MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Tel.: + 49 - 2263 - 880 •Fax: + 49 - 2263 - 4588 •E-Mail: [email protected] •www.mdtautomation.de
Stand: 0212
Technische Daten
Technical Data BE-08000A.01
Konguration
Conguration
Ausbaustufe
Signal voltage
potentialfreier Kontakt
oating contact
Anzahl Eingänge
Number of Inputs 8/16
Nennspannung
Power Supply
Versorgungsspannung
Mains voltage KNX Bus
Leistungsaufnahme typ.
Power Consumption --
Max. Kabelquerschnitt
Permitted wire gauge
Schraubklemmen
Screw terminal
0,5 - 4,0mm² solid core
0,5 - 2,5mm² nely stranded
KNX Busklemme
KNX busconnection terminal 0,8mm Ø, single core
Max. Eingangsleitungslänge
Permitted input cable length 100m **
Umgebungstemperatur
Operation temperature range 0 bis + 45°C
Schutzart
Enclosure IP 20
Abmessungen (B x H x T)
Design (W x H x D) 100mm x 40mm x 88mm
Technische Daten Binäreingang BE AP- Technical Data Binary Input BE AP
BE-08xxx.01 BE-16xxx.01
Allgemeine Sicherheitshinweise - Important safety notes
Lebensgefahr durch elektrischen Strom - Danger High Voltage
Das Gerät darf nur von Elektrofachkräften montiert und angeschlossen werden. Beachten sie die länderspezischen •
Vorschriften sowie die gültigen KNX-Richtlinien. Installation and commissioning of the device only be carried out by
authorised electricans. The relevant standards, directives, regulations and instructions must be observed.
Use in USA is prohibited.
Vor Arbeitsbeginn am Gerät immer über die vorgeschalteten Sicherungen spannungsfrei schalten.•
Disconnect the mains power supply prior to installation or disassembly.
Anschlußklemmen, Bedien- und Anzeigeelemente Binäreingang BE AP
Terminals, Operating and Display Binary Input BE AP
Betriebsanleitung Binäreingang BE AP
nur für autorisiertes Elektrofachpersonal
Operating Instructions Binary Input BE AP
for authorised electricans
1
2
3
4
BE-08000A.01
1 - Busanschlußklemme
- KNX busconnection terminal
2 - Programmiertaster
- Programming key
3 - Rote Programmier LED
- Red programming LED
4 - Anschlußklemmen
- Output power terminal
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Tel.: + 49 - 2263 - 880 •Fax: + 49 - 2263 - 4588 •E-Mail: [email protected] •www.mdtautomation.de
Stand: 0212
Anschlußbeispiel BE-08000A.01 - Exemplary circuit design BE-08000A.01
Beschreibung Binäreingang BE AP- Description Binary Input BE AP
Der Binäreingang ist in drei Varianten erhältlich, Eingangsspannungsbereich 24VDC, 230VAC und Eingangsbeschaltung über
potentialfreie Taster. Die Binäreingänge erkennen Zustandsänderungen an Ihren Eingängen und lösen abhängig von der Parametrierung
KNX/EIB Telegramme aus. An den einzelnen Eingängen können Taster/Lichtschalter, Tür und Fensterkontakte sowie Hilfskontakte abgefragt
werden. Als besonders Merkmal sind vier logische Funktionmodule integriert. Jedes Funktionmodul kann alle Eingänge sowie zwei externe
Objekte logisch auswerten. Damit können einfach Telegramme wie zb. „alle Fenster geschlossen“ oder „EG geschlossen“ und sonstige
Meldefunktionen erzeugt werden. Jeder Eingang ist durch die ETS3 individuell parametrierbar. Von der Telegrammratenbegrenzung über
Entprellzeit, Dimmer/Jalousiefunktion, Impuls/Schaltzähler, Kontaktart und Sperrobjekte stehen zahlreiche Funktionen zur Auswahl.
Der Binäreingang ist zur Aufputzmontage in Abzweigkästen, z.B. in Zwischendecken oder in Doppelböden, vorgesehen.
Die Montage muß in trockenen Innenräumen erfolgen.
The MDT Binary Inputs are available in 3 versions, input detection of 24VAC signals, input detection of 230VAC signals and reading out
of oating contacts. If the inputs conditions change, a KNX/EIB telegram is sent on the bus. You can connect conventionel push-buttons
or auxiliary contacs (e.g. door and window contacs) to the device. The Binary Inputs include four integrated logical modules to implement
logical operations and logical control. These logical modules interpret all the inputs plus two external objects. So you can easily create KNX/
EIB telegrams which are required in daily practice (e.g. fault telegrams or „all windows closed“). Each input is parameterised individually via
ETS3. The device provides extensive functions like switching of lighting, operation of blinds and shutters, counting of pulses, debounce time,
contact typ and telegram rate limitation. The command for rising and falling edge can be dened independently and with the block commu-
nication object each channel can be blocked or released. The logic module can release two telegrams after receiving a trigger signal from the
inputs. The Binary Input is a installation device for xed installation in dry rooms. It ts into wiring boxes.
Montage und Anschluß Binäreingang BE AP - Installation Binary Input BE AP
1. Montieren Sie den Binäreingang im Abzweigkästen. Place the Binary Input into a wiringbox.
2. Schließen Sie den Binäreingang am KNX Bus an. Connect the Binary Input to the KNX bus.
3. Verkabeln Sie den Binäreingang laut Zeichnung.
Wire up the Binary Input as descripted in the circuit diagram.
4. Busspannungsversorgung zuschalten. Switch on KNX power supply.
Inbetriebnahme Binäreingang BE AP - Commissioning Binary Input BE AP
Hinweis: Die Produktdatenbank nden Sie unter www.mdtautomation.de\downloads.html
Note: Before commisioning please download application software at www.mdtautomation.de\downloads.html
1. Pysikalische Addresse vergeben und Applikationsprogramm in der ETS3 erstellen.
Assign the physical address and set parameters with the ETS3.
2. Laden Sie die Physikalische Addresse und das Applikationsprogramm in den Binäreingang.
Drücken Sie den Programmiertaster wenn Sie dazu aufgefordert werden.
Upload the pysical address and parameters into the Binary Input.
After request press programming button.
3. Die rote LED erlischt nach erfolgreicher Programmierung.
After sucessfull programming the red LED goes out.

Popular I/O System manuals by other brands

Murrelektronik MODLINK MSDD DBL COMBI INSERT manual

Murrelektronik

Murrelektronik MODLINK MSDD DBL COMBI INSERT manual

M-system R7C-MS4 instruction manual

M-system

M-system R7C-MS4 instruction manual

National Instruments FIELDPOINT FP-PWM-520 operating instructions

National Instruments

National Instruments FIELDPOINT FP-PWM-520 operating instructions

Puls Dimension C Series manual

Puls

Puls Dimension C Series manual

Rockwell Automation Allen-Bradley ArmorBlock 5000 Series user manual

Rockwell Automation

Rockwell Automation Allen-Bradley ArmorBlock 5000 Series user manual

NCR 7600-K021 Kit instructions

NCR

NCR 7600-K021 Kit instructions

Moxa Technologies ioLogik E1210 user manual

Moxa Technologies

Moxa Technologies ioLogik E1210 user manual

Festo VIGE-03-FB Series Supplementary Description

Festo

Festo VIGE-03-FB Series Supplementary Description

National Instruments C Series CALIBRATION PROCEDURE

National Instruments

National Instruments C Series CALIBRATION PROCEDURE

WAGO 750 Series manual

WAGO

WAGO 750 Series manual

WAGO 750-540 manual

WAGO

WAGO 750-540 manual

Elpro Technologies Condor ELPRO 415U-1-Cx Series Configuration manual

Elpro Technologies

Elpro Technologies Condor ELPRO 415U-1-Cx Series Configuration manual

Spectrum Controls Micro800 2085-IR8-SC user manual

Spectrum Controls

Spectrum Controls Micro800 2085-IR8-SC user manual

ADLINK Technology NuDAQ cPCI-7248 user guide

ADLINK Technology

ADLINK Technology NuDAQ cPCI-7248 user guide

Yamaha LMY2-MLAB manual

Yamaha

Yamaha LMY2-MLAB manual

Curtis Instruments 1351 manual

Curtis Instruments

Curtis Instruments 1351 manual

FortrezZ MIMO2+ user manual

FortrezZ

FortrezZ MIMO2+ user manual

Siemens SIMATIC ET 200AL manual

Siemens

Siemens SIMATIC ET 200AL manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.