The MM1005 DC input alarm monitors
a 4/20mA DC input signal and trips a
dpdt relay when the input exceeds the
setpoint. Specifically designed for use
with two-wire and other 24 VDC
powered transmitters, the MM1005
contains an integral 24 VDC transmitter
power supply.
The MM1005 can be supplied as a HI
or LO alarm. The output relay is normally
energized, and de-energizes for an
alarm condition. This provides alarm
indication upon loss of power to the
alarm. A set of red/green LEDs
indicates alarm status.
A 25 turn deadband adjustment, allows
deadband settings between 0.5% and
100% of span. The deadband is
symmetrical about the setpoint.
OPTIONS
The following options are available on the
MM1005. Options installed are listed on
thelabelattachedtothesideofthemodule.
H/L
H= High alarm.
Alarm occurs on an increasing
signal.
L = Low alarm.
Alarm occurs on a decreasing
signal.
RThe Normal condition for the
relay is energized. It de-
energizes for an alarm condition
(Failsafe). Option R (Reverse
Sense) reverses this logic.
UAll circuit boards conformal
coated for protection against
moisture.
MM1005
4-20mASINGLEALARM
WITH 24VDC POWER
SUPPLY FOR TWO-WIRE
TRANSMITTER
SPECIFICATIONS
INPUT RANGE
4/20 mA
INPUT RESISTANCE
61.9 ohms
TRANSMITTER POWER SUPPLY
24 VDC regulated, 30 mA max
DEADBAND
0.5% to 100% of span
SETPOINT
0 to 100% of span
RESPONSE TIME
20 ms typical
OPERATING TEMPERATURE
14°F to 140°F/-10°C to 60°C
RELAY CONTACTS
(dpdt)
Resistive Load:
5 A max, 150 W max,
220 VAC max, 30 VDC max
Inductive Load
(Power Factor ³0.4):
2.5 A max, 75 W max,
220 VAC max, 30 VDC max
POWER OPTIONS
115 VAC ±10%, 50/60 Hz
230 VAC ±10%, 50/60 Hz
(2.5 W max)
CONTROLS
The MM1005 alarm module contains two
adjustments: setpoint and deadband. No
other calibrations are needed.
CALIBRATION
Connect a 4/20 mA calibration signal to
the module input and set it for the
desired trip point. Turn the DEADBAND
control fully ccw. Adjust the SETPOINT
untilthe alarm trips (LEDturnsfromgreen
to red).
Adjust the DEADBAND control for the
desired amount of deadband. Vary the
input signal up and down to check the
levels at which the relay trips and rests.
The setpoint will remain centered in the
middle of the deadband.
RELAYCONTACTPROTECTION
When inductive loads such as motors,
relays or transformers are switched,
voltage transients may be generated
which exceed the ratings of the relay
contacts. The resulting arcing can
quickly destroy the contacts. (Refer to
theSPECIFICATIONS below for therelay
contact ratings.)
Surge suppression is required across
inductive loads to guard against
premature relay failure. Figure 1
illustrates diode surge suppression for
a DC load. The diode's operating (peak
inverse) voltage should exceed the
load's supply voltage by at least 50%
and should have a current fating of at
least one ampere.
Figure 2 shows surge suppression for
an AC load, using an MOV (Metal Oxide
Varistor) and a capacitor. The
breakdown voltage ratings of both the
MOV and the capacitor must exceed the
peak AC voltage.
With normal sine-wave power, PEAK =
1.414 x RMS voltage. For 115 VAC
power a 200 volt peak rating is
recommended.
1 2
Specifications are subject to change without notice. © 2008 Wilkerson Instrument Co., Inc. DWG#W100920B 3/15
WARRANTY
The Mighty Module Series of products
carry a limited warranty of 10 + 5 years.
In the event of a failure due to defective
material or workmanship, during the 10
year period, the unit will be repaired or
replaced at no charge. For a period of 5
years after the initial 10 year warranty,
the unit will be repaired, if possible, for
a cost of 10% of the original purchase
price.
Relays are not covered by the warranty.
MOUNTING
The module is designed to plug into a
standard 11-pin relay socket. Part
numberMP011 is a moldedplasticsocket
suitable for mounting on a flat surface
or in a 2¾" wide PVC snap track
(TRK48). Use CLP-1 hold-down clip if
needed. A Killark HK Series explosion-
proof housing with dome and 11-pin
socket is available (HKB-HK2D-11).
ADINrailmountedsocket(P/NDMP011)is
available for 35mm symmetrical rail.
CASE DIMENSIONS INCHES [mm]
3 4

Popular Power Supply manuals by other brands

TriTerra Kaihon1000 user manual

TriTerra

TriTerra Kaihon1000 user manual

GW Instek PEL-300 manual

GW Instek

GW Instek PEL-300 manual

Raychem C-150-E manual

Raychem

Raychem C-150-E manual

Pulsar BLACK POWER PSBEN 5012D/LCD manual

Pulsar

Pulsar BLACK POWER PSBEN 5012D/LCD manual

Rockwell Automation 1606-XLEDNET3 instruction manual

Rockwell Automation

Rockwell Automation 1606-XLEDNET3 instruction manual

PR electronics 2220 manual

PR electronics

PR electronics 2220 manual

Altronix WayPoint307A installation guide

Altronix

Altronix WayPoint307A installation guide

Gallagher 083114 quick start guide

Gallagher

Gallagher 083114 quick start guide

Nemtek MERLIN 4 Installer manual

Nemtek

Nemtek MERLIN 4 Installer manual

Antec TRUEPOWER NEW TP-550 user manual

Antec

Antec TRUEPOWER NEW TP-550 user manual

Altimium PWSU12 user manual

Altimium

Altimium PWSU12 user manual

Pulsar HPSB 7012D manual

Pulsar

Pulsar HPSB 7012D manual

Alpha DOCSIS DM31 quick start guide

Alpha

Alpha DOCSIS DM31 quick start guide

Eaton Powerware Prestige Series 1500 VA Installation and operator's manual

Eaton

Eaton Powerware Prestige Series 1500 VA Installation and operator's manual

Camtec CPS-EC480 manual

Camtec

Camtec CPS-EC480 manual

VOLTCRAFT SPS-1000I operating instructions

VOLTCRAFT

VOLTCRAFT SPS-1000I operating instructions

Pulsar HPSB 11A12E manual

Pulsar

Pulsar HPSB 11A12E manual

Gooloo GTX300 user manual

Gooloo

Gooloo GTX300 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.