurs sans contact. Vérifiez à nouveau l’ouvre-barrière après tout
réglage de la force de déclenchement ou du seuil de fin de course. Un réglage incorrect de l’ouvre-barrière ou l’omission de vérifier à nouveau
le fonctionnement de l’ouvre-barrière peut causer des blessures, voire la mort.
5. Use the emergency release only when the gate is not moving.
5. Ne déclenchez le dispositif de désaccouplement d’urgence que lorsque la barrière ne bouge pas.
6. KEEP GATES PROPERLY MAINTAINED. Read the user’s manual. Have a qualified service person make repairs to gate hardware.
6. ASSUREZ-VOUS QUE LA BARRIÈRE EST CORRECTEMENT ENTRETENUE. Lisez le manuel de l’utilisateur. Confiez la réparation du matériel
de la barrière à un technicien qualifié.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
7. La voie d’accès est réservée aux véhicules seulement. Les piétons doivent utiliser une voie d’accès différente.
8. SAVE THESE INSTRUCTIONS.
8. CONSERVEZ CES INSTRUCTIONS.
important safety information

7
UL 325 2018 MAX Arm and MAX Super Arm V11a
CLASS I
Residential Vehicular Gate Operator - A vehicular gate operator
(opener or system) intended for use in a home of one to four
single family dwellings, or a garage or parking area associated
therewith.
CLASS II
Commercial/General Access Vehicular Gate Operator - A
vehicular gate operator (opener or system) intended for use in
a commercial location or building such as a multi-family
housing unit (five or more single family units) hotel, garages,
retail store or other building servicing the general public.
CLASS III
Industrial/Limited Access Vehicular Gate Operator - A
vehicular gate operator (opener or system) intended for uses
in an industrial location, loading dock area or other location
not intended to service the general public.
CLASS IV
Restricted Access Vehicular Gate Operator - A vehicular gate
operator (opener or system) intended for use in a guarded
industrial location or buildings such as airport security area or
other restricted access locations not servicing the general
public, in which unauthorized access is prevented via
supervision by security personnel.
SECURITY
AUTHORIZED
PERSONNEL
ONLY
ul 325 model classifications
A- Inherent entrapment protection system.
B1 - Provision for connection of a non-contact sensor
(photoelectric sensor or the equivalent).
B2 - Provision for connection of a contact sensor
(edge device or the equivalent).
C- Inherent adjustable clutch or pressure relief device.
D- Provision for connection of an actuating device
requiring continuous pressure to maintain opening
or closing motion of the gate.
E- An audio alarm.
Gate Type Class I & II
Swing Gate A, B1*, B2*, C, D
Slide Gate A, B1*, B2*, D
Class III & IV
A, B1*, B2*, C, D, E
A, B1*, B2*, D, E
ul 325 required entrapment protection
*B1 and B2 means of entrapment protection must be MONITORED.
This vehicular gate operator must be installed with at least two independent entrapment protection means as specified in the table and
definitions below.
The same type of device shall not be used for both entrapment protection means. Use of a single device to cover both the opening and
closing directions is in accordance with the requirement, however, a single device is not required to cover both directions. This operator
has been provided with type A entrapment protection. The installer is required to install additional entrapment protection devices in each
entrapment area.

8
UL 325 2018 MAX Arm and MAX Super Arm V11a
Weld a horizontal bar across entire gate on any installation for strength. DO NOT weld the crossbar on just a few pickets, or they could bend.
Make sure that the operator is mounted level or it will not function properly. Arm should be mounted at least 12 inches above the ground.
Make sure there is slack in the operator cable. DO NOT over-bend the operator cable. Doing this will cause the wires to eventually break.
DO NOT install on ANY pedestrian passageways, doorways, or gates.
gate safety installation
Horizontal Bar
Gate should have a smooth bottom edge, with vertical bottom edged protrusions not exceeding 0.50 inches.
If distance is greater than 4 inches for this area,
then entrapment protection is required.
If distance is less than 16 inches, entrapment protection is required in this area.
With the hinge mounted on the
corner of the pilaster, the
entrapment area is eliminated
and protection is NOT needed
for this area.
Gate Closed
Gate Opened
4” to 16”
DO NOT install operator upside down.
DO NOT install next to sprinklers or any area that may expose the system to water.
DO NOT install on uphill or downhill gates.
Gate Closed
Gate Opened
Arm MUST be installed level.
MAX 10K mini sensing
edge works well in this
area if entrapment
protection is needed.
Hinge Area
Closed Gate
If the bottom of gate is 4 inches to 16” or higher above the
ground, then edge safety sensor must be installed.
Operator wire
should be in
flexible Conduit.

9
UL 325 2018 MAX Arm and MAX Super Arm V11a
gate safety installation
DO NOT install on uphill or downhill gates.
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time
without prior warning.
Do not let children operate the gate or play
in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
A minimum of two (2) WARNING SIGNS shall be installed.
One on EACH side of the gate area where easily visible.
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time
without prior warning.
Do not let children operate the gate or play
in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
Install on back side
DO NOT install a opening device
accessible through the gate.
It MUST be mounted a minimum
of 6 feet away from all moving
parts of the gate and in sight of
the gate.
Install it high enough to keep out
of reach of small children.

10
UL 325 2018 MAX Arm and MAX Super Arm V11a
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time
without prior warning.
Do not letchildren operate the gate or play
in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate maymove at any time
without prior warning.
Do not let children operate the gate or play
in the gate area.
Thisentrance is for vehicles only.
Pedestrians must use separate entrance.
Safety
Loop
Safety
Loop
JOGGATE
OPEN/CLOSE
RESETALARM
closeopen
Warning Signs
BOTH sides
close open
JOGGATE
OPEN/CLOSE
RESETALARM
Entrapment
Area
Separate
Pedestrian Entrance
Entry
Device
Entry
Device
Separate
Pedestrian Entrance
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time
without prior warning.
Do notlet children operate the gate or play
in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
Moving Gate CanCause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time
without prior warning.
Do not letchildren operate the gate or play
in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
intended use of
swing gate operator
The operator is intended for use on a VEHICULAR slide gate ONLY. It is intended to be used WITH appropriate entrapment
protection safety devices and in-ground vehicle loop detection system. This operator has a inherent entrapment protection
system and requires additional external monitored entrapment protection devices (Non-contact Photo sensors or contact
sensing edges) for each entrapment area prior to gate operation. Pedestrians MUST use a separate entrance.
Entrapment Area
Exit Loop
Safety Loop
Inside
Property
Inside
Property
Outside Property
Outside
Property
Outside
Property
Shadow Loop
Exit Loop
Safety Loop
Shadow Loop
Sensing Edge
Warning Signs
BOTH sides
Opening Photo Sensor
Opening Photo
Sensor
Closing Photo Sensor
Sensing Edge
Hinge Sensing Edge
May be necessary
Hinge Sensing Edge
May be necessary
pull open
push open

11
UL 325 2018 MAX Arm and MAX Super Arm V11a
DUAL GATE OPERATORS: When installing dual gate operators, also refer to page 24.
1mount arm
2mount control box
step-by-step installation
Mount your selected arm to the gate. See MAX Arm - pages 25-27 OR MAX Super Arm 2300 - pages 28-30.
Read and understand this ENTIRE manual BEFORE installation. Check with the local building department prior to installing
this gate operator to comply with local building code requirements. The gate must be installed in a location so that enough
clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment.
Swinging gates should not open into public access areas.
115VAC
3A max
7A
FUSE
POWER
On
Off
WARNING: For continued protection
against fire, replace only with the
same type and rating of fuse.
AVERTISSEMENT: pour ne pas compromettre la
protection contre les risques d’incendie, utiliser un
fusible de mêmes type et caractéristiques nominales.
Select Input Voltage
115VAC or 230VAC
(AC)
POWER IN
115V
SAFETYCENTEREXIT
J3
J2
J4 J5
EXIT PWR
ALARM
POWER /
SOLAR IN
BATTERY
INPUT
OPENING CLOSING
MOTOR 2MOTOR 1
ERD
OBD PORT
BLACK BOX
PROGRAMMING
SOLAR MODE
MOTOR
OVER
LOAD
ERD
MOTOR
OVER
LOAD MIN MAX
OFF
MAX
SENSE MAX
SENSE
BATTERY
BACKUP MODE
ERD SENSITIVITY
MOTION CONTROL
OPEN
CLOSING GATE SPEED
MOTOR 2
LIMITS
MAG
LOCK
UL
ENTRAP
STOP CLOSE
CLOSE
TIMER
MAGLOCK
DELAY
JOG
BATTERY
TEST
BATTERY
INPUT
ERROR
BATTERY
IN USE
POWER
REPLACE
BATTERY
LEAVE
CLOSED
LEAVE
OPEN OPEN
1 TIME
BATTERY VOLTAGE
EF1/2
RESET
ID
PLUG
MODULE
PORT
GATE OPEN
GND
OPEN ONLY NC
OPEN ONLY 10K
PHOTO CLS NC
OPEN / CLS NC
GND
12VDC OUT
GND
GND
GND
GND
GND
JOG CLOSE
JOG OPEN
TAMPER IN
TAMPER NO
GATE DISABLE
KEYPAD/CARD
GND
GND
MAX OPEN
FIRE DEPT
RADIO GND
RADIO SIGNAL
STRIKE
CLOSE
COM
COM
STOP
OPEN
CLS ONLY 10K
OPEN / CLS 10K
12VDC OUT
NO
COM
NC
COM
GATE CLOSED
LIMIT 1
GND
LIMIT 2
MOTOR 1
LIMITS
MOTOR 1
MOTOR 2
LIMIT 1
GND
LIMIT 2
LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
ID PLUG
ERROR
24VDC OUTPUT
12VDC OUTPUT
GND
GND
GND
LOOP
LOOP PWR
LOOP
CENTER
SAFETY
OFF
SINGLE
OPEN
ON/OFF
BATTERY
CLOSE
DUAL
ON
ANTI-
TAILGATE
PUSH
OPEN PULL
OPEN
GATE
OFF
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
MIN MIN
MAX MAX
ON
OFF 2.5 sec
1.5 sec
FAULTS
OPERATOR
DSP ARM CONTROLLER
OFF
EXIT LOOP
16
MIN
16
MIN
3
1
14 12
9
73
1
14 12
9
7
UL SENSOR 10K UL SENSOR N.C.
MODE A MODE B
PROGRAM
MOTOR 1
INPUTS
[+]
[
-
]
[+]
[
-
]
MOTOR 2
INPUTS
MAXIMUM CONTROLS
DSP ARM CONTROLLER
13.5” 5.75”
17”
1 1/2” 2 1/8”
Knock-Outs
3/4” Conduit
Knock-Outs
2 1/2”
2 1/2”
4 1/2” 4 1/2” 3”
2 1/2”
Front
Bottom
Side
JOG GATE
OPEN / CLOSE
RESET ALARM
Mount the control box as near as possible to the actuator arm. Avoid drilling holes in the side or top of the box.
Seal any holes made in box to keep out moisture.
Use the knock-outs to run desired 3/4” conduit.
Never run low voltage wires in the same conduit
as high voltage wire.
CAREFULLY remove the
delicate control board and
other components before
mounting box. Use the 4
mounting holes to install
box. See components
connections to help with
re-installation.
Couplings and conduit
not provided Use flexible conduit to connect
to control box, not provided.
EXIT PWR
ALARM
POWER /
SOLAR IN
BATTERY
INPUT
OPENING CLOSING
MOTOR 2MOTOR 1
ERD
OBD PORT
BLACK BOX
PROGRAMMING
SOLAR MODE
MOTOR
OVER
LOAD
ERD
MOTOR
OVER
LOAD MIN MAX
OFF
MAX
SENSE MAX
SENSE
BATTERY
BACKUP MODE
ERD SENSITIVITY
MOTION CONTROL
OPEN
CLOSING GATE SPEED
MOTOR 2
LIMITS
MAG
LOCK
UL
ENTRAP
STOP CLOSE
CLOSE
TIMER
MAGLOCK
DELAY
JOG
BATTERY
TEST
BATTERY
INPUT
ERROR
BATTERY
IN USE
POWER
REPLACE
BATTERY
LEAVE
CLOSED
LEAVE
OPEN OPEN
1 TIME
BATTERY VOLTAGE
EF1/2
RESET
ID
PLUG
MODULE
PORT
GATE OPEN
GND
OPEN ONLY NC
OPEN ONLY 10K
PHOTO CLS NC
OPEN / CLS NC
GND
12VDC OUT
GND
GND
GND
GND
GND
JOG CLOSE
JOG OPEN
TAMPER IN
TAMPER NO
GATE DISABLE
KEYPAD/CARD
GND
GND
MAX OPEN
FIRE DEPT
RADIO GND
RADIO SIGNAL
STRIKE
CLOSE
COM
COM
STOP
OPEN
CLS ONLY 10K
OPEN / CLS 10K
12VDC OUT
NO
COM
NC
COM
GATE CLOSED
LIMIT 1
GND
LIMIT 2
MOTOR 1
LIMITS
MOTOR 1
MOTOR 2
LIMIT 1
GND
LIMIT 2
LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
ID PLUG
ERROR
24VDC OUTPUT
12VDC OUTPUT
GND
GND
GND
LOOP
LOOP PWR
LOOP
CENTER
SAFETY
OFF
SINGLE
OPEN
ON/OFF
BATTERY
CLOSE
DUAL
ON
ANTI-
TAILGATE
PUSH
OPEN PULL
OPEN
GATE
OFF
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
MIN MIN
MAX MAX
ON
OFF 2.5 sec
1.5 sec
FAULTS
OPERATOR
DSP ARM CONTROLLER
OFF
EXIT LOOP
16
MIN
16
MIN
3
1
14 12
9
73
1
14 12
9
7
UL SENSOR 10K UL SENSOR N.C.
MODE A MODE B
PROGRAM
MOTOR 1
INPUTS
[+]
[
-
]
[+]
[
-
]
MOTOR 2
INPUTS
MAXIMUM CONTROLS
DSP ARM CONTROLLER
Components Connections
Battery
Plug
Toroid Box Connector
Jog Gate
Open/Close
Reset Alarm
Alarm
Loop Rack
Loop
Ground
White-
Purple-
Blue-
Green-
Yellow-
Brown-
Black-
Exit Pwr
Exit Loop
Gnd
Center Loop
Loop Pwr
Safety Loop
Faults Yellow-
Gray-
Black-
Jog Open
Jog Close
Gnd
Board
Ground
SAFETYCENTEREXIT
J3
J2
J4 J5
Red
Red
Operator wire
should be in
flexible Conduit,
not provided.
Flex
Conduit
J-Box
Make sure there is slack in the operator cable.
DO NOT over-bend the operator cable.
Doing this will cause the cable to eventually break.
DO NOT install near sprinklers or any area that
may expose the system to water.
Radio Receiver
Back
11” Mounting
Hole
Mounting
Hole
Mounting
Hole
Mounting
Hole
6 1/8”4 Mounting Holes
Mounting hardware
not provided
10”
1 1/4”
1 1/4”
1”
Please read all the
“SAFETY PAGES” in
front of this manual
(pages 3-10) for
installation
requirements and
restrictions.

12
UL 325 2018 MAX Arm and MAX Super Arm V11a
3ac input power ONLY
7A
FUSE
POWER
On
Off
WARNING: For continued protection
against fire, replace only with the
same type and rating of fuse.
AVERTISSEMENT: pour ne pas compromettre la
protection contre les risques d’incendie, utiliser un
fusible de mêmes type et caractéristiques nominales.
Select Input Voltage
115VAC or 230VAC
(AC)
POWER IN
115V
7A
FUSE
POWER
On
Off
WARNING: For continued protection
against fire, replace only with the
same type and rating of fuse.
AVERTISSEMENT: pour ne pas compromettre la
protection contre les risques d’incendie, utiliser un
fusible de mêmes type et caractéristiques nominales.
Select Input Voltage
115VAC or 230VAC
(AC)
POWER IN
115V
DANGER
HIGH VOLTAGE!
Choose either 115V or 230V setting on input AC power selector switch.
Wire desired input AC power wire to power terminal.
Turn Power ON
Turn Power OFF
Chassis (Green)
Neutral (White)
Line (Black)
Chassis (Green)
Neutral (White)
Line (Black)
Input AC Power Options
Single Phase 115VAC Only
115VAC
Set to 115V
115V
Single Phase 230VAC Only
230VAC
230V
Set to 230V
Power Terminal
IMPORTANT: Make sure there are NO exposed
bare wires at the power terminal connection.
115 OR 230VAC
Input AC Power Wire
CAUTION: Make sure circuit
breaker is OFF from incoming
AC input wire BEFORE wiring!
CAUTION: If input AC power selector
switch is set for 115V but input power
is actually 230 V, 7 Amp Fuse will blow.
7A
FUSE
POWER
On
Off
WARNING: For continued protection
against fire, replace only with the
same type and rating of fuse.
AVERTISSEMENT: pour ne pas compromettre la
protection contre les risques d’incendie, utiliser un
fusible de mêmes type et caractéristiques nominales.
Select Input Voltage
115VAC or 230VAC
(AC)
POWER IN
115V
MAX Toroid Box
(located inside of control box)
AC Power Selector Switch
7 Amp Fuse
LEDs should light up on DSP board.
Battery power automatically turns ON.
ON/OFF
BATTERY
1Turn OFF POWER Switch on MAX Toroid Box.
Battery power will remain ON.
2Press and HOLD the RED ON/OFF
BATTERY button on DSP board until
beep is heard, then release button.
IMPORTANT: This procedure
must be followed whenever ALL
power must be turned OFF.
NOTE: IF solar power is being installed, see page 34 for wiring.
115VAC
3A max
115VAC
3A max
115VAC
3A max

13
UL 325 2018 MAX Arm and MAX Super Arm V11a
115VAC
3A max
WARNING: For continued protecti
against fire, replace only with t
same type and rating of fu
s
AVERTISSEMENT: pour ne pas compromettr
e
protection contre les risques d’incendie, utiliser
fusible de mêmes type et caractéristiques nominal
e
SAFETYCENTEREXIT
J3
J2
J4 J5
EXIT PWR
ALARM
POWER /
SOLAR IN
BATTERY
INPUT
OPENING CLOSING
MOTOR 2MOTOR 1
ERD
OBD PORT
BLACK BOX
PROGRAMMING
SOLAR MODE
MOTOR
OVER
LOAD
ERD
MOTOR
OVER
LOAD MIN MAX
OFF
MAX
SENSE MAX
SENSE
BATTERY
BACKUP MODE
ERD SENSITIVITY
MOTION CONTROL
OPEN
CLOSING GATE SPEED
UL
ENTRAP
STOP CLOSE
CLOSE
TIMER
MAGLOCK
DELAY
JOG
BATTERY
TEST
BATTERY
INPUT
ERROR
BATTERY
IN USE
POWER
REPLACE
BATTERY
LEAVE
CLOSED
LEAVE
OPEN OPEN
1 TIME
BATTERY VOLTAGE
EF1/2
RESET
ID
PLUG
MODULE
PORT
GND
GND
GND
JOG CLOSE
JOG OPEN
TAMPER IN
TAMPER NO
GATE DISABLE
KEYPAD/CARD
GND
GND
MAX OPEN
FIRE DEPT
RADIO GND
RADIO SIGNAL
STRIKE
CLOSE
COM
COM
STOP
OPEN
MOT
O
MOT
O
ID PLUG
ERROR
24VDC OUTPUT
12VDC OUTPUT
GND
GND
GND
LOOP
LOOP PWR
LOOP
CENTER
SAFETY
OFF
SINGLE
OPEN
ON/OFF
BATTERY
CLOSE
DUAL
ON
ANTI-
TAILGATE
PUSH
OPEN PULL
OPEN
GATE
OFF
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
MIN MIN
MAX MAX
ON
OFF 2.5 sec
1.5 sec
FAULTS
OPERATOR
DSP ARM CONTROLL
E
OFF
EXIT LOOP
16
MIN
16
MIN
3
1
14 12
9
73
1
14 12
9
7
UL SENSOR 10K UL SENSOR N C
MODE A MODE B
PROGRAM
MAXIMUM CONTROLS
DSP ARM CONTROLLER
5ground control box
Operator MUST be Properly GROUNDED
IMPORTANT: Operator MUST be grounded in lightning
prone areas or warranty will be VOIDED!
NOTE: Consult city codes for AC line wiring.
Beware of existing underground services.
Proper grounding of this control box is a requirement for
LIGHTNING PROTECTION in lightning prone areas. To be
effective, ground connections should be made with a minimum
12 AWG, 600 volt insulated wire to a ground point within 10 feet
of the control box. The ground point must be at an electrical
panel, a metallic cold water pipe that runs in the earth, or a
grounding rod.
Chassis
Ground
Grounding Rod
4wire arm to dsp board
Super Arm 2300 wiring
MAX
MOTOR 2
LIMITS
LIMIT 1
GND
LIMIT 2
MOTOR 1
LIMITS
MOTOR 1
MOTOR 2
LIMIT 1
GND
LIMIT 2
LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
MOTOR 1
INPUTS
[+]
[
-
]
[+]
[
-
]
MOTOR 2
INPUTS
White
Yellow
Red
Black
Green
Motor 1
Motor 2 connects the same as Motor 1.
(Bi-Parting Gates ONLY)
Motor 2
Connection
Motor 2
Connection
MAX
MOTOR 2
LIMITS
LIMIT 1
GND
LIMIT 2
MOTOR 1
LIMITS
MOTOR 1
MOTOR 2
LIMIT 1
GND
LIMIT 2
LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
MOTOR 1
INPUTS
[+]
[
-
]
[+]
[
-
]
MOTOR 2
INPUTS
12453
Motor 1
1
2
3
5
4
Motor 2 connects the same as Motor 1.
(Bi-Parting Gates ONLY)
Motor 2
Connection
Motor 2
Connection
Wire numbers
are printed on
each wire.
Select desired operator.
MAX Arm wiring
DO NOT CYCLE OPERATOR
AT THIS TIME.
DAMAGE COULD OCCUR!
NOTE: Operator
wire should be in
flexible Conduit,
not provided.

14
UL 325 2018 MAX Arm and MAX Super Arm V11a
EXIT PWR
ALARM
POWER /
SOLAR IN
BATTERY
INPUT
OPENING CLOSING
MOTOR 2MOTOR 1
ERD
OBD PORT
BLACK BOX
PROGRAMMING
SOLAR MODE
MOTOR
OVER
LOAD
ERD
MOTOR
OVER
LOAD MIN MAX
OFF
MAX
SENSE MAX
SENSE
BATTERY
BACKUP MODE
ERD SENSITIVITY
MOTION CONTROL
OPEN
CLOSING GATE SPEED
MOTOR 2
LIMITS
MAG
LOCK
UL
ENTRAP
STOP CLOSE
CLOSE
TIMER
MAGLOCK
DELAY
JOG
BATTERY
TEST
BATTERY
INPUT
ERROR
BATTERY
IN USE
POWER
REPLACE
BATTERY
LEAVE
CLOSED
LEAVE
OPEN OPEN
1 TIME
BATTERY VOLTAGE
EF1/2
RESET
ID
PLUG
MODULE
PORT
GATE OPEN
GND
OPEN ONLY NC
OPEN ONLY 10K
PHOTO CLS NC
OPEN / CLS NC
GND
12VDC OUT
GND
GND
GND
GND
GND
JOG CLOSE
JOG OPEN
TAMPER IN
TAMPER NO
GATE DISABLE
KEYPAD/CARD
GND
GND
MAX OPEN
FIRE DEPT
RADIO GND
RADIO SIGNAL
STRIKE
CLOSE
COM
COM
STOP
OPEN
CLS ONLY 10K
OPEN / CLS 10K
12VDC OUT
NO
COM
NC
COM
GATE CLOSED
LIMIT 1
GND
LIMIT 2
MOTOR 1
LIMITS
MOTOR 1
MOTOR 2
LIMIT 1
GND
LIMIT 2
LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
ID PLUG
ERROR
24VDC OUTPUT
12VDC OUTPUT
GND
LOOP
LOOP PWR
LOOP
CENTER
SAFETY
OFF
SINGLE
OPEN
ON/OFF
BATTERY
CLOSE
DUAL
ON
ANTI-
TAILGATE
PUSH
OPEN PULL
OPEN
GATE
OFF
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
MIN MIN
MAX MAX
ON
OFF 2.5 sec
1.5 sec
FAULTS
OPERATOR
DSP ARM CONTROLLER
OFF
EXIT LOOP
16
MIN
16
MIN
3
1
14 12
9
73
1
14 12
9
7
UL SENSOR 10K UL SENSOR N.C.
MODE A MODE B
PROGRAM
MOTOR 1
INPUTS
[+]
[
-
]
[+]
[
-
]
MOTOR 2
INPUTS
MAXIMUM CONTROLS
DSP ARM CONTROLLER
6settings: gate/id plug/operator
7
select actuator type & gate length
ENING
T
M
OPEN
BATTE
TEST
BATTER
Y
INP
U
T
E
RR
O
R
TTERY
USE
BATT
E
TI-
TE
ON
16
N
1
4
12
9
7
MA
DSP
ERD
OTO
VER
OAD
SP A
S
ER
24VDC
OU
TP
UT
12VDC OUTPUT
LOOP
Y
FAULTS
D
OPEN
FIRE DEPT
RADIO GND
R
ADI
O
S
I
G
NAL
DU
AL
Gate:
Set the desired opening direction.
See next pages.
ID Plug Error: If ID plug is NOT plugged in, board
will constantly beep and arm will NOT function.
Operator:
Set operator to SINGLE for a single arm installation.
Set operator to Dual for a bi-parting gates installation.
MAX
ACTUATOR
ARM
Closed Gate
Open Open
INSIDE
Property
OUTSIDE
Property
PULL OPEN
PUSH OPEN
Wall
SINGLE DUAL
OPERATOR
PULL
OPEN
PUSH
OPEN
GATE
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
OFF
MODE A MODE B
Switches
4 & 5
1
2
3
4
5
6
7
8
9
10
OFF
1
2
3
4
5
6
OFF
MODE A MODE B
OFF for
Max Arm
ON for
Super Arm
2300
Select actuator type Mode B DIP-switch 6. Select gate length Mode B DIP-switches 4 & 5.
5
OFF
OFF
ON
ON
4 Gate Length
OFF
ON
OFF
ON
G < 7 ft
7 ft < G < 10 ft
10 ft < G < 13 ft
G > 13 ft

15
UL 325 2018 MAX Arm and MAX Super Arm V11a Continued on next page.
8limit switch adjustments
With gate in the exact Close and then OPEN
positions respectively, adjust each limit until the
appropriate LED lights up and a BEEP is heard
for each gate limit position.
Adjust the limit switches for OPEN and CLOSE gate
positions for your selected MODEL OPERATOR and
OPENING DIRECTION on the next 3 pages. Mode B
DIP-switches 4&5, 6 MUST be set correctly for your
operator. See previous page.
Operator MUST be wired to control box. Control box MUST have power.
2. Mount actuator arm on REAR bracket ONLY.
(Rear bracket already secured to gate post)
3. Manually release actuator arm. See page 43.
4. Retract shaft until a BEEP is heard from
control box.
5. Extend shaft to 3 1/4” (typical) as shown.
This will be OPEN position of operator.
6. Bolt FRONT bracket to operator.
7. Move gate to OPEN position.
1. Clear limits on control box. Press and HOLD STOP and CLOSE
buttons together for 5 sec. until BEEP is heard. Screen will
display “LEARNING LIMITS”.
9. Make sure gate remains in OPEN position. Rotate OPEN limit
screw until BEEP is heard.
10. Manually move gate to CLOSE position.
PULL
OPEN
PUSH
OPEN
GATE
PULL OPEN configuration:
- LIMIT 1 is OPEN limit
-LIMIT 2 is CLOSE limit
PUSH OPEN configuration:
- LIMIT 1 is CLOSE limit
-LIMIT 2 is OPEN limit
Limit LEDs
MOTOR 1
MOTOR 2 LIMIT 1
LIMIT 2
LIMIT 1
LIMIT 2
PUSH
OPEN
GATE
PULL
OPEN
BEEP
BEEP
BEEP
open
3 1/4”
Typical
(2.16” Min)
REAR
bracket Manual Release
FRONT bracket position
OPEN position
8. With operator shaft in same position, temporarily mount FRONT bracket (Clamp or tack weld) to gate in the OPEN position.
Retract
MOTION CONTROL
OPEN
STOP CLOSE
LEARNING LIMITS
close open
Super Arm 2300 - pull open
Extend
Open
Close
NOTE: Rotate OPEN limit screw in “MINUS” direction for gate to open LESS.
Rotate OPEN limit screw in “PLUS” direction for gate to open FURTHER.

16
UL 325 2018 MAX Arm and MAX Super Arm V11a
Continued on next page.
11. Rotate CLOSE limit screw until BEEP is heard.
12. Re-lock Manual release.
close
13. Learn newly adjusted limits on control box. Push the OPEN button, gate will open
and learn open limit. Push the CLOSE button, gate will close and learn close limit.
NOTE: Gate may not ramp down when approaching limits while “LEARNING”
gates but will ramp down after gate has been learned.
NOTE: If 2 consecutive beeps are heard when moving gate to CLOSED position,
then adjust gate to FIRST beep position.
NOTE: If limits need to be re-adjusted, then they MUST be cleared first from control box, see #1 on previous page.
closeopen
BEEP
CAUTION: If BEEP is NOT heard, readjust front bracket position.
Re-lock Manual Release
Operator MUST be wired to control box. Control box MUST have power.
2. Mount actuator arm on REAR bracket ONLY.
(Rear bracket already secured to gate post)
3. Manually release actuator arm. See page 43.
4. Retract shaft until a BEEP is heard from
control box.
5. Extend shaft to 3 1/4” (typical) as shown.
This will be CLOSE position of operator.
6. Bolt FRONT bracket to operator.
7. Move gate to CLOSE position.
1. Clear limits on control box. Press and HOLD STOP and CLOSE
buttons together for 5 sec. until BEEP is heard. Screen will display
“LEARNING LIMITS”.
9. Make sure gate remains in CLOSE position. Rotate OPEN limit
screw until BEEP is heard.
10. Manually move gate to OPEN position.
BEEP
BEEP
BEEP
open
3 1/4”
Typical
(2.16” Min)
REAR
bracket Manual Release
FRONT bracket position
CLOSE position
8. With operator shaft in same position, temporarily mount FRONT bracket (Clamp or tack weld) to gate in the CLOSE position.
Retract
MOTION CONTROL
OPEN
STOP CLOSE
LEARNING LIMITS
close open
Super Arm 2300 - push open
GATE
PULL
OPEN
PUSH
OPEN
Extend
Close
Open
MOTION CONTROL
OPEN
STOP
CLOSE
NOTE: Rotate CLOSE limit screw in “MINUS” direction for gate to close LESS.
Rotate CLOSE limit screw in “PLUS” direction for gate to close FURTHER.
NOTE: Rotate OPEN limit screw in “MINUS” direction for gate to close LESS.
Rotate OPEN limit screw in “PLUS” direction for gate to close FURTHER.

17
UL 325 2018 MAX Arm and MAX Super Arm V11a Continued on next page.
11. Rotate CLOSE limit screw until BEEP is heard.
12. Re-lock Manual release.
close
13. Learn newly adjusted limits on control box. Push the OPEN button, gate will open
and learn open limit. Push the CLOSE button, gate will close and learn close limit.
NOTE: Gate may not ramp down when approaching limits while “LEARNING” gates
but will ramp down after gate has been learned.
NOTE: If limits need to be re-adjusted, then they MUST be cleared first from control box, see #1 on previous page.
close open
BEEP
2. Mount actuator arm on REAR bracket ONLY.
(Rear bracket already secured to gate post)
3. Manually release actuator arm. See page 43.
4. Retract shaft until a BEEP is heard from
control box.
5. Extend shaft to 5.5” (typical) as shown.
This will be OPEN position of operator.
6. Bolt FRONT bracket to operator.
7. Move gate to OPEN position.
1. Clear limits on control box. Press and HOLD STOP and CLOSE
buttons together for 5 sec. until BEEP is heard. Screen will
display “LEARNING LIMITS”.
9. Loosen OPEN limit knob and slide until
BEEP is heard. Tighten knob when finished.
11. Loosen CLOSE limit knob and slide until
BEEP is heard. Tighten knob when finished.
10. Manually move gate to CLOSE position.
PUSH
OPEN
GATE
PULL
OPEN
BEEP
BEEP
Open Knob
REAR
bracket
Manual Release
FRONT bracket position
OPEN position
8. With operator shaft in same position, temporarily mount FRONT bracket (Clamp or tack weld) to gate in the OPEN position.
Retract
MOTION CONTROL
OPEN
STOP CLOSE
LEARNING LIMITS
MAX Arm - pull open
Operator MUST be wired to control box.
Control box MUST have power.
5.5”
Typical (3.5” Min)
Close Knob
Extend
Open
Close
MOTION CONTROL
OPEN
STOP
CLOSE
Re-lock Manual Release
NOTE: If 2 consecutive beeps are heard when moving gate to OPEN position,
then adjust gate to FIRST beep position.
CAUTION: If BEEP is NOT heard, readjust front bracket position.
CAUTION: If BEEP is NOT heard, readjust front bracket position.
NOTE: If 2 consecutive beeps are heard when moving gate to CLOSED position, then adjust gate to FIRST beep position.
NOTE: Rotate CLOSE limit screw in “MINUS” direction for gate to open LESS.
Rotate CLOSE limit screw in “PLUS” direction for gate to open FURTHER.

18
UL 325 2018 MAX Arm and MAX Super Arm V11a
12. Re-lock Manual release.
13. Learn newly adjusted limits on control box. Push the OPEN button, gate will open and learn open
limit. Push the CLOSE button, gate will close and learn close limit.
NOTE: Gate may not ramp down when approaching limits while “LEARNING” gates but will ramp
down after gate has been learned.
NOTE: If limits need to be re-adjusted, then they MUST be cleared first from control box, see #1 on previous page.
GATE
PULL
OPEN
PUSH
OPEN
12. Re-lock Manual release.
13. Learn newly adjusted limits on control box. Push the OPEN button, gate will open and learn open
limit. Push the CLOSE button, gate will close and learn close limit.
NOTE: Gate may not ramp down when approaching limits while “LEARNING” gates but will ramp
down after gate has been learned.
NOTE: If limits need to be re-adjusted, then they MUST be cleared first from control box, see #1 above.
MOTION CONTROL
OPEN
STOP
CLOSE
MOTION CONTROL
OPEN
STOP
CLOSE
Re-lock Manual Release
2. Mount actuator arm on REAR bracket ONLY.
(Rear bracket already secured to gate post)
3. Manually release actuator arm. See page 43.
4. Retract shaft until a BEEP is heard from
control box.
5. Extend shaft to 5.5” (typical) as shown.
This will be CLOSE position of operator.
6. Bolt FRONT bracket to operator.
7. Move gate to CLOSE position.
1. Clear limits on control box. Press and HOLD STOP and CLOSE
buttons together for 5 sec. until BEEP is heard. Screen will
display “LEARNING LIMITS”.
9. Loosen OPEN limit knob and slide until
BEEP is heard. Tighten knob when finished.
11. Loosen CLOSE limit knob and slide until
BEEP is heard. Tighten knob when finished.
10. Manually move gate to OPEN position.
BEEP
BEEP
REAR
bracket
Manual Release
FRONT bracket position
CLOSE position
8. With operator shaft in same position, temporarily mount FRONT bracket (Clamp or tack weld) to gate in the CLOSE position.
Retract
Extend
MOTION CONTROL
OPEN
STOP CLOSE
LEARNING LIMITS
MAX Arm - push open
Operator MUST be wired to control box.
Control box MUST have power.
5.5”
Typical (3.5” Min)
Close Knob
Open Knob
Open
Close
CAUTION: If BEEP is NOT heard, readjust front bracket position.
NOTE: If 2 consecutive beeps are heard when moving gate to
CLOSED position, then adjust gate to FIRST beep position.