Mestek HW-06-ECM Instruction manual

HWL2-0818
IN UNITED STATES: 260 NORTH ELM ST. WESTFIELD, MA 01085 800-465-8558 / FAX (413) 564-5815
IN CANADA: 7555 TRANMERE DRIVE, MISSISSAUGA, ONTARIO, L5S 1L4 (905) 670-5888 / FAX (905) 670-5782
MODEL HW-ECM
INSTALLATION,
OPERATION &
MAINTENANCE
MANUAL
Low Temperature
High Wall Heating/Cooling Fan Coil
Units up to 2 Ton Capacity
A. General Description...........................................................2
B. Technical Data.................................................................3-5
GeneralSpecication...........................................................3
CoilData ..............................................................................4
SoundPowerandPressureData ........................................4
DimensionalDrawings .........................................................5
C. Service and Installation................................................6-11
InstallationofHigh-WallUnit................................................6
SelectingaLocation ............................................................6
MountingPlateDimensions .................................................7
InstallingtheMountingPlate................................................7
DrillingtheCondensateDrainageHole ...............................8
InstallingtheHydronicUnit ..................................................8
DrainagePipingWorks ........................................................8
UnitMaintenanceandPreparation ......................................9
OpeningandClosingofLift-UpGrilleCover........................9
RemovingFrontCoverAssembly ........................................9
AirPurging ...........................................................................9
WiringConnections..............................................................9
D. ControlSpecications:CompleteControlPCB-
S Type Control ............................................................10-14
DenitionofInput/Output ...................................................10
WiringDiagramFullControlPCB–SControlType .......... 11
CongurationSettings .......................................................12
ControlLogicsfor2-PipeSystem ......................................13
WithThermoelectricValveConguration...........................13
SleepMode........................................................................14
AutoFanSpeed.................................................................14
LEDLights .........................................................................14
LEDDisplayandErrorDescription ....................................14
E. ControlSpecications:FlexibleControlPCB
W Type Control ...........................................................15-16
DenitionofInput/Output ...................................................15
WiringDiagramFlexibleControlPCB-
WControlType ..................................................................16
F. Users Interface.................................................................17
RemoteControlHandset ...................................................17
G. SensorResistanceR-TConversionTable................18-19
H. TroubleshootingGuide ...................................................20

2
Every product is manufactured to meet the
stringent requirements of the internationally
recognized ISO 9001 standard for quality
assurance in design, development and
production.
AllproductsconformtoULstandardforSafety
forHeatingandCoolingEquipmentUL19954th
Edition,October14,2011;
AllproductsconformtoCSAstandardforSafety
forHeatingandCoolingEquipmentCSAC22.2
No.236-11,4thEdition,October142011.
Allproductsconformtothe“WEEE”directiveto
guarantee correct standards of environmental
solutions.
ALWAYSMAKESURETHISMANUALREMAINSWITHTHEUNIT.READTHISMANUALBEFOREPERFORMINGANYOPERATION
ON THE UNIT.
INVESTING IN QUALITY, RELIABILITY & PERFORMANCE.
World Leading Design and Technology
Equipped with the latest air-conditioning test
rooms and manufacturing technology, we
produce over 50,000 fan coil units each year,
all conforming to the highest international
standardsofqualityandsafety.
The Highest Standards of Manufacturing
Inordertoguaranteetheveryhigheststandards
and performance, we manage every stage in
themanufacturingofourproducts.Throughout
the production process we maintain strict
control, starting with our extensive resources
in research and development through to the
design and manufacture of almost every
individualcomponent,frommoldedplasticsto
theassemblyofunitsandcontrollers.
Quality Controlled from Start to Finish
Ourhighly-trainedstaffandstrictqualitycontrol
methods enable us to produce products with
an exceptional reputation for reliability and
efciency, maintained over many years. As
well as full CE certication and ISO 9001,
severalproductsrangeshaveUL/ETLsafety
approval in the USA and Canada, Eurovent
performanceandsoundcerticationaswellas
ROHS compliance for Europe, giving you the
condenceofknowingourcompanyistheright
choicewhenselectingfancoilunits.
A. General Description
ThisHighWallUnitisdesignedtomeetandexceeddemandingrequirementsforefciency,quietoperationandappearance.The
sleek prole and elegantly styled cabinet complements any interior design theme, while the microprocessor assures accurate
environmentalcontrol.
Cabinet-thestylishcabinetisconstructedofdurableameresistantacrylonitrile-butadiene-styrene(ABS)plastic.Thesilverwhite
colorandroundedcornersprovideitsmodernlook.
WaterCoil-thewatercoilhasalargeheattransfersurfaceandutilizesthelatestnproletechnology.Itcombinesanadvanced
technologyapproachwiththesecurityofatraditionaldesignregardingtubethickness.Thewatercoilisalsoequippedwithanair
ventvalveandawaterpurgevalve.
Integral Hoses - an integral hose is a synthetic elastomer tube, with stainless steel outer braiding and brass connectors, which
enablesquick,lowcostconnectionswithnobrazing.
BlowerandMotor-theunitincorporatesonlyspeciallydesignedandtestedECmotors,allowingtheblowerwheeltoprovideoptimum
performanceinairow-efciencyandquietoperation.
Filters-washable,easy-to-remove,nemeshairltersarestandardtoallHighWallmodels.Tabslocatedonthefrontoftheunit
canbeunsnapped,allowingtheltertobeeasilysliddownwardandremoved.Notoolsarerequired,noranydismantlingofthe
equipment.
ISO 9001 QUALITY
ETL SAFETY STANDARDS
WEEE MARK

3
B. Technical Data
GeneralSpecication–HW-ECMSeries
Productrange:HW-ECMHydronicHighWall2PipewithECMotor
HW-[Size]-ECM 6 15 18
UnitConguration
Conguration 2-Pipe
NumberOfFanBlowers Single
PowerSupply (V/Ph/Hz) 115/1/60
Performance
Data
Air AirFlow
H
CFM
294 379 464
M 218 294 435
L 171 218 335
Cooling
CoolingCapacity
H
BTU/Hr
6967 10207 12602
M 5534 8394 11069
L 4620 6339 9040
SensibleCoolingCapacity
H 4889 7126 8808
M 3856 5822 7702
L 3202 4357 6247
Heating HeatingCapacity
H
BTU/Hr
11147 16331 20163
M 8854 13430 17710
L 7392 10142 14464
Electrical Fanmotorpower
H
W
18 26 30
M 13 20 20
L 10 13 13
FanMotorRunningCurrent@H115V A 0.284 0.364 0.544
Sound SoundPressureLevelH/M/L dB(A) 39/31/26 45/34/31 49/44/37
Hydronic
Weight
CoolingWaterFlowRate
H
GPM
1.39 2.03 2.52
M 1.1 1.68 2.2
L 0.92 1.26 1.81
CoolingPressureDrop
H
Ft.wg
7.53 8.92 6.12
M 5.09 6.37 4.91
L 3.75 3.95 3.48
HeatingWaterFlowRate GPM Sameas"CoolingWaterFlowRate"
@H/M/L
HeatingPressureDrop
H
Ft.wg
6.03 7.13 4.89
M 4.07 5.09 3.93
L 3 3.16 2.79
WaterContent gal 0.02 0.03 0.05
Water Type Socket(NPTThreadedFemale)
Connections In
in 1/2
Out
CondensateDrainageConnection 0.63
NetWeight lbs 26.5 28.7 30.9
a.CoolingMode(2-Pipe):
Returnairtemperature:80°FDB/67°FWB.
Inlet/Outletwatertemperature:45°F/55°F
b.HeatingMode(2-Pipe):
Returnairtemperature:70°F
Inletwatertemperature:140°F
AirGrilleDistribution-allunitsareequippedwithbothdeectorbladesandindependentdirectionalvanes,enablingsupplyairtobe
automaticallydistributed,andairowanddirectiontobecustomized.
Microprocessorcontrols(S3type)
The PCB (printed circuit board) Modbus microprocessor controls functionality of the indoor-fan motor, water valves (ON/OFF or
modulating)andelectricheater(optional),tomaintainroomconditionsatauser-denedsetpoint.Temperaturesettings,fanspeeds
andothercontrolfunctionscanbechangedbyeitherinfraredhandsetorwiredwallpad.
Electro-mechanicalcontrols(W3type)
A 24VAC power strip is provided. Louver stepping motor controlled from PCB. Normally open or normally closed contacts are
standard,allowingconnectionandcontrolofelddevices.
• HighefciencyECmotor.
• Cool,Heat,Auto,DehumidierandFanmodes.
• Sleep,Auto-Fan,DailyTimer,Auto-Restartwithmemoryfunctions.
• Userfriendlyremotecontrol.
• Heatandcooltemperatureprotectionsandsafetycutout.
• Manualcontrolpanelincabinet.
• Auxiliaryswitchforcoolingandheatingsignal.

4
SoundPowerandPressureData
Sound Pressure
Model HW-06-ECM HW-15-ECM HW-18-ECM
A-weighted 33.8 24.6 20.7 40.9 27.9 24.3 44.4 39.4 32
Sound Pressure dB(A)
Sound
Pressure
in 1/3
Octave-
bands
(unit:dB)
31.5Hz 11.5 -8.4 -5.1 1.1 -4.6 -3.8 -5.7 -5.3 2.2
63Hz 10 -3.8 -5.9 3.8 -6.2 -5.4 13.1 5.3 1.9
125Hz 17 -0.8 -3.8 12.9 1.7 2.5 17.9 11.2 5.8
250Hz 30.3 13.2 8.6 29 15.3 16.1 33.1 26.9 20.3
500Hz 35.1 17.3 11.9 32.4 20.5 21.3 36.6 31.1 25.9
1000Hz 32.3 11.9 7.1 31 16.4 17.2 34.7 29.3 22.2
2000Hz 26.1 7.7 5.9 26.6 10.3 11.1 31.5 24.6 15.2
4000Hz 18.3 6.6 6.1 16.9 6.3 7.1 22.5 15.3 8.7
8000Hz 14.8 5.7 5.1 7.8 4.9 5.7 11.2 6.9 5.7
16000Hz 8 -1.4 -1.3 -1.3 -2.2 -1.4 -1.1 1.5 -1.4
Speed H M L H M L H M L
Model Fin Height
(inch)
Fin Length
(inch) Fins per Inch No. of Rows No. of Copper No. of Circuits TubeDiameter
(inch)
HW-06-ECM 14.1 26.8
19.5
2 20 4 0.3
HW-15-ECM 14.1 26.8 2 26 5 0.3
HW-18-ECM 14.1 26.8 2 34 5 0.3
CoilData–2-PipeSystems

5
DimensionalDrawings–HW-06/15/18-ECM
(Alldimensionsareshownininches)
UnitDimensions
ABC D E F G H
1.57 4.13 34.45 2.17 4.13 R0.78 2.36 2.91
UnitDimensions
abcdef g h
7.87 2.17 1.18 1.18 8.66 9.02 0.39 11.81
UnitDimensions
1234
26.18 6.69 27.95 4.92
HW-06/15/18-ECM

6
C. Service and Installation
Operating Limits
PowerSupplies
WaterCircuit
InstallationofHighWallUnit
Selecting a Location
SelectthelocationfortheHighWallunitwiththefollowingconsiderations:
1. Theairinletandoutletareashouldbeclearwithoutobstructions.Theairshouldowfreely.
2. TheHighWallunitshouldbemountedonsolidwall.
3. Thelocationshouldalloweasyaccesstoconnectwaterpipeseasilyachievedrainage.
4. Ensuretheclearancearoundthefancoilunitconformstothefollowingdrawing.
5. Theunitshouldbeinstalledhigherthaneyelevel.
6. Avoidinstallingtheunitwithdirectsunlight.
Notes:
Requiredclearanceformaintenanceandservicingisasshownabove.
Alldimensionsshownininches.
7. Thesignalreceiverontheunitmustbekeptawayfromanyhighfrequencyemissionsource.
8. Keeptheunitawayfromuorescentlamps,whichmayaffectthecontrolsystem.
9. Avoidelectromagneticcontrolsysteminterference,ensurecontrolwiresareinstalledseparatelyfrom110VACpowersupplywires.
10.Useshieldedsensorcableswhereelectromagneticwavespresent.
11.Installanoiselterifthepowersupplycreatesanydisruptivenoises.
Volt Phase Hz
110-120 1 60
Minimumenteringwatertemperature 35.6°F(+2°C)
Maximumenteringwatertemperature 176°F(+80°C)
Watersiderecommendedmaximumpressure 232PSI(1600kPa)
Higher than eye level

7
Mounting Plate Dimensions
Installing the Mounting Plate
1. Selectthestructuralposition(e.g.apillarorlintel)onthewall.
2. Thentemporarilyfastenthemountingplateonthewallwithasteelnail.
3. Mountthemountingplatehorizontallyasshownintheabovegureorbymeansof
gradiometer.Failuretofollowthismaycausewatertodripindoorsandcreateatypicalnoise.
4. Fixthemountingplatebymeansofexpansionscrewsortappingscrews.
(Alldimensionsareininches)

8
Drilling the Condensate Drain Hole
1. Ensurethattheholeforcondensatedrainiscorrectlypositioned.Theheightshouldbelowerthanthebottomedgeoftheindoor
unit.
2. Drilla2.5"diameterholewithadescendingslope.
3. Sealitoffwithputtyafterinstallation.
Installing the Hydronic Unit
1. Passthepipingthroughtheholeinthewallandhooktheindoorunitonthemountingplatebytheupperhooks.
2. Movethebodyoftheunitfromsidetosidetoverifyifitissecurelyxed.
3. Whilepushingtheunittowardthewall,liftitslightlyfrombeneathtohookituponthemountingplatebythelowerhooks.
4. Makesuretheunitrmlyrestsonthehooksofthemountingplate.
Drain Piping Works
1. Installthedrainhosesothatitslopesdownwardslightlyforfreedrainage.Avoidinstallingitasshowninthebelowillustrations
markedwithan“X”.
2. Putwaterinthedrainpanandmakesurethatthewaterdrainsoutdoors.
3. Iftheexibledrainhoseprovidedwiththeindoorunitisnotlongenough,pleaseextenditbyjoiningittoaeldsuppliedextension.
Besuretoinsulatetheconnectingpartoftheextensionwithashieldpipeasshown.
4. Iftheattacheddrainhosepassesthroughanindoorarea,insulateitwithinsulationmaterial.

9
UnitMaintenanceandPreparation
Opening and Closing Of Lift-Up Grille Cover
RemovingFrontCoverAssembly
1. Setthehorizontallouvertothehorizontalposition.
2. Removethescrewcapsbelowthelouver,andthenremovethemountingscrews.
3. Openthelift-upgrillecoverbygraspingthepanelatbothsidesasshownabove.
4. Removetheremainingscrewslocatedinthecenterofthefrontcover.
5. Graspthelowerpartofthefrontcoverandpulltheentireassemblyoutanduptowardsyou.
Air Purging
1. After connecting the water inlet and outlet pipes to the main supply lines turn on the main breaker and operate the unit in
COOLINGmode.
2. Openthewaterinletvalveandoodthecoil.
3. Checkallconnectionsforwaterleakage.Ifnoleakisfound,openthepurgingvalvewithanopenendwrenchwhilesupporting
theunitwithyourotherhand.Thenpurgetheairtrappedinsidethecoil.Whenperformingthisactivity,takecarenottotouchthe
electricalparts.
4. Closethepurgingvalvewhennobubblesappear.
5. Openthewateroutletvalve.
Wiring Connections
Unitcomponentsarewiredtotheterminalblockoftheindoorunit.Wiringcanbeaccessedfromtheterminalblockinsidethecontrolbox.
Openthegrillecoverbyliftingfromthebottompositionindicated
bythearrows.
Closethegrillecoverbypressingdownatthepositionsindicated
bythearrows..

10
D.ControlSpecications:CompleteControlPCB-STypeControl
Abbreviations
Ts=Settingtemperature AUX1=Hotwaterfreecontact
Tr=Roomairtemperature AUX2=Chilledwaterfreecontact
Ti1=Chilledwatercoiltemperature MTV1=ChilledMotorizedvalve
Ti2=Hotwatercoiltemperature MTV2=HotMotorizedvalve
DenitionofInput/Output
I/O Code 2-Pipe
AnalogueInput Returnairsensor AI1 Returnairtemperature(Tr)
Coilsensor AI2 Chilled/hotwatercoilcircuit(Ti1)
Input LEDdisplay/IRreciever X-DIS1 DigitalcommunicationporttoLEDdisplay/IRreceiverboard.
Digitalinput Occupancycontact On/Off Windowcontacts:forremoteON/OFF(whenDIPBSW1=1).Economy
contacts:forremoteactivationofeconomymode(whenDIPBSW1=0).
Powerinput
Phase L1
Powersupply:115V/1Ph/60HzNeutral N1
Earth PE1
Voltageoutput
Fan CN4 Fandriver
Valve1 MTV1 2-pipecoilcircuitvalveoutput-chilled/hotwatervalve.
Voltageoutput(L)
Valve2 MTV2 Reserved
Output
Steppingmotor CN1 / CN2 Louversteppingmotorrelay
Auxiliarycontact2 AUX2 Coolingmodesignalrelay(NO).Voltagefreecontact.Toensurethe
sensitivityoftheconnection,pleasemakesuremaxwiringlength<100ft.
Auxiliarycontact1 AUX1 Heatingmodesignalswitch(NO).Voltagefreecontact.Toensurethe
sensitivityoftheconnection,pleasemakesuremaxwiringlength<200"100ft.

11
WiringDiagramFullControlPCB-SControlType
Wiring Schematic

12
MotorizedFanSpeedSettingsforDifferentModelsonDIPB:
Modeconguration:
HighWallUnitON/OFF
Thereare3waystoturnthesystemonoroff:
a) BytheON/OFFbuttononthehandsetorwiredwallpad.
b) Bytheprogrammabletimeronthehandsetorwiredwallpad.
c) BythemanualcontrolbuttonontheHighWallunit.
PowerOnSetting
Thereare3waystoturnthesystemonoroff:
a) Handsetonlyuserinterface:WhenthepowerONsignalisreceivedbytheunit,theMode,FanSpeed,Settemperature
andLouversettingwillbethesameasthehandsetsettingbeforethelastpowerOFF.
b) WhenthepowerONsignalisreceivedbytheHighWallunit,theMode,FanSpeed,Settemperature,Louversettingand
TimerON/OFFweeklyprogramwillbethesameasthehandsetsettingbeforethelastpowerOFF.
Unit Model Speed (RPM)
Low Medium High
HW-06-ECM 600 700 900
HW-15-ECM 700 800 1100
HW-18-ECM 900 1100 1300
DefaultRPM 900 1200 1350
DIPA-S1 Model
SW7 SW8 Model setting
0 0 Cool-Heat
0 1 Cool-Heat+boosterheater
1 0 Coolingonly
1 1 Cool+primaryheater

13
ControlLogicsFor2-PipeSystem(StandardUnit)
WithThermoelectricValveConguration
COOL MODE
a) MTV2,AUX1andheaterarealwaysoff.
b) IfTr≥Ts+1.8ºF(or+7.2ºFifeconomycontactisactivated),thencooloperationisactivatedandMTV1andAUX2areturnedon.
Indoorfanrunsatsetspeed.
c) IfTr<Ts,thencooloperationisterminatedandMTV1andAUX2areturnedoff.Indoorfanrunsatsetspeed.
d) TherangeofTsis60.8-86ºF
e) Indoorfanspeedcanbeadjustedtolow,medium,highandauto.
f) Whenturnedon,MTV1requires30secondsbeforeitisfullyopen.
g) Whenturnedoff,MTV1requires120secondsbeforeitisfullyclosed.
h) Whentheunitisturnedoff,theindoorfanwillshutdownafter5seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a) IfTi1≤35.6ºFfor2minutes,thenMTV1andAUX2areturnedoff.Ifindoorfanissetforlowspeed,itwillrunatmediumspeed.If
itissetatmediumorhighspeed,itwillkeeprunningatthesamespeed.
b) IfTi1≥41ºFfor2minutes,thenMTV1andAUX2areturnedon.Indoorfanrunsatsetspeed.
FAN MODE
a) Indoorfanrunsatthesetspeedwhileheater,MTV1,MTV2,AUX1andAUX2areturnedoff.
b) Indoorfanspeedcanbeadjustedtolow,mediumandhigh.
PRE-HEAT
a) IfTi1<96.8ºF(or82.4ºFdependingonDIPsetting),thenMTV1andAUX1areturnedon,indoorfanrunsat200RPM.
b) IfTi1≥100.4ºF(or86ºFdependingonDIPsetting),thenMTV1andAUX1areturnedon,indoorfanrunsatsetspeed.
c) Iftheindoorcoiltemperaturesensorisdamaged,thenthepre-heattimeissetfor2minutes.Indoorfanrunsatsetspeed.
POST-HEAT
a) IfTi1≥100.4ºF,thenMTV1andAUX1areturnedoff.Indoorfancontinuestorunatsetspeed.
b) If96.8ºF≤Ti1≤100.4ºF,thenMTV1andAUX1areturnedoff.Indoorfanmaintainsitsoriginalstate.
c) IfTi1<96.8ºF,thenMTV1andAUX1areturnedoff.Indoorfanrunsat200RPM.
d) Iftheindoorcoiltemperaturecoilisdamaged,thenthepost-heattimeissetfor3minuteswiththeindoorfanrunningatsetspeed.
OVER-HEAT PROTECTION OF INDOOR COIL
a) IfTi1≥167ºF,thenMTV1andAUX1areturnedoff.Indoorfanremainsonandrunsathighspeed.
b) IfTi1<158ºF,thenMTV1andAUX1areturnedon.Indoorfanremainsonandrunsatsetspeed.
c) Iftheindoorcoiltemperaturesensorisdamaged,thentheprotectionmodewillbeoverriddenandtheunitwillworkaccordingto
thepre-heatandpost-heatprogram.
DEHUMIDIFICATION MODE
a) MTV2,AUX1andheaterarealwaysoff.
b) IfTr≥77ºF,thenMTV1andAUX2willbeturnedonfor3minutes,andthenofffor4minutes.
c) If60.8ºF≤Tr<77ºF,thenMTV1andAUX2willbeturnedonfor3minutes,andthenofffor6minutes.
d) IfTr<60.8ºF,MTV1andAUX2willbeturnedofffor4minutes.
e) Attheendoftheabovedehumidicationcycle,thesystemwilldecidethenextdehumidicationcontroloption.Indoorfanwillrun
atlowspeedthroughoutthedehumidicationprocess.
AUTOMODE
a) Everytimetheunitisturnedon,MTV1isonwhileAUX1,AUX2andfanareoff.MTV2andtheheaterarealwaysoff.After120
seconds,thesubsequentoperationmodeisdecidedaccordingtothefollowing:
i. Ifthecoiltemperaturesensor(Ti1)≥96.8°F,thenMTV1,AUX1andfanturnonoroffaccordingtoHEATmode.
ii. IfTi1<96.8°F,thenMTV1,AUX2andfanturnonoroffaccordingtoCOOLmode.
b) UnitremainsinAUTOCOOLorAUTOHEATmodethroughouttheoperatingcycleuntiltheuserchangesthemodemanuallyor
restartstheunit.
c) ShouldtheTi1sensorfailorbedamaged,automodewillnotfunction.
Note:AUTOCOOLorAUTOHEAToperationsarethesameasCOOLorHEATmoderespectively.

14
SleepMode
a) Thesleepmodecanonlybesetwhentheunitisincoolmodeorheatmode.
b) Ifthesleepmodeisactivatedwhentheunitisincoolmode,thentheindoorfanwillrunatlowspeedandTswillincreaseby3.6ºF
over2hours.
c) Ifthesleepmodeisactivatedwhentheunitisinheatmode,thentheindoorfanwillrunatsetspeedandTswilldecreaseby3.6ºF
over2hours.
d) Changingthemodeofoperationwillcancelthesleepmode.
Thecoolmodesleepproleis: Theheatmodesleepproleis:
AutoFanSpeed
InCOOLmode,thefanspeedcannotchangeuntilithasrun
formorethan30seconds.Fanspeedisregulatedaccordingto
theprolebelow.
LEDLights
LEDDisplayandErrorDescription
InHEATmode,thefanspeedcannotchangeuntilithasrunfor
morethan30seconds.
For all units
Power/OperationLEDlight(bothgreen)
Uniton PowerLEDOff,OperationLEDOn
Unitinstandby PowerLEDOn,OperationLEDOff
For all units - Operation LED light (Green)
Error Description Blink Reason Remedy
Electricalheaterfailure GreenLEDblinks1times,
stopsfor3s
OnlyforunitwithEH.
EHsafetyswitchisopen.
1.Changefanspeedtohigh.
2.ReplacethedamagedEHsafetyswitch.
Indoorcoilsensor2
failure
GreenLEDblinks2times,
stopsfor3s
Ti2sensorunpluggedor
damaged.
1.CheckifTi2plugisconnectedornot.
2.Checkifsensor’sresistanceiscorrectornot.
Returnairsensor
failure
GreenLEDblinks3times,
stopsfor3s
Roomsensorunpluggedor
damaged.
1.CheckifTrplugisconnectedornot.
2.Checkifsensor’sresistanceiscorrectornot.
Indoorcoilsensor1
failure
GreenLEDblinks4times,
stopsfor3s
Ti1sensorunpluggedor
damaged.
1.CheckifTi1plugisconnectedornot.
2.Checkifsensor’sresistanceiscorrectornot.
Indoorcoillow
temperatureprotection
GreenLEDblinks5times,
stopsfor3s
Watertemperatureislower
than37.4ºF. Checkthewatertemperature.
Indoorcoiloverheat
protection
GreenLEDblinks6times,
stopsfor3s
Watertemperatureishigher
than158ºF. Checkthewatertemperature
ECmotorfailure GreenLEDblinks9times,
stopsfor3s NoECmotorfeedback 1.CheckDIPB-SW5andSW6setting.
2.ChecktheECmotor.

15
E.ControlSpecications:FlexibleControlPCB-WTypeControl
Abbreviation
Ti1=Chilledwatercoiltemperature
DenitionofInput/Output
I/O Code 2-Pipe
AnalogueInput ChilledwaterSensor AI1 Coilsensor(Ti1)
Powerinput
HighSpeed Lo 24Voltageinput(NO).Ifanyspeedispowered,theunitisturnedon.
Ifnospeedreceivespower,theunitisturnedoff.
MediumSpeed Med
LowSpeed Hi
Powerinput
Phase L
Powersupply:115V/1Ph/60HzNeutral N
Earth GND
Output
ECmotor CN3 ECmotoroutput
Steppingmotor CN1, CN2 Steppingmotoroutput
ElectricHeaterSignal CN4, CN5 ElectricHeatercontrolsignal
LEDDisplay X-DIS LEDDisplaysignal

16
WiringDiagramFlexibleControlPCB-WControlType
Wiring Schematic

17
F. Users Interface
RemoteControlHandset
Attention
When unit with handset is the master unit, its
settings are automatically sent to the slave units;
Auto Cool -Heat operation will be applicable in 4-
pipe system only.
“Swing” function is not applicable.
European version only uses degree C setting.
Swing
It is not available.

18
G.SensorResistanceR-TConversionTable
Resistance: R(77°F)=10KΩ±1%
BetaConstant: B(25/85)=3977±1%
T Rmin Rnom Rmax T Rmin Rnom Rmax
(°F) (KΩ) (KΩ) (KΩ) (°F) (KΩ) (KΩ) (KΩ)
-22 174 182.7 191.8 39.2 26.11 26.9 27.71
-20.2 163.4 171.5 179.9 41 24.85 25.59 26.34
-18.4 153.6 161.1 168.9 42.8 23.65 24.35 25.05
-16.6 144.4 151.3 158.5 44.6 22.52 23.17 23.83
-14.8 135.8 142.2 148.9 46.4 21.45 22.06 22.68
-13 127.8 133.8 140 48.2 20.44 21.01 21.59
-11.2 120.3 125.8 131.6 50 19.48 20.02 20.55
-9.4 113.3 118.4 123.8 51.8 18.58 19.7 19.58
-7.6 106.7 111.5 116.5 53.6 17.71 18.18 18.65
-5.8 100.6 105.1 109.7 55.4 16.9 17.33 17.77
-4 94.9 99.03 103.3 57.2 16.12 16.53 16.94
-2.2 89.51 93.39 97.41 59 15.39 15.77 16.16
-0.4 84.5 88.11 91.85 60.8 14.69 15.05 15.41
1.4 79.8 83.17 86.64 62.6 14.03 14.37 14.7
3.2 75.39 78.53 81.76 64.4 13.41 13.72 14.03
5 71.26 74.18 77.19 66.2 12.81 13.1 13.4
6.8 67.37 70.1 72.9 68 12.24 12.52 12.79
8.6 63.73 66.26 68.88 69.8 11.7 11.96 12.22
10.4 60.3 62.67 65.1 71.6 11.19 11.43 11.67
12.2 57.08 59.28 61.55 73.4 10.71 10.93 11.15
14 54.05 56.1 58.22 75.2 10.24 10.45 10.66
15.8 51.19 53.12 55.08 77 9.8 10 10.2
17.6 48.51 50.3 52.14 78.8 9.374 9.57 9.765
19.4 45.98 47.66 49.37 80.6 8.969 9.16 9.351
21.2 43.61 45.17 46.77 82.4 8.584 8.77 8.957
23 41.36 42.82 44.31 84.2 8.218 8.4 8.582
24.8 39.25 40.61 42 86 7.869 8.047 8.225
26.6 37.26 38.53 39.83 87.8 7.537 7.71 7.885
28.4 35.38 36.56 37.78 89.6 7.221 7.39 7.56
30.2 33.6 34.71 35.85 91.4 6.92 7.085 7.251
32 31.93 32.97 3402 93.2 6.633 6.794 6.956
33.8 30.35 31.32 32.3 95 6.36 6.517 6.675
35.6 28.85 29.76 30.68 96.8 6.099 6.252 6.407
37.4 27.44 28.29 29.15 98.6 5.85 6 6.151

19
Resistance: R(77°F)=10KΩ±1%
BetaConstant: B(25/85)=3977±1%
T Rmin Rnom Rmax T Rmin Rnom Rmax
(°F) (KΩ) (KΩ) (KΩ) (°F) (KΩ) (KΩ) (KΩ)
100.4 5.614 5.759 5.907 167 1.417 1.474 1.532
102.2 5.387 5.53 5.673 168.8 1.37 1.426 1.482
104 5.172 5.31 5.451 170.6 1.326 1.379 1.434
105.8 4.966 5.101 5.238 172.4 1.282 1.335 1.389
107.6 4.769 4.901 5.034 174.2 1.241 1.292 1.344
109.4 4.582 4.71 4.84 176 1.201 1.25 1.302
111.2 4.402 4.527 4.654 177.8 1.162 1.211 1.261
113 4.231 4.353 4.477 179.6 1.125 1.172 1.221
114.8 4.067 4.186 4.307 181.4 1.089 1.135 1.183
116.6 3.911 4.027 4.144 183.2 1.055 1.1 1.146
118.4 3.761 3.874 3.989 185 1.021 1.065 1.111
120.2 3.618 3.728 3.84 186.8 0.9891 1.032 1.077
122 3.481 3.588 3.697 188.6 0.9582 1 1.044
123.8 3.35 3.454 3.561 190.4 0.9284 0.9697 1.012
125.6 3.225 3.326 3.43 192.2 0.8998 0.9401 0.9818
127.4 3.105 3.204 3.305 194 0.8721 0.9115 0.9522
129.2 2.99 3.086 3.185 195.8 0.8455 0.8839 0.9237
131 2.88 2.974 3.07 197.6 0.8198 0.8573 0.8961
132.8 2.774 2.866 2.959 199.4 0.795 0.8316 0.8696
134.6 2.673 2.762 2.854 201.2 0.7711 0.8069 0.8439
136.4 2.576 2.663 2.752 203 0.748 0.783 0.8192
138.2 2.483 2.568 2.655 204.8 0.7258 0.7599 0.7953
140 2.394 2.477 2.562 206.6 0.7043 0.7376 0.7722
141.8 2.309 2.39 2.472 208.4 0.6836 0.7161 0.7499
143.6 2.227 2.306 2.386 210.2 0.6635 0.6953 0.7283
145.4 2.149 2.225 2.304 212 0.6442 0.6752 0.7075
147.2 2.073 2.148 2.224 213.8 0.6255 0.6558 0.6874
149 2.001 2.074 2.148 215.6 0.6075 0.6371 0.6679
150.8 1.931 2.002 2.075 217.4 0.59 0.619 0.6491
152.6 1.865 1.934 2.005 219.2 0.5732 0.6015 0.631
154.4 1.801 1.868 1.937 221 0.5569 0.5846 0.6134
156.2 1.739 1.805 1.872
158 1.68 1.744 1.81
159.8 1.623 1.686 1.75
161.6 1.569 1.63 1.692
163.4 1.516 1.576 1.637
165.2 1.466 1.524 1.583

20
H.TroubleshootingGuide
IN UNITED STATES: 260 NORTH ELM ST. WESTFIELD, MA 01085 800-465-8558 / FAX (413) 564-5815
IN CANADA: 7555 TRANMERE DRIVE, MISSISSAUGA, ONTARIO, L5S 1L4 (905) 670-5888 / FAX (905) 670-5782
This manual suits for next models
2
Table of contents
Other Mestek Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Samsung
Samsung AS09HM3N user manual

Mitsubishi Electric
Mitsubishi Electric PLA-M100EA installation manual

York
York YUHA 18 FS Service manual

EcoNet
EcoNet A2024AJVCA installation instructions

York
York YNKFZC024-055BAADAFX owner's manual

Mitsubishi Electric
Mitsubishi Electric MS-GK36VAT operating instructions