Minco 830 User manual

MINCO 830/840
Intelligent Controller Manual
GuiLin Minco Electronic Co., Ltd.
GuiLin Glminco Intelligent Control S&T Co., Ltd.
Add: Building B-216, Venture Park of Returned Scholars,
Guilin High-Tech Zone, Guangxi, China
Tel: +86-773-5812281 5828281
Fax: +86-773-5828281
E-mail: [email protected] [email protected]
Http: //www.glminco.com www.glminco.cn

- 2 -
Contents
I、Summarization..............................................................................1
II、Characteristics .............................................................................1
III、Fixup dimension drawing ..........................................................1
IV、Function definition and operate instruction ............................2
4.1.Operate panel function instruction.....................................2
(1).System menu operation button. ..........................................2
(2).LCD display ............................................................................2
(3).Operation keys.......................................................................3
(4).State indicator light ................................................................3
4.2.Connection port definition ...................................................4
V、Parameter setting........................................................................5
5.1.Parameter setting instruction .............................................6
5.2.System parameter description .........................................10
5.3.Delay Time Instruction.......................................................12
5.4.Timing Start Instruction......................................................14
VI、Normal failure and handling method.....................................14
VII Outside wiring diagram.............................................................16
VIII、Front and back panel diagram.............................................17

- 1 -
I、Summarization
Minco 830/840 generator set intelligent controller adopts high performance
microprocessor and industry components. It has measuring, controlling, protection,
four remote control, flexible software setting functions and high anti-jamming ability.
The controller display all the measuring parameters, control parameters and
genset running state. Actually meets different types of generator auto control
requirements.
II、Characteristics
1. Minco830 apply for single generator automatic control system;
2. Based on 830, Minco840 adds mains monitoring, apply for double power
automatic control system;.
3. Double processing chip, virtual measurement of voltage and current,
multifunction, smart action;
4. Wide-screen LCD display with back-light;
5. Chinese and English double language menu, mutual operation, All the setting
and operation can be completed without computer;
6. Auto start, auto protection, auto supply control;
7. Prefect auto protection, display warning message and work state, failure
record more than 50 items;
8. Plenty of connected parameters (coolant temp, double oil pressure, oil temp.
oil level etc.);
9. All relay contact capability is above 10A/250VAC/30VDC;
10. User-defined input/output, timer start & stop generator;
11. RS232 communication, attached “four remote control” monitor software;
III、Fixup dimension drawing
Operate panel W 213 X H 153mm
Install hole W 199 X H 139mm
Deepth D 52mm

- 2 -
IV、Function definition and operate instruction
4.1.Operate panel function instruction
Operate panel is composed of 128*64 LCD display,running operation button,
indicator light and system menu operation button.
(1).System menu operation button.
Content Function
Parameter setting/enter to next menu/ confirm to revise
Exit / Back to the superior menu
Switch the display content, view all the measuring parameters of the
generator set and the current state; Page up the menu/add value.
Switch the display content, examine all the generator set measuring
parameter and current state, menu page down/degree value.
(2).LCD display
Genset runs is normal (Not setting state or nor fault state)
Operation Description
Main screen 1
or switch the display
interface(This page is just for 840)
Normal 00.0HZ
L-N: 000 000 000V
Main screen 2
or switch the display
interface
F: 00.0HZ PF:0.00
L-N: 000 000 000V
00.0 00.0 00.0 A
Power 0000.0 KW
Main screen 3
or switch the display
interface
Speed: 0000 RPM
(Success start genset time)Starts: 0005
Hours: 00000.05
(Electrical qty) ENERGY: 00000.0
Main screen 4
or switch the display
interface
TEMP 1: --- ℃
TEMP 2: --- ℃
OIL P1--- MPa
OIL P2 ---- MPa
Main screen 5
or switch the display
interface
BATTERY: 27.7 V
CHARGER: 00.0 V
FUEL_L: --- %
Main screen 6
or switch the display
interface
Stop/OFF status
08-06-03/09:12:15

- 3 -
Note:
1. When “display change mode” set in “auto” switch state, the LCD display screen
will switch to next page for each 10 seconds; when “background light control” set
in “auto” state, the LCD screen background light will be auto turn off without any
operate after three minutes. Once the fault appear or press any button, the
background light turns on. When “Background light” control setting as “constant
light”, the LCD background light will keep lighting.
2. Without Coolant temp. Oil pressure, or Fuel level sensor connection,、the
controller display “―――”,which does not affect controller normal work.
(3).Operation keys
Content Function
Press the button, controller in “start” state, the green LED keep
bright .This is start by manual, the generator will keep running.
(Auto)
Press the button, controller in “Auto” state, the yellow LED keep
bright. ①When the “Remote start” switch is turned off and mains
resume, the generator set will be stopped after cool down delay.
②When “Remote start” switch is turned on or mains failure, the
generator set will be delay started. ③If timing start generator is
valid, generator is be timing started. After the end of the timed
start, will delay shutdown.
Press the button, the above red LED keep bright, the controller is
in “stop/reset” state, it will unload, decelerate and idle stop, the
fuel will be cut off after idle delay. When During decelerate and
idle the “reset” indicator keep flash, keep light when generator
stop. If quickly press the button twice, generator will be cut off fuel
and stop immediately, without decelerate, idle process.
Press the button, yellow indicator keep bright. Controller in “TEST”
state. Start the generator by hand directly, when generator runs
in normal, the controller make generator onload automatically
and keeps onload running.(whether “remote start” switch turn
on/off
(4).State indicator light
Content Function
Indicate the generator set failure, protected stop, Display the fault
content.
Indicate the generator set warning information, Display alarm
detail

- 4 -
Indicate “remote start” port state, used for mains state monitoring
4.2.Connection port definition
PortNo. Function
Power supply(8~36VDC, normal work current<300mA)
1 “+” battery anode input
2 “-” battery cathode input
Analog input(input voltage range 0~5.0VDC)
5 Fuel level sensor
6 Oil pressure sensor 1
7 Temp. sensor 1
8 Oil pressure sensor 2
9 Temp. sensor 2
Mains three phase voltage input (0-300VAC ,insulation inside) This
function is just for 840
10 Mains voltage phase R
11 Mains voltage phase S
12 Mains voltage phase T
13 Mains zero line N
Three phase load current input(0-5A AC, without inside isolation, current
transformer must be added
14、15 A phase load current
16、17 B phase load current
18、19 C phase load current
Genset three phase voltage input(0-300V AC, without inside isolation,
current transformer must be added)
20 U phase genset voltage
21 V phase genset voltage
22 W phase genset voltage
23 N (Genset N wire)
Switch output port(relay insulated, connector capacity
10A/250VAC /30VDC)
24、25 Generator set supply(load)
26、27 Mains supply (This function is just for 840)
3 User-defined output1(inversed diode inside)
4 User-defined output2(inversed diode inside)
28 User-defined output 4 NO

- 5 -
29 Comm.
30 NC.
31 NO.
32 Comm.
33
User-defined output 3
NC.
34 Excitation/Charge failure input(charge generator input port D+,
forbid connect to GND)
35 Fuel(inversed diode inside)
36 Comm.(Fuel & start contacts comm.)
37 Start(inversed diode inside)
Switch input port(add photoelectricity isolator, valid when connect to
GND)
38 User-defined input 4
39 User-defined input 3
40 User-defined input 2
41 User-defined input 1
42 Remote reset
43 Remote start
46
47 Speed signal input
V、Parameter setting
All the parameters can be read and written by communication protocol. Except
coolant temp.
oil pressure / fuel level sensor curve data adjust, all the parameters can be setting
by controller.
Press
button
Enter to parameter set interface
Alarm limit set; Timer start set; Input port state set;
Output port state set , Measure regulate set, Coolant temp set
Failure record set; Delay time set; Oil pressure set
Data and time set, System parameter set, Fuel level data set;
Press
button
Select examine/setting parameter content
(reversed display when selected)
Press
button Enter to the selected menu
Press
button
Exit the parameter setting state
Note: Without any operation over three minutes, it will auto exit the

- 6 -
parameter setting state, to avoid illegimate operation
5.1.Parameter setting instruction
Switch
input
status
Real time display controller input port state
Remote start: 0 Remote reset: 0 Emergency stop: 1
AUX input 1: 0 AUX input 2: 0 AUZ input 3: 0 AUX input 4: 0
Note: Press any menu key will be exit
Relay
output
status
Real time display controller output port state
Start: 0 Fuel: 0 Load: 0 Mains:0(It is for 840)
AUX out 1: 0 AUX out 2: 0AUX out 3: 0 AUX out 4: 0
Note: Press any menu key will be exit
Failure
record
Failure record
01/04 (Fault serial No./Fault amount)
Emergency stop!! (fault reason)
08-06-03/11:26:38 (fault time)
Note: press or button,display up or down failure;
press or button, will be exit
Date and
time set
Press or to change the reverse display data ;
press reverse display move to the left; Press , back to
the superior menu ,date and time will not changed.
Press reverse display move to the right,move to the last
position press ,back to superior menu, date and time have
been changed
Alarm limit
set
High voltage:0250 High frequency :0530 High power :0500
Low fuel level:0020 Low voltage :0200 Low frequency:0470
High cooltant temp.:0050 Low battery voltage :0105
High over current:0400 High over speed:0550
High fuel level:0080 Low charge:0080
Low oil pressure: 0020
Press or choose content and the content reversed
display ,Press back to superior menu ;Press enter
choosing parameter setting state, the selected parameter is
underline, enter the parameter setting state, press
or change the reversed display data;Press move to
the end of left; Press back to the superior menu, press

- 7 -
reversed display move to the end of right, press back
to the superior menu, parameter changed and saved.
Note: Unit of frequency:0.01Hz, unit of battery, charging
voltage:0.01V, unit of oil pressure:0.01MPa, The rest without a
decimal point, unit is 1
Measure
regulate
Password: 8421(Default password)
Genset A phase: 0000 Battery voltage: 0120
Genset B phase: 0000 Charge voltage: 0120
Genset C phase: 0000 Fuel regulate: 0050
Current A phase: 0000
Current B phase: 0000 Oil pressure 1 : 0020
Current C phase: 0000 Oil pressure 2 : 0020
Mains phase A Coolant temp.1: 0090
Mains phase B Coolant temp.2: 0090
Mains phase C
Note: The measure regulate of mains three phase is just for
840. Coolant temp. ,oil pressure and oil temp./fuel level
adjusting value are relevant to the error of real measuring.
Password authentication input method
Press or change data ;Press move to the left, move
to first digit press back to superior menu; press move to
the right,move to last digit, then press ,enter next menu.
As per the error value of controller measuring data and the real
data to decide whether you need to data adjust. The controller
already adjusted before leave factory. But it may be some warp
in the use environment, if the warp is in the error range, we
suggest not to adjust the data again.
Press or choose content reversed display ;
Press back to superior menu;Press ,enter to choose
data adjustment state, and the adjustment parameter underline.
The data can be change.(Adjust range:-10——+10)
Enter data adjusting state ,press or change data ;
press back to superior menu, data adjustment in valid,
Press data adjustment achieved, parameter change saved.
Note: Minco830/840 provides calibration for three phase

- 8 -
voltage, three phase current, and battery charge voltage. The
measurement of controller will increase(reduce) according the
increased(decreased) value of adjustment. The scope of
adjustment is ±10%.
But the calibration of coolant temp., oil pressure and fuel level
are different. Special explain, for coolant temp., oil pressure,
fuel level sensors maybe positive modulus (It means the sensor
output add along with input add), It maybe negative modulus(It
means the sensor output minish along with input add). Add or
minish adjust value lead to adjust result which is decided by the
real situation.
Note: The unit of current, battery voltage and charge voltage is
0.1.(e.g. actual value=displayed value *0.1), The unit of oil
pressure is 0.01 Mpa
Delay time
set
Password: 8421 (Default)
Cool down :020 Idle stop:015 Transform:005
Genset start:005 Acc time:020 Over load:003
Cycle crank space:015 Crank time:008 Over voltage:003
Bypass time:020 Over frequency:003 Warm up:010
ETS fuel:000 Pre-fuel:005 Lose speed:030
Idle start :010 Close time :000 Low speed:020
AUX input 1:003 AUX input 2:005 AUX input 3:002
AUX input 4:005
Press or choose content reversed display;
press back to superior menu;press enter to choose
parameter setting state,the adjusting parameter is underline.
Enter setting state,press or change data,
Press cursor turn left,move to the first digit Press back
to superior menu,data will not be changed.;press cursor
turn right,move to last digit, press back to superior menu,
Changed parameter be saved.
Note: Delay time up limit can’t be over 255 seconds, if setting
over 255s , system will change to 255s automatically.。
System
parameter
set
Input password: 8421 (default)
Trip speed:0400 Output set 3 :002 Display mode:0
CT: 0500 Output set 4:004 Language C/E:0

- 9 -
Password:8421 LCD mode:0 Address:120
Speed source:0 Gear tooth No:135
Start method: 0 Voltage measure method:0
Input set 1:002 Input set 2:001 Input set 3:006
Input set 4 :008 Output set 1:000 Output set 2:006
Press or choose content reversed display ;
Press back to superior menu;Press enter setting state,
the adjusting parameter is underline. Press or change
data;press data will not be saved,press the data can
be saved ,then back to superior menu.
Timing
start set
Date:Month-day/week
T_1 :Begin time:Minute-end time:minute
T_2 :Begin time:Minute-end time:minute
T_3:Begin time:Minute-end time:minute
Press or change the data of reversed display ;
press to turn left, when the reversed display move to first
digit, press back to superior menu, the date and time will
not be changed;Press to turn right,when the reversed
display move the end of right, press back to superior menu,
the date and time setting will be saved
Coolant
temp. set 1-0.66V/120 2℃-1.04V/100 3℃-1.27V/90 4℃-1.62V/80℃
5-1.94V/70 6℃-2.36V/60 7℃-3.00V/40 8℃-4.06V/10℃
Oil
pressure
set
1-0.31V/0.00MP 2-1.29V/0.20MP
3-1.85V/0.40MP 4-2.07V/0.50MP
5-2.26V/0.60MP 6-2.41V/0.70MP
7-2.54V/0.80MP 8-2.75V/1.00MP
Fuel level
set 1-0.08V/00% 2-0.33V/13 % 3-0.68V/27% 4-0.93V/40%
5-1.10V/53% 6-1.25V/67% 7-1.41V/80% 8-1.56V/100%

- 10 -
5.2.System parameter description
Trip
frequency
When start the genset, if examine the genset rotate speed >trip
speed, it considers the genset start successful and stop the
crank output (trip speed generally setting to 1/3 of genset
normal working rotate speed )
CT ration CT rate setting correspond ratio is 5, for example the current
rate setting in 500, it’s correspond with 500:5
Passport Leave factory password 8421,please change the password on
your own
Address Only use for multi equipment network, to differentiate the
equipment 。
Gear tooth
number
The definition of this parameter is related with “speed source
option”. when “speed source option” is 0, the speed can be
obtained by measuring frequency, this parameter is the ratio of
speed to frequency, when “speed source” is 1,this parameter is
the flywheel teeth of engine.
Output 1
Output 2
Output 3
Output 4
AUX output definition:0-Shutdown;1-Auxiliary shutdown;
2-Clutch(LOAD);3-Automation;4-Idle (close);
5-Idle (open);6-Pre-fuel;7-Warm up;8-Acceleration;
9-Deceleration;10-Over speed;11-Over load,
12-High speed,13-Battery low,14-Pumping,15-Alarm
Input 1
Input 2
Input 3
Input 4
AUX input definition :0-Monitor,1-Low oil pressure;
2-High coolant temp.;3-Acceleration limit;
4-Deceleration limit;5-High oil temp;
6-Low fuel level(alarm but non-stop),7-High fuel level,
8-Float charge failure ,9-Alarm ,10 -Alarm non-stop
(running period),11-Alarm stop. 12-Monitor,
Definition 16-31 are same as function of definition 0-15, 0-15
are effective when they are closed, 16-31 are effective when
they are cut-off.
Crank
mode
0:Detect low oil press when crank
1:Not detect low oil press when crank
Display
mode 0:Switchinmanual 1:Auto switch
Language
Selection 0:Chinese 1:English
LCD mode 0:Autoshutdown 1:Constant light

- 11 -
Speed
source 0 : From Genset power supply frequency
1 : From Speed sensor
Measure
voltage
Method
0:Measure phase voltage
1: measure line voltage
Generator
type AUX
Auxiliary Output Definition Instruction
Shutdown:Any of failure for engine protection stop can bring public failure output;
Auxiliary Shutdown:Output is energized when genset stops. Output will be
de-energized when ETS delay is finished;
Genset supply: Output will be energized when remote start switch closed after
normal running;
Automation:Auto relay will have an output when the controller is in auto state;
Idle (close) /Idle (open):Output will be energized during the period of idle start
and idle stop,but the state of which are opposite;
Pre-fuel: Output will be energized during the period of pre fuel;
Warm-up: Output will be energized before pre-fuel and generator start;
Acceleration/Deceleration: Output will be energized during the period of
acceleration delay and deceleration delay ,which
coordinate to finish the mechanical speed governing;
Over Speed:Output will be energized when the genset is over speed;
Over load: Output will be energized when genset is over load.
High speed:Output will be energized when genset is running with rated speed.
Low Battery: Output will be energized when battery voltage is low.
Pumping: Output will be energized when low fuel level is detected to alarm,
output will be vanished when high fuel level is detected, fuel can be
resupplied automatically;
Alarm:Output will be energized when genset alarm
Auxiliary Input Definition Instruction:
Monitor:Not control,only monitor the state,needless input ports can be set up to
monitor;
Low Oil Pressure:Genset will shutdown when low oil pressure is detected;
High Coolant Temperature: Genset will shutdown when the high coolant
temperature is detected;
Acceleration Limit/Deceleration Limit: Coordinate with output of acceleration
and deceleration to finish mechanical speed governing
High Oil Temperature: Genset will be protected & stopped when high oil
temperature is detected;
Low Fuel Level: Alarm when low fuel level is detected, but genset will not stop;
High Fuel Level: Realize pumping function with low fuel level together;
Float charge Failure Alarm:Float charge failure alarms during the running time
(this port is closed), but genset will not shutdown.

- 12 -
Alarm:User-defined alarm,instruct to auxiliary input 1-4 alarm;
Alarm Non-stop:User-defined alarm,but only during the period of genset
working,instruct to auxiliary input 1-4 alarm;
Alarm Stop:User-defined alarm, cause to shutdown when genset is running,
instruct to auxiliary input 1-4 stop
Attention:Display, alarm and protection of coolant temp., oil pressure and fuel
level can be realized by measuring the analog volume,and also can be realized by
defining the high coolant temp., low oil pressure, fuel level to the auxiliary input
portion. If the analog volume and alarm input are exist together in the system, then
any of alarm can come into being protection and alarm. If the switch alarm
protection is no need, please define the auxiliary input to another function; if the
analog volume alarm protection is no need, please set the alarm up-low limit to the
measurement limit so as to not alarm.
Fuel temp. & oil pressure sensor just for display, not for control
Output of acceleration and deceleration are in coordination with limit of
acceleration and deceleration to realize mechanical speed adjustment. Normal
speed adjustment function can be realized by definite output of acceleration and
deceleration but not detect properly and not alarm.
Since output and input can be user-defined, Minco 830/840 controller’s input and
output function actualized is much more than the real amount of input and output.
Although some function of controller has been appointed, which can’t execute if
there is no definition for input and output port.
5.3.Delay Time Instruction
Delay of
“cool stop
(down)”
When the controller is in “Auto” state, once the “Remote start”
switch input turn off and mains resumed the genset will be
stopped after delay.
Delay of
“genset
start”
When the controller is in “Auto” state, once the “Remote start”
switch input turn on or mains failure , the genset will be started
after delay.
Delay of
“Crank
INTerval”
When the cranking time delay finish, if the start succeed
condition is not satisfied and not reach the crank times limit, the
delay will be repeated and crank times added 1.
Delay of
“cranking
time”
When the genset start and begin to delay, if the start succeed
condition is satisfied (genset rotate speed>trip speed) it’s
consider to be genset start successful and stop delaying.
Delay of
“bypass
time”
After the gen-set start successfully, that begin to start the
delay of bypass. "low oil pressure", "high coolant temperature "
etc will not be monitored during the delay to avoid mistake
alarm when genset in initially starting.
Delay of
“energize
to stop”
Output of auxiliary stop relay is energized when engine
stop.”Ergize to stop” delay begin, output of auxiliary stop relay is
de-energized when delay finish.

- 13 -
Delay of
“pre-fuel”
Delay of pre-fuel has begun before engine starts and relay of
pre-fuel close at the same time., Relay of pre-fuel cutoff after
delay finish, and engine start to crank.
Delay of
“idle start” Delay of idle start begin after the engine starts successfully, and
the relay of “idle start” begin to work at same time.
Delay of
“idle stop” When genset stops, delay of “idle stop” begin after deceleration
finish, and idle relay begins to work.
Delay of
“ACC”
Genset start successful and idle (start) finish. Acc relay closed
when Acc delay begins.”Acc failure” will alarm when the delay
finish but not get the signal of Acc in a right position.
Delay of
“Auxiliary
Input 1”
Delay begins at the time of auxiliary input 1 closes, delay will
break off when the state returns to be normal. When the input
still closes after delay finishes, it will alarm.
Delay of
“Auxiliary
Input 2”
Delay begins at the time of auxiliary input 2 closes, delay will
break off when the state returns to be normal. When the input
still closes after delay finishes. it will alarm.
Delay of
“Auxiliary
Input 3”
Delay begins at the time of auxiliary input 3 closes, delay will
break off when the state returns to be normal. When the input
still closes after delay finishes, it will alarm.
Delay of
“Auxiliary
Input 4”
Delay begins at the time of auxiliary input 4 closes, delay will
break off when the state returns to be normal. When the input
still closes after delay finishes, it will alarm.
Delay of
“Loss
Speed”
Delay begins when no speed signal is detected during the
running. If the speed signal isn’t be detected until delay finish,
then it will alarm.
Delay of
“Supply(clo
se) time”
The time of the closing relay output is set to 0, the relay
continuous has output.
Delay of
“Retransfor
mation”
When “remote start” switch turn off and starts to delay, the
controller is in a “auto” state, and it gets ready to stop after
delay finishes.
Delay of
“over load”
Delay begins when current is exceed the alarm upper limit. If
the current is in normal, delay will break off. When it’s still over
current after delaying, it will be overload to stop. When the
current exceeds stop upper limit, then protect to stop without
any delay.
Delay of
“over
voltage”
Delay begins when voltage exceeds the upper limit. When
voltage returns to normal during the period of delay, delay will
be interrupted. If the phenomena of overvoltage still exists after
delay finishes,then it will be in an overvoltage protection to stop

- 14 -
Delay of
“over
frequency”
Delay begins when the frequency exceed the upper limit. When
voltage returns to normal during the period of delay, delay will
be interrupted. If the phenomena of over frequency still exists
after delay finishes, then it will be in an over frequency
protection to stop. If the frequency is above the upper limit, then
it will stop to be protected without any delay.
Delay of
“Warm Up”
It provides a delay between starts and loads successfully. It can
prolong the time of transferring to supply. It also can help the
genset to run to supply in the best condition and avoid friction
loss of genset to the minimum when it’s in not an emergency
situation.
Delay of
“Decelerati
on”
Delay begins at when genset stops, and deceleration relay will
close. The controller will alarm for “deceleration failure” when
the right deceleration signal can not be detected after delay
finishes.
5.4.Timing Start Instruction
Timing start is only valid on the automatic state of Minco830/840.
Auto start estimate the now date( month-day/week) to be correct or not, if it’s
correct, then start the machine to work or stop the machine to halt at the setting
time(hour: minute).All the parameters are set to 0, then it means time start function
is not available.
Any one of month/day/week is set to 0,it means that the setting corresponds with
current time. When month/day/week are all set to 0, it means timing start daily.
When day and month are set to 0,it means timing start weekly. When month and
week are set to 0,it means timing start monthly.
For example:
The date of timing start is set to:08-00/01 Time: 10:00-12:20. It means that the
genset will starts at 10:00,and stops at 12:20 in every Monday of every week in
August.
The date of timing start is set to:00-03/00 Time: 10:00-12:20. It means that the
genseet will starts at 10:00,and stops at 12:20 in the 3rd of every month.
Three times interval can be set on every day, please set “0” to no-use time
interval.
VI、Normal failure and handling method
Failure Description Solution
Manual start
failure
Press the key,
the green light isn’t
bright on the above
and the motor
doesn’t work.
Check whether the green light is
broken, if the LED light isn’t broken,
please contact with the factory; If the
LED light is broken, please see below
solution.

- 15 -
Press the key,
the green light is
bright on the above
and the motor
doesn’t work.
Check the menu of “low oil pressure” in
the “input port state”, if display
“0”,please check whether the oil
pressure sensor is ok; if display “1”,the
oil pressure sensor is ok, now please
press ,measuring the module port
37 “start” whether there’s 24V with a
multimeter, if the voltage is 24V,check
whether the outside middle relay, start
motor is broken, and whether the
battery voltage is enough; If port 37 no
output, the module might be damaged.
Module in
(Auto)state,
inspection “remote
start” have input, the
“remote start” state
light isn’t bright and
the motor doesn’t
work.
Check the menu of “remote start” in the
“input state”, if the “remote start” display
“0” means that the outside timer etc
module relay is broken cause didn’t
receive the input signal; If display “1”,
the module might be broken.
Auto start
failure
Module in
(Auto) state,
inspection “remote
start” have input, the
“remote start” state
light is bright on and
the motor doesn’t
work.
Check the oil pressure sensor; Switch
to the manual start, check whether
there’re output signal of the port 37-
“remote start”, the outside components
and the battery voltage.
Wheel tooth
is fighting
when start
Start successful and
motor keep running,
the wheel tooth is
fighting.
Lower down the trip speed;
Suggest used speed sensor to get the
rotate speed.
On load
current
display
incorrect.
Current ratio setting
incorrect. Reset the current ratio.

- 16 -
VII Outside wiring diagram
(Mains connection will be removed on 830)
44
40
38
43
41
45
35
34
33
32
31
25
20
24
9
8
7
18
22
21
19
16
36
37
2
1
46
3
13
47
15
30
42
39
14
17
6
5
4
10
11
12
23
26
29
28
27
MINCO830/840
44
40
38
43
41
45
35
34
33
32
31
25
20
24
9
8
7
18
22
21
19
16
36
37
2
1
46
3
13
47
15
30
42
39
14
17
6
5
4
10
11
12
23
26
29
28
27
SPEED SENSOR
BATTERY
8
-
36V
B+
U
V
COMM1
REMOTE RESET
IA
IB
IC
W
N2
MAINS 220VAC
REMOTE START
IDLE NC(AUX.OUT4)
VCC
GENS VOLT.
IDLE NO(AUX.OUT4)
GOV IDLE COMM(AUX.OUT4)
GENS SUPPLY
CRANK
FUEL
B+
E.STOP
BUZZ
E
FAILURE(AUX.OUT1)
STOP(AUX.OUT2)
OIL TEMP./FUEL LEVEL
OIL PRESS.1
COOL.TEMP.1
OIL PRESS.2
COOL.TEMP.2
D+
AUX.OUT3 NO
AUX.OUT3 COMM
SPEED
SPEED
LOW OIL PRESS(AUX.INPUT2)
AUX.INPUT4
AUX.INPUT3
HIGH COOL.TEMP(AUX.INPUT1)
AUX.OUT3 NC
MAINS SUPPLY
R
S
T
N1 MAINS VOLT.

- 17 -
VIII、Front and back panel diagram (Minco 830 and Minco840)

- 18 -