MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
5. HARDWARE SPECIFICATIONS
5.1 61C-x1 (No. of channels codes 04, 08, or 16 in x)
ITEM SPECIFICATIONS
Analog input 1 – 5 V DC (input resistance ≥ 1 MΩ)
Protocol CC-Link, Ver.1.10
Digital output 16-bit signed binary (14 bits for data)
I/O characteristics 0 – 10000 proportional to analog input 0 – 100%
Maximum resolution 1 mV for 1 – 5 V DC range
Accuracy ±0.1%
No. of analog input channels 61C-041 4
61C-081 8
61C-161 16
Isolation Input to CC-Link to power
Required nodes 61C-041 1 (RX/RY 32 points each, RWr/RWw each 4 points)
61C-081 2 (RX/RY 32 points each, RWr/RWw each 8 points)
61C-161 4 (RX/RY 32 points each, RWr/RWw each 16 points)
Connection CC-Link
Euro type connector terminal (applicable wire size: 0.2 – 2.5 mm
2
, stripped length 7 mm)
Input Via the Installation Base (model: MxBS2)
Power input
Via the Installation Base (model: MxBS2)
Noise immunity 500 V p-p, 1µsec.
Dielectric strength 1500 V AC @ 1 minute (input to CC-Link to power )
Insulation resistance ≥ 100 MΩ with 500 V DC (input to CC-Link to power )
Weight 250 g (0.55 lb)
Power input 61C-x1-K 85 – 132 V AC, 47 – 66 Hz
61C-x1-R 24 V DC ±10%
Power consumption 61C-x1-K approx. 4 VA
Current consumption 61D-x1-R approx. 160 mA
5.2 61C-x2 (No. of channels codes 04, 08, or 16 in x)
ITEM SPECIFICATIONS
Analog output 1 – 5 V DC (load resistance ≥ 20 kΩ)
Protocol CC-Link, Ver.1.10
Digital input 16-bit signed binary (14 bits for data)
I/O characteristics 0 – 10000 proportional to analog output 0 – 100%
Maximum resolution 1 mV for 1 – 5 V DC range
Accuracy ±0.1% excluding the accuracy of I/O modules
No. of analog output channels 61C-042 4
61C-082 8
61C-162 16
Isolation Output to CC-Link to power
Required nodes 61C-042 1 (RX/RY 32 points each, RWr/RWw each 4 points)
61C-082 2 (RX/RY 32 points each, RWr/RWw each 8 points)
61C-162 4 (RX/RY 32 points each, RWr/RWw each 16 points)
Connection CC-Link
Euro type connector terminal (applicable wire size: 0.2 – 2.5 mm
2
, stripped length 7 mm)
Output Via the Installation Base (model: MxBS2)
Power input
Via the Installation Base (model: MxBS2)
Noise immunity 500 V p-p, 1 µsec.
Dielectric strength 1500 V AC @ 1 minute (output to CC-Link to power)
Insulation resistance ≥ 100 MΩ with 500 V DC (output to CC-Link to power)
Weight 250 g (0.55 lb)
Power input 61C-x2-K 85 – 132 V AC, 47 – 66 Hz
61C-x2-R 24 V DC ±10%
Power consumption 61C-x2-K approx. 4 VA
Current consumption 61C-x2-R approx. 160 mA
61C
EM-6627 Rev.9 P. 4 / 12