15
Discharge
It is a requirement of Building Regulation G3 that any
discharge from an unvented system is conveyed to where
it is visible, but will not cause danger to persons in or about
the building. The tundish and discharge pipes should be
fitted in accordance with the requirements and guidance
notes of Building Regulation G3. The G3 Requirements
and Guidance section 3.50 - 3.63 are reproduced in the
following sections of this manual. For discharge pipe
arrangements not covered by G3 Guidance advice should
be sought from your local Building Control Officer. Any
discharge pipe connected to the pressure relief devices
(expansion valve and temperature/pressure relief valve)
must be installed in a continuously downward direction
and in a frost free environment.
Water may drip from the discharge pipe of the pressure
relief device. This pipe must be left open to the
atmosphere. The pressure relief device is to be operated
regularly to remove lime deposits and to verify that it is
not blocked.
G3 REQUIREMENT
“...there shall be precautions...to ensure that the hot
water discharged from safety devices is safely conveyed
to where it is visible but will not cause danger to persons
in or about the building.”
The following extract is taken from the latest G3
Regulations
Discharge pipes from safety devices
Discharge pipe D1
3.50 Each of the temperature relief valves or combined
temperature and pressure relief valves specified in 3.13
or 3.17 should discharge either directly or by way of
a manifold via a short length of metal pipe (D1) to a
tundish.
3.51 The diameter of discharge pipe (D1) should be not
less than the nominal outlet size of the temperature relief
valve.
3.52 Where a manifold is used it should be sized to accept
and discharge the total discharge from the discharge
pipes connected to it.
3.53 Where valves other than the temperature and
pressure relief valve from a single unvented hot water
system discharge by way of the same manifold that is
used by the safety devices, the manifold should be
factory fitted as part of the hot water storage system unit
or package.
Tundish
3.54 The tundish should be vertical, located in the same
space as the unvented hot water storage system and be
fitted as close as possible to, and lower than, the valve,
with no more than 600mm of pipe between the valve
outlet and the tundish (see fig 12).
Note: To comply with the Water Supply (Water Fittings)
Regulations, the tundish should incorporate a suitable air
gap.
3.55 Any discharge should be visible at the tundish. In
addition, where discharges from safety devices may not
be apparent, e.g. in dwellings occupied by people with
impaired vision or mobility, consideration should be given
to the installation of a suitable safety device to warn
when discharge takes place, e.g. electronically operated.
Discharge pipe D2
3.56 The discharge pipe (D2) from the tundish should:
(a) have a vertical section of pipe at least 300mm long
below the tundish before any elbows or bends in the
pipework (see fig. 12 page 17); and
(b) be installed with a continuous fall thereafter of at
least 1 in 200.
3.57 The discharge pipe (D2) should be made of:
(a) metal; or
(b) other material that has been demonstrated to be
capable of safely withstanding temperatures of the water
discharged and is clearly and permanently marked to
identify the product and performance standard (e.g. as
specified in the relevant part of BS 7291).
3.58 The discharge pipe (D2) should be at least one pipe
size larger than the nominal outlet size of the safety device
unless its total equivalent hydraulic resistance exceeds
that of a straight pipe 9m long, i.e. for discharge pipes
between 9m and 18m the equivalent resistance length
should be at least two sizes larger than the nominal
outlet size of the safety device; between 18 and 27m at
least 3 sizes larger, and so on; bends must be taken into
account in calculating the flow resistance. See Fig 12,
Table 4 and the worked example.
Note: An alternative approach for sizing discharge
pipes would be to follow Annex D, section D.2 of BS
6700:2006 Specification for design, installation, testing
and maintenance of services supplying water for domestic
use within buildings and their curtilages.
3.59 Where a single common discharge pipe serves more
than one system, it should be at least one pipe size larger
than the largest individual discharge pipe (D2) to be
connected.
3.60 The discharge pipe should not be connected to a
soil discharge stack unless it can be demonstrated that
the soil discharge stack is capable of safely withstanding
temperatures of the water discharged, in which case, it
should:
(a) contain a mechanical seal, not incorporating a water
trap, which allows water into the branch pipe without
allowing foul air from the drain to be ventilated through
the tundish;
(b) be a separate branch pipe with no sanitary
appliances connected to it;