Mestek UT-87 Instruction manual

UT2-1116
IN UNITED STATES: 260 NORTH ELM ST. WESTFIELD, MA 01085 800-465-8558 / FAX (413) 564-5815
IN CANADA: 7555 TRANMERE DRIVE, MISSISSAUGA, ONTARIO, L5S 1L4 (905) 670-5888 / FAX (905) 670-5782
SECTION 1: INTRODUCTION.................................................. 2
SECTION 2: SAFETY PRECAUTIONS .................................. 2
SECTION 3: SPECIFICATIONS
3.1 Specication Table................................................................. 3
3.2 Working Conditions ............................................................... 3
3.3 Overall Dimensions ............................................................... 4
SECTION 4: INSTALLATION
4.1 Installation Precautions ......................................................... 5
4.2 Installation: Positioning the Unit ............................................ 5
4.3 Minimum Clearances............................................................. 5
4.3a Floor Installation .................................................................. 6
4.4 Water Connections ................................................................ 7-8
4.5 Condensate Discharge.......................................................... 9
4.6 Venting Air ............................................................................. 9
SECTION 5: START-UP AND OPERATION
5.1 Control Function .................................................................... 10
5.2 Setting Temperature ..............................................................11-12
5.3 Usage of Remote Control......................................................13-14
5.4 Adjustable Parameters .......................................................... 14
SECTION 6: MAINTENANCE AND TROUBLE SHOOTING
6.1 Maintenance..........................................................................15-16
6.2 Trouble Shooting ................................................................... 16
SECTION 7: WIRING
7.1 Networking Wiring Diagram................................................... 17
7.2 Connections .......................................................................... 17
7.3 Wiring Diagram...................................................................... 18
Warranty ...................................................................................... 19
Terms and Conditions of Sale ..................................................... 19
MODEL UT
INSTALLATION,
OPERATION &
MAINTENANCE
MANUAL
Low Temperature
ThinWall Heating/Cooling Fan Coil
Units up to 1 Ton Capacity

2
Section 1: Introduction
Section 2: Safety Precautions
Thank you for choosing the ThinWall water fan coil. The products
strictly comply with design and production standards to provide
high quality operation, perfect performance, high reliability and
good adaptability.
These units are designed to operate at water temperatures
below 160°F. Operating at temperatures above 160°F may
result in severe damage to the product and void the warranty.
Read this installation and maintenance manual carefully before
installing and starting up the appliance. All repair or maintenance
work must be performed by the technical service department or
by professionally qualied personnel. Do not modify or attempt to
repair the appliance as this could cause serious injury and void
the manufacturer’s warranty.
This instruction manual must always accompany the appliance.
If it is lost or damaged, contact the local manufacturer technical
service center.
Failure to comply with these recommendations will void the
warranty.
• This appliance must be installed by an authorized installer.
• All repair or maintenance work must be performed by the
technical service department or by a professionally qualied
personnel.
• All repair or maintenance work must be performed in the
manufacturer’s specied period and times.
• Use genuine standard spare parts from the manufacturer for
any necessary repairs.
To prevent injury to the users and others and avoid damage to
the unit or other property, use the heat pump properly. Read this
manual carefully and understand the following information.
The following terms are used throughout this manual and bring
attention to the presence of potential hazards or to important
information concerning the product:
Indicates an imminently hazardous situation which,
if not avoided, will result in death, serious injury or
substantial property damage.
Indicates an imminently hazardous situation which,
if not avoided, will result in death, serious injury or
substantial property damage.
Indicates an imminently hazardous situation which,
if not avoided, may result in minor injury or property
damage.
Used to notify of special instructions on installation,
operation or maintenance which are important to
equipment but not related to personal injury haz-
ards.
In case of water leaks, turn the master switch of the system to
“OFF” and close the water taps. As soon as possible call the
manufacturer’s technical service department or professionally
qualied personnel. Do not attempt to personally repair the
appliance.
If the unit is not used for a long time, you should:
• Power off the unit.
• If there is no anti-freeze protection, drain out the water.
Packing list
Figure 1
PFP:
90 90
2-8
165mm
165mm
025~100
90
165mm
165mm
025~100
025
040
060
080
100
mm
0
200
400
600
800
90
025
040
060
080
100
mm
0
200
400
600
800
2-8
TEMP
MODEFAN
ON/OFF
PM
10:50 0 00
Screw cap
electrothermal
3-way valve
Feet
optional
Screw
Toggle bolts
Brackets
Installation Template
Vertical Water Fan Coil ManualDrain Pipe
Flexible Water
Connectors
Remote controller optional
Code Compliance
Fan coil unit installation must conform to the requirements
of the local authority having jurisdiction, or in the absence of
such requirements, to the National Board of Fire Underwriters
regulations. Fan coil unit meets ETL listing requirement.
All electrical wiring must be in accordance with the National
Electrical Code ANSI/NFPA No. 70-latest edition and any
additional state or local code requirements. If an external
electrical source is utilized, the fan coil unit, when installed, must
be electrically grounded.

3
Section 3: Specications
3.1 Specication Table
3.2 Working Conditions
(1) Heating ambient temperature: 41-84.2°F, Inlet water temperature: 95-158°F.
(2) Cooling ambient temperature: 48.2-95°F, Inlet water temperature: 41-68°F.
Model UT-87 UT-135 UT-196 UT-246 UT-320
Heating Capacity* BTU/H 8700 13500 19600 24600 32000
Water Flow Rate GPM 1.0 1.5 2.2 2.8 3.5
Pressure Drop PSI 1.5 1.8 3.8 4.0 4.1
Cooling Capacity** TONS 1/4 1/2 3/4 1 1 1/4
Water Flow Rate GPM 0.8 1.5 1.9 2.6 3.3
Pressure Drop PSI 1.6 1.9 4 4.1 4.4
Air Volume CFM 94 188 270 340 381
Noise DB (A) 30 32 37 39 41
Power Supply 120V/1PH/60Hz
Power Input W 12 16 20 24 30
Water In/Out NPT 3/4
Drain INCH 5/8
Net Dimensions
Length
INCH
27-5/8 35-3/8 43-5/16 51-1/2 59-1/8
Width 5 1/8
Height 26 3/8
Shipping Dimensions
Length
INCH
29-1/8 37 44-7/8 52-13/16 60-5/8
Width 7-1/8
Height 28-11/16
Net Weight LBS 35 44 53 62 73
Ship Weight LBS 40 51 60 68 79
* Heating: Entering Water Temp. 158°F
** Cooling: Entering Water Temp. 45°F

4
Section 3: Specications (continued)
3.3 Overall Dimensions (Inches)
Figure 2 Product Model UT-87/135/196/246/320
Figure 3 Product Model UT-87/135/196/246/320
A
29-3/16
26-3/8
3-3/8
7-5/16
3-5/16
12-1/2
5-1/8
1-5/8
9-1/2
3-1/8
Unit Model
UT-87 UT-135 UT-196 UT-246 UT-320
35
-1/2
27-1/2
A(inch) 43-3/8 51-1/8 59-1/16
A
29-3/16
26-3/8
3-3/8
7-5/16
3-5/16
12-1/2
5-1/8
1-5/8
2

5
Section 4: Installation
4.1 Installation Precautions
To ensure that the installation is performed correctly
carefully follow the instructions indicated in this manual.
Failure to follow instructions indicated not only can cause
malfunctions of the appliance but also void the warranty.
It is important that the electrical installation is made in
accordance with local codes, respects the data indicated
in the technical sheet and is correctly earthed.
The appliance must be installed in a position that allows
for routine maintenance, such as lter cleaning.
The system inlet water temperature must not exceed
160°F. Failure to comply can severly damage the unit and
will void the warranty.
4.2 Positioning the Unit
Avoid installing the unit in close proximity to:
-positions subject to exposure of direct sunlight
-in proximity to sources of heat
-in damp areas or places with probable contact with water
-in places with oil fumes
-places subject to high frequencies
Make sure that:
-the wall on which the unit is to be installed on is strong
enough to support the weight
-the part of the wall being used does not have pipes or
electric wires passing through
-is free of obstacles which could interfere with the inlet
and outlet air ow
-is preferably an outside perimeter wall to allow the
discharge of condensation outside.
4.3 Minimum Clearances
Figure 5 indicates the minimum mounting distances be-
tween the wall-mounted cooler-convector and furniture
present in the room.
Figure 5
0.79inch 0. 79inch
3.54inch
15.7 5inch
5.51inch
A
B
C
E
Removal of Side Panel (Fig. 6)
Dismount the upper grill (Fig. 6 Ref. A) by unscrewing the
xing screws.
Lift the cover (Fig. 6 Ref. B) that protects the screw (Fig.
6 Ref. C) and unscrew it. Move the side panel slightly and
lift it out.
Figure 6
Wall installation or vertical oor
Using the paper template, trace the position of the wall
(Fig. 7). Use a suitable drill to make the holes with and
insert the toggle bolts (2 for each bracket) (Fig. 8 Ref. A);
afx the two brackets (Fig. 8 Ref. B).
Figure 7
Figure 8
PFPtemplate code: 20000-23030 9
Para l lel to th efloor
Level c heck line
16 5 mm
90
Level c heckline
165mm
025
040
06 0
08 0
100
0
200
400
600
80 0
90
025
040
060
08 0
100
0
20 0
400
60 0
800
2- 8Lo c a te hole
Make suretha tt he spac e be tw een two t emplates
is according to t he tabl e requ ir ement whe n
installing PFP 025 to 10 0.
The distancefrom the center of
locatehole to the topedge of
machineis 165mm
The distancefrom the center of
locatehole to the topedge of
machineis 165mm
2-8 L o c ateh ole
Make suret ha t the s pace be tweentwo templates
is accordingto the tabl e requ irement when
installing PFP 025to 100.
Water inlethole
without electrothermal3-way valve
Water inlethole
Water outlethole
Condensation drainhole
The distancebetween
two templates(mm)
The distancebetween
two templates(mm)
Model
Model
The bottomof machine The bottomof machine
Fold 90degree along thisline Fold90 degree along thisline
R es e rvedare afor wa terp ipe hol e
Paral lel tothe f loor
A
B
This manual suits for next models
4
Table of contents
Other Mestek Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual