Murrelektronik MODLINK MSDD DBL COMBI INSERT User manual

Operating instructions 4000-68000-4390003_ina_en_12 1/19
Murrelektronik GmbH +49 7191 47-0
Falkenstraße 3 | 71570 Oppenweiler +49 7191 47-491000
ENGLISH (en)
Document Product designation
Operating instruc-
tions
Modlink MSDD dbl combi insert
Version Art. no.
1.2 4000-68000-4390003
This document is valid for the following products:
Article number Product designation
4000-68000-4300000 MODLINK MSDD DBL COMBI INSERT GERMANY
RCD opening
4000-68000-4300001 MODLINK MSDD DBL COMBI INSERT GERMANY
1xRJ45 fem./fem. + RCD opening
4000-68000-4300003 MODLINK MSDD DBL COMBI INSERT GERMANY
1xRJ45+USB-A + RCD opening
4000-68000-4310000 MODLINK MSDD DBL COMBI INSERT FRANCE
RCD opening
4000-68000-4310001 MODLINK MSDD DBL COMBI INSERT FRANCE
1xRJ45 fem./fem. + RCD opening
4000-68000-4310003 MODLINK MSDD DBL COMBI INSERT FRANCE
1xRJ45+USB-A + RCD opening
4000-68000-4320000 MODLINK MSDD DBL COMBI INSERT GREAT BRITAIN
RCD opening
4000-68000-4320001 MODLINK MSDD DBL COMBI INSERT GREAT BRITAIN
1xRJ45 fem./fem. + RCD opening
4000-68000-4320003 MODLINK MSDD DBL COMBI INSERT GREAT BRITAIN
1xUSB, 1xRJ45 fem./fem. + RCD opening
4000-68000-4330000 MODLINK MSDD DBL COMBI INSERT ITALY
RCD opening
4000-68000-4330001 MODLINK MSDD DBL COMBI INSERT ITALY
1xRJ45 fem./fem. + RCD opening
4000-68000-4330003 MODLINK MSDD DBL COMBI INSERT ITALY
1xRJ45+USB-A + RCD opening
4000-68000-4340000 MODLINK MSDD DBL COMBI INSERT SWITZERLAND
RCD opening
© Murrelektronik GmbH

2/19 Operating instructions 4000-68000-4390003_ina_en_12
4000-68000-4340001 MODLINK MSDD DBL COMBI INSERT SWITZERLAND
1xRJ45 fem./fem. + RCD opening
4000-68000-4360000 MODLINK MSDD DBL COMBI INSERT AUSTRALIA
RCD opening
4000-68000-4360001 MODLINK MSDD DBL COMBI INSERT AUSTRALIA
1xRJ45 fem./fem. + RCD opening
4000-68000-4380001 MODLINK MSDD DBL COMBI INSERT CHINA
1xRJ45 fem./fem. + RCD opening
4000-68000-4390000 MODLINK MSDD DBL COMBI INSERT GERMANY YELLOW
RCD opening
4000-68000-4390001 MODLINK MSDD DBL COMBI INSERT GERMANY YELLOW
1xRJ45 fem./fem. + RCD opening
4000-68000-4390003 MODLINK MSDD DBL COMBI INSERT GERMANY YELLOW
1xRJ45+USB-A + RCD opening
4000-68000-4400001 MODLINK MSDD DBL COMBI INSERT FRANCE SC
1xRJ45 fem./fem. + RCD opening
4000-68000-4410001 MODLINK MSDD DBL COMBI INSERT FRANCE WITH LED
1xRJ45 + RCD opening
4000-68000-4410003 MODLINK MSDD DBL COMBI INSERT FRANCE WITH LED
1xRJ45+USB-A + RCD opening

Introduction
Operating instructions 4000-68000-4390003_ina_en_12 3/19
1 Introduction
Symbols
CAUTION!
Type and source of danger.
Consequences if the danger is ignored.
Avoiding (measures to prevent the danger).
NOTE
Other technical information and notes of Murrelektronik GmbH.
RECOMMENDATION
Notes with this symbol are recommendations of Murrelektronik GmbH.
PRODUCTS AND ACCESSORIES
This symbol indicates accessories or product recommendations.
Instruction for
use
An arrow marks instructions.
Read and observe the instructions.
1 | If they are numbered, it is absolutely necessary to follow them in the
correct order.
2 | Read and observe the instructions.
Service and support
Sales and distri-
bution
Our sales employees in the indoor and outdoor service and our techni-
cians will support you at any time.
Pictogram Signal Signal
word
Meaning Consequences if ig-
nored
Danger! Immediate danger Death or serious injuries
Warning! Possible danger Death or serious injuries
Caution! Low-risk danger Minor injuries
Attention! Possible material dam-
age
Damage to the device
and/or the system.

Introduction
4/19 Operating instructions 4000-68000-4390003_ina_en_12
Customer Ser-
vice Center
(CSC)
Our staff of the Customer Service Center will help you with all questions
concerning installation and start-up. They support you, for example, if
you have problems with combining hardware and software products
from different manufacturers.
Call us on +49 7191 47-2050 or send us an
e-mail to: support@murrelektronik.com
General notes
Storage and
Transport
Avoid mechanical shocks during transport or operation.
Observe the climatic conditions according to chapter
"Technical data".
Environmental-
ly friendly dis-
posal
Dispose of the product at the end of its service life according to the
applicable statutory regulations.
If you want to dispose of the product, it may be returned free of
charge to Murrelektronik GmbH. This also applies to the original
packaging and batteries or accumulators. Devices contaminated
with hazardous substances will not be taken back, neither for repair
nor for disposal.
We ensure disposal in accordance with German legislation. Trans-
port to the place of return is the the last owner's responsibility.

For your safety
Operating instructions 4000-68000-4390003_ina_en_12 5/19
2 For your safety
Use of the de-
vice
Comply with all safety and accident prevention regulations when
conducting project engineering, installation, startup, operation, and
testing of the device.
Check material resistance if aggressive media are used.
NOTE
Interventions in the hardware and software of the device dare, if they are
not described in this document, only be carried out by qualified person-
nel from Murrelektronik GmbH.
Designated use The device has been designed and manufactured for:
industrial use
operation according to specified ambient conditions
installation in an enclosure
Warranty and li-
ability claims
Warranty and liability claims will be lost if,
the product is not used as intended,
damage is due to the fact that the manual was not observed,
the staff was not competent.
NOTE
The operating instructions must be always available to the operator of
the machine where the device is used.
NOTE
This document merely describes the mounting of the MSDD. Additional
information and safety regulations can be found in the data sheets.

Technical Data
6/19 Operating instructions 4000-68000-4390003_ina_en_12
3 Technical Data
Socket
y el l ow V DE t yp e ,
FK
Socket
white VDE type,
FK
Socket yellow VDE type, FK - according to DIN VDE 0620
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 16 A
Number of poles 2 + protective earthing
contact
Connection type Spring clamp terminals
(FK)
Connecting cable ≤2 x 2.5 mm2
Stripped insulation 13 mm
Material PC RAL 1023 (yellow)
Socket used in:
4000-68000-4390000, 4000-68000-4390001, 4000-68000-4390003
Socket white VDE type, FK - according to DIN VDE 0620
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 16 A
Number of poles 2 + protective earthing
contact
Connection type Spring clamp terminals
(FK)
Connecting cable ≤2 x 2.5 mm2
Stripped insulation 10 mm
Material PC
Socket used in:
4000-68000-4300000, 4000-68000-4300001, 4000-68000-4300003

Technical Data
Operating instructions 4000-68000-4390003_ina_en_12 7/19
Socket
France type, SK
Socket
France type, FK
Socket France type, SK - according to NFC 61-314
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 16 A
Number of poles 2 + protective earthing
contact
Connection type Screw terminals (SK)
Connecting cable ≤2 x 4 mm²
Stripped insulation 10 mm
Material PC
Socket used in:
4000-68000-4310000, 4000-68000-4310001, 4000-68000-4310003
Socket France type, FK - according to NFC 61-314
Parameters Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 16 A
Number of poles 2 + protective earthing
contact
Type of connection Spring clamp terminals
(FK)
Connection cross-section ≤2 x 2.5 mm2
Stripping length 12 mm
Material PC
Socket used in:
4000-68000-4400001, 4000-68000-4400003

Technical Data
8/19 Operating instructions 4000-68000-4390003_ina_en_12
Socket
Italy type, SK
Socket
Switzerland
type, FK
Socket Italy type, SK - according to CEI 23-50
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 16 A
Number of poles 2 + protective earthing
contact
Connection type Screw terminals (SK)
Connection cross-section ≤2 x 4 mm2
Stripped insulation 9 mm
Material PC
Socket used in:
4000-68000-4330000, 4000-68000-4330001, 4000-68000-4330003
Socket Switzerland type, FK - according to IEC 669-1, EN 60669-1
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 10 A
Number of poles 2 + protective earthing
contact
Connection type Spring clamp terminals
(FK)
Connecting cable ≤2 x 1,5 mm2
Stripped insulation 10 mm
Material PC
Socket used in:
4000-68000-4340000, 4000-68000-4340001

Technical Data
Operating instructions 4000-68000-4390003_ina_en_12 9/19
Socket
England type,
SK
Socket
Australian type,
SK
Socket England type, SK - British Standard BS 1363
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 13 A
Number of poles 2 + protective earthing
contact
Connection type Screw terminals (SK)
Connecting cable ≤2 x 4 mm2
Stripped insulation 9 mm
Material PC
Socket used in:
4000-68000-4320000, 4000-68000-4320001, 4000-68000-4320003
Socket Australian type, SK
Parameter Conditions Value
Rated voltage 240 V
Frequency 50 Hz
Rated current 15 A
Number of poles 2 + protective earthing
contact
Connection type Screw terminals (SK)
Connecting cable ≤2 x 4 mm2
Stripped insulation 9 mm
Material PC
Approval SABS, AUS
Socket used in:
4000-68000-4360000, 4000-68000-4360001

Technical Data
10/19 Operating instructions 4000-68000-4390003_ina_en_12
Socket
China type, SK
Socket
France type with
LED, FK
Socket China type, SK
Parameter Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 10 A
Number of poles 2 + protective earthing
contact
Connection type Screw terminals (SK)
Connecting cable single-wire ≤2 x 4.0 mm2
Connecting cable finely stranded ≤2 x 4.0 mm2
Stripped insulation 9 mm
Socket used in:
4000-68000-4380001
Socket France type with LED, FK - according to NFC 61-314
Parameters Conditions Value
Rated voltage 250 V
Frequency 50 Hz
Rated current 16 A
Number of poles 2 + protective earthing
contact
Type of connection Spring clamp terminals
(FK)
Connection cross-section ≤2 x 2.5 mm2
Stripping length 12 mm
Material PC
Socket used in:
4000-68000-4410001, 4000-68000-4410003

Technical Data
Operating instructions 4000-68000-4390003_ina_en_12 11/19
RJ45 female / fe-
male
USB female / fe-
male
8-pole RJ45 female / female, shielded
Parameters Conditions Value
Rated voltage UL Rating ≤42.4 V
30 V
Operating current UL Rating ≤175 mA
Specification According to DIN EN 50173-
1;2011
Cat 5e (100 MHz)
Connection type Both sides RJ45
Mounting of the
connector
Front side Snap-lock system,
pluggable
Mounting of the
connector
Rear side Snap-lock system,
pluggable
Enclosure Tin-plated
Plastic UL 94V-0 Technical thermoplastic
Contacts Phosphor bronze
Coating Gold on nickel
Plug-in cycles ≤50
USB 3.0 form A - female / female
Parameter Conditions Value
Rated voltage Voltage supply
Pin 1 (V+) and pin 4 (GND)
≤12 V
Rated voltage UL Rating ≤42,4 V
Operating current ≤2 A
Operating current UL Rating ≤175 mA
Data rate ≤5 Gbits/s
Specification Downward compatible USB 3.0
Fastening of the
connection plug
Front side Plug-in
Fastening of the
connection plug
Rear side Pluggable, secured with
cable tie

Technical Data
12/19 Operating instructions 4000-68000-4390003_ina_en_12
Environmental characteristics
Climatic
Parameter Conditions Value
Installation height Above sea level ≤2000 m
Climate class EN 50178 3K3
Article number Parameter Conditions Value
4000-68000-4390003
4000-68000-4310000
4000-68000-4320000
4000-68000-4330000
4000-68000-4340000
4000-68000-4360000
4000-68000-4390000
Storage tempera-
ture
Operating tem-
perature
-10 °C ... +60 °C
-5 °C ... +50 °C
Article number Parameter Conditions Value
4000-68000-4300001
4000-68000-4300003
4000-68000-4310001
4000-68000-4310003
4000-68000-4320001
4000-68000-4320003
4000-68000-4330001
4000-68000-4330003
4000-68000-4340001
4000-68000-4360001
4000-68000-4380001
4000-68000-4390001
4000-68000-4390003
Storage tempera-
ture
Operating tem-
perature
+5 °C ... +40 °C
+5 °C ... +40 °C

Technical Data
Operating instructions 4000-68000-4390003_ina_en_12 13/19
Electrical safety
Article number Parameter Conditions Value
4000-68000-4400001 Storage tempera-
ture
Operating tem-
perature
-10 °C ... +70 °C
-5 °C ... +50 °C
Article number Parameter Conditions Value
4000-68000-4410001
4000-68000-4410003
Storage tempera-
ture
Operating tem-
perature
-10 °C ... +70 °C
-5 °C ... +35 °C
Parameter Conditions Value
Degree of pollution 2
Degree of
protection
Front side
EN 60529
IP20
Degree of
protection
Rear side
EN 60529
IP00

Technical Data
14/19 Operating instructions 4000-68000-4390003_ina_en_12
Mechanical data
Dimension of insert
Fig. 3-1: Full equipment, exemplary assembly
Parameter Conditions Value
Dimension (H) 87,5 mm
Dimension (B) 115,5 mm
Dimension (T) 69 mm

Mounting
Operating instructions 4000-68000-4390003_ina_en_12 15/19
4 Mounting
Fig. 4-1: Mounting in mounting frame, exemplary assembly

Mounting
16/19 Operating instructions 4000-68000-4390003_ina_en_12
Fig. 4-2: Mounting of RJ45
Fig. 4-3: Mounting of USB
M3 0.5 Nm +/- 0.1 Nm Art.-No.
7000-98001-0000000

Mounting
Operating instructions 4000-68000-4390003_ina_en_12 17/19
NOTE
The shielding plate has to be connected according to Directive EN
61439-1.
NOTE
Grounding strap (see Accessories), M4 and M5 toothed washers, M4
nut not included in scope of delivery.
Grounding strap fastening
Fig. 4-4: Grounding strap fastening
1 | M5 DIN 6797
2 | M4
3 | M4 DIN 6797
4 | M4 DIN 934
M4 0.9 +/- 0.1 Nm 7 mm

Installation
18/19 Operating instructions 4000-68000-4390003_ina_en_12
5 Installation
WARNING!
High electrical voltages
Electric shock may cause life-threatening injuries.
Only an electric installer is allowed to connect the device!
Protective mea-
sures during
connection work
According to IEC 60364 -Protection against electric shock
WARNING!
Risk of fire due to short circuit or overload
This may result in death or serious injuries.
The sockets have to be secured against short circuit and overload.
Adapt the strength of current of the fuse to the corresponding sock-
et. Use only a suitable fuse.
Securing
against short
circuit and over-
load
According to IEC 60950-1 Information Technology Equipment -
Safety - Part 1
WARNING!
Electric shock
This may result in death or serious injuries.
Operate with installed circuit breakers only!
Circuit breakers
NOTE
Slots for circuit breakers by Siemens 5SU 1356-7KK10 or with identical
design.
NOTE
The electric circuits connected to the data and communication interfaces
must meet the requirements of SELV circuits (Safety Extra-low Voltage
Circuit), TNV electric circuits (Telecommunications Network Voltage Cir-
cuit) or the requirements to electric circuits with current limitation accord-
ing to IEC 60950-1.

Operation
Operating instructions 4000-68000-4390003_ina_en_12 19/19
6 Operation
NOTICE
Defective and damaged devices
They can cause material damage. The correct function of the devices is
not guaranteed.
Replace defective and damaged devices.
Clean soiled contacts using oil-free compressed air or a leather
cloth only.
Do not use contact spray.
Accessories
PRODUCTS AND ACCESSORIES
You will find a wide range of products in our catalog or
in our Murrelektronik online shop http://shop.murrelektronik.com
Notes
This manual suits for next models
23
Table of contents
Other Murrelektronik I/O System manuals

Murrelektronik
Murrelektronik MVP12 Series User manual

Murrelektronik
Murrelektronik xtreme DB DP-34005-12 User manual

Murrelektronik
Murrelektronik Data Panel xtremeDB xDB08-PVE User manual

Murrelektronik
Murrelektronik MVP8 Series User manual

Murrelektronik
Murrelektronik DATA PANEL xtremeDB DP-34044-3 User manual

Murrelektronik
Murrelektronik CUBE20S User manual