
12
E. EXHAUST REQUIREMENTS
Exhaust duct work shouldbedesigned and installed by a qualified professional. Improperly sized duct work will
create excessive back pressure which results in slow drying, increased use of energy, overheating of the dryer,
andshutdownof the burnerbythe airflow (sail)switches,burner hi-limits, orbasket(tumbler) hi-heat thermostats.
CAUTION: IMPROPERLYSIZEDor INSTALLEDEXHAUSTDUCTWORKCAN
CREATEAPOTENTIALFIREHAZARD.
The exhaust duct work should be laid out in such a way that the duct work travels as directly as possible to the
outdoors with as few turns as possible. When single dryer venting is used, the duct work from the dryer to the
outside exhaust outlet must not exceed 10 feet (3.05 meters). In the case of multiple (common) dryer venting,
the distance from the last dryer to the outside exhaust outlet must not exceed 20 feet (6.1 meters). The shape
of the exhaust duct work is not critical so long as the minimum cross-sectional area is provided.
1. Single Dryer Venting
Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct work
should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as
few turns as possible. It is suggested that the use of 90º turns in ducting be avoided; use 30º or 45º angles
instead. The shape of the exhaust duct work is not critical so long as the minimum cross-sectional area is
provided.
IMPORTANT: Exhaust back pressure measured by a manometer at the dryer’sexhaustductarea
mustnot exceed0.3 inches of water column (W.C.) - 0.74 mb - when both baskets
(tumblers)areoperating.
It is suggested that the duct work from each dryer not exceed 10 feet (3.05 meters) with no more than two
(2) elbows. If the duct work exceeds 10 feet (3.05 meters) or has numerous elbows, the cross-sectional
area of the duct work must be increased in proportion to length or number of elbows in it.
IMPORTANT: For extendedductwork runs, the cross-sectional area of theduct work can only be
increasedtoanextent. Maximumproportionalductworkrunscannot exceed 10 feet
(3.05meters)morethanthe originallimitationsof10feet(3.05meters) with two(2)
elbows. Whentheductwork approachesthemaximumlimitsas notedinthismanual,
aprofessionalheating, venting,andair-conditioning(HVAC)firmshouldbeconsulted
forproperventinginformation.
The duct work should be smooth inside with no projections from sheet metal screws or other obstructions,
which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be
connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the
building. Also, inspection doors shouldbe installed at strategic points in the exhaust duct work for periodic
inspection and cleaning.