EM-7781-AP Rev.4 P. 1 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
DC VOLTAGE INPUT MODULE, 2 points
(Screw terminal) MODEL R6N-SV2
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
DC voltage input module ....................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
The unit is programmable using the PC Configurator Soft-
ware. For detailed information on the PC configuration, re-
fer to the R6CON users manual. The R6CON PC Configu-
rator Software is downloadable at our web site.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside a panel.
• Insert a noise filter for the input and communication line
connected to the unit. NEC TOKIN Model ESD-SR-250
or equivalent is recommended.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■HOT INSERTION/REMOVAL OF MODULES
• Removing or replacing modules does not affect other mod-
ules on the same backplane. It is possible to replace them
without removing the power supply. However, replacing
multiple modules at once may greatly change line voltage
levels. We recommend that you replace them one by one.
■GENERAL PRECAUTIONS
• Do NOT set the switches while the power is supplied.
The switches are used only for maintenance without the
power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■UNUSED INPUT CHANNELS
• Set the unused channels to -10 – +10 V range. Unused
channels left open with other settings may be equal to the
input lower than -15%, which sets a data abnormality at
the PLC or the host device.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Specifications
Body
Front Cover
Mounting Adaptor
INSTALLATION
Mount the unit on the base (model: R6N-BS).
R6N-SV2
EM-7781-AP Rev.4 P. 2 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
EXTERNAL VIEWS
8
6
7
3
4
5
2
1
0
F
E
D
C
B
A
9
• Front View (cover opened) • Side View
5678
1234
1
SW3
SW2
SW1
2345678
OFF
ON
0
16
SW3
SW2
SW1
Module Address
Setting
Operating Mode
Setting
Status LED
Power LED
■INDICATOR LED
ID COLOR FUNCTION
Power OFF Power supply is off
Green ON Power supply is on.
Status OFF Standing by (at the startup)
or communication error
Green ON Normal communication
Green blink Configuration mode
Red ON DIP switch error
Red blink
2 sec. interval
Parameter error
Red blink
0.5 sec. interval
Analog input overrange
(≤ -15% or ≥ 115%)
■MODULE ADDRESS
Module address is selectable between 0 and 31. Choose 0 or
16 with SW1 for offsetting the address selected with SW2 (0
to F, hexadecimal).
The module’s slot position on the base and the module ad-
dress are not necessarily correlated.
ADDRESS SW1 SW2 ADDRESS SW1 SW2
0 0 0 16 16 0
1 0 1 17 16 1
2 0 2 18 16 2
3 0 3 19 16 3
4 0 4 20 16 4
5 0 5 21 16 5
6 0 6 22 16 6
7 0 7 23 16 7
8 0 8 24 16 8
9 0 9 25 16 9
10 0 A 26 16 A
11 0 B 27 16 B
12 0 C 28 16 C
13 0 D 29 16 D
14 0 E 30 16 E
15 0 F 31 16 F
■OPERATING MODE
(*) Factory setting
• Conguration Mode
CONFIGURATION MODE SW3-8
DIP SW (*)
PC ■
■= ON, Blank = OFF
• INPUT RANGE
RANGE
INPUT 1 INPUT 2
SW3 SW3
123456
-10 – +10 V DC (*)
-5 – +5 V DC ■ ■
-1 – +1 V DC ■ ■
0 – 10 V DC ■ ■ ■ ■
0 – 5 V DC ■ ■
1 – 5 V DC ■ ■ ■ ■
0 – 1 V DC ■ ■ ■ ■
-0.5 – +0.5 V DC ■■■■■■
■= ON, Blank = OFF
Note: Be sure to set unused SW 3-7 to OFF.
R6N-SV2
EM-7781-AP Rev.4 P. 3 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
102 (4.02)
7.5 (.30)
*Screwdriver stem diameter: 6 mm (.24”) or less
102 (4.02)
8–M3
SCREW TERMINAL
WIRE INSERTION ANGLE
: approx. 35°
SCREWDRIVER
*
INSERTION ANGLE
: approx. 55°
5678
1234
■CONNECTION DIAGRAM
BUS CONNECTOR
INPUT 1
3
1
+
–
2
NARROW SPAN
WIDE SPAN
+
INPUT 2
7
5
+
–
6
NARROW SPAN
WIDE SPAN
+
INTERNAL
POWER
INTERNAL
BUS
• Wide span: -10 – +10 V DC, -5 – +5 V DC, 0 – 10 V DC,
0 – 5 V DC, 1 – 5 V DC
• Narrow span: -1 – +1 V DC, -0.5 – +0.5 V DC, 0 – 1 V DC
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.5 N·m
■SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Solderless terminals with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm2
3.2 (.13) dia.
4 min.
(.16)
5.8 max.
(.23)
5.5 max.
(.22)
R6N-SV2
EM-7781-AP Rev.4 P. 4 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R6CON for detailed operation.
■CHANNEL INDIVIDUAL SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Input range -10 to +10 V DC,
-1 to +1 V DC
-10 to +10 V DC
Lower range value -10.00 to +10.00 (V)
-1.00 to +1.00 (V)
-10.00 (V)
Upper range value -10.00 to +10.00 (V)
-1.00 to +1.00 (V)
10.00 (V)
Fine zero adjustment -320.00 to +320.00 (%) 0.00 (%)
Fine gain adjustment -3.2000 to +3.2000 1.0000
Scaled range Zero -32000 to +32000 0
Scaled range Span -32000 to +32000 10000
■CHANNEL BATCH SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Loss of internal bus commu-
nication detection time
0.0 – 99.9 (sec.) 1.0 (sec.)
Conversion rate 10, 20, 40, 80 (msec.) 80 (msec.)

Other MG I/O System manuals

MG M2BS-16U0 User manual

MG

MG M2BS-16U0 User manual

MG R7F4DC-DC16B-H User manual

MG

MG R7F4DC-DC16B-H User manual

MG M2BS2 User manual

MG

MG M2BS2 User manual

MG 10YS User manual

MG

MG 10YS User manual

MG DLC E2 Series User manual

MG

MG DLC E2 Series User manual

MG R5-SV1A User manual

MG

MG R5-SV1A User manual

MG R30BS User manual

MG

MG R30BS User manual

MG Devicenet R7F4DD-DA16B-H User manual

MG

MG Devicenet R7F4DD-DA16B-H User manual

MG R3-DA16 User manual

MG

MG R3-DA16 User manual

MG R7HL-YS4L User manual

MG

MG R7HL-YS4L User manual

MG Mini-M M2LMS User manual

MG

MG Mini-M M2LMS User manual

MG DLC-C1 Series User manual

MG

MG DLC-C1 Series User manual

MG R7K4FML3-6-DAC32B User manual

MG

MG R7K4FML3-6-DAC32B User manual

MG R6D-SV2 User manual

MG

MG R6D-SV2 User manual

MG R7F4HEIP-DA16A User manual

MG

MG R7F4HEIP-DA16A User manual

MG R8-FS16N User manual

MG

MG R8-FS16N User manual

MG 10FNS User manual

MG

MG 10FNS User manual

MG R9WTU-ED User manual

MG

MG R9WTU-ED User manual

MG R5-DS1A User manual

MG

MG R5-DS1A User manual

MG DLS-M1 User manual

MG

MG DLS-M1 User manual

MG R3Y-MS8 User manual

MG

MG R3Y-MS8 User manual

MG R30XN16A User manual

MG

MG R30XN16A User manual

MG 61C User manual

MG

MG 61C User manual

MG Devicenet R7F4HD-DC32B User manual

MG

MG Devicenet R7F4HD-DC32B User manual

Popular I/O System manuals by other brands

Allnet ALLDAQ ADQ-10-cPCI manual

Allnet

Allnet ALLDAQ ADQ-10-cPCI manual

Bosch B208 installation guide

Bosch

Bosch B208 installation guide

ICP DAS USA CAN-2054C user manual

ICP DAS USA

ICP DAS USA CAN-2054C user manual

Frontier RUT-G 2005 manual

Frontier

Frontier RUT-G 2005 manual

Meilhaus Electronic ME-5004 manual

Meilhaus Electronic

Meilhaus Electronic ME-5004 manual

National Instruments NI 9236 Getting started guide

National Instruments

National Instruments NI 9236 Getting started guide

turck TBIP-L-FDIO1-2IOL Series Safety manual

turck

turck TBIP-L-FDIO1-2IOL Series Safety manual

Caen V977 Technical information manual

Caen

Caen V977 Technical information manual

OneFex CE-IO Series manual

OneFex

OneFex CE-IO Series manual

National Instruments NI REM-11100 Getting started guide

National Instruments

National Instruments NI REM-11100 Getting started guide

Galletti EVO quick start guide

Galletti

Galletti EVO quick start guide

Pellas X CAN I/O MC-1 manual

Pellas X

Pellas X CAN I/O MC-1 manual

Siemens SIMATIC ET 200SP manual

Siemens

Siemens SIMATIC ET 200SP manual

M-system R3-PC16A instruction manual

M-system

M-system R3-PC16A instruction manual

Advantech AMAX-5000 Series user manual

Advantech

Advantech AMAX-5000 Series user manual

Smarteh LPC-2.DO4 user manual

Smarteh

Smarteh LPC-2.DO4 user manual

Ziton ZR451-3 installation guide

Ziton

Ziton ZR451-3 installation guide

ABB SAM600 Series Operation manual

ABB

ABB SAM600 Series Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.