Type Probe type without decimal point with decimal point
Sensore: TC
0 TC J °C 0/1000 0.0/999.9
1 TC J °F 32/1832 32.0/999.9
2 TC K °C 0/1300 0.0/999.9
3 TC K °F 32/2372 32.0/999.9
4 TC R °C 0/1750 0.0/999.9
5 TC R °F 32/3182 32.0/999.9
6 TC S °C 0/1750 0.0/999.9
7 TC S ° F 32/3182 32.0/999.9
8 TC T °C -200/400 -199.9/400.0
9 TC T °F -328/752 -199.9/752.0
10 TC B °C 44/1800 44.0/999.9
11 TC B °F 111/3272 111.0/999.9
12 TC E °C -100/750 -100.0/750.0
13 TC E °F -148/1382 -148.0/999.9
14 TC N °C 0/1300 0.0/999.9
15 TC N °F 32/2372 32.0/999.9
16 L-GOST °C 0/600 0.0/600.0
17 L-GOST °F 32/1112 32.0/999.9
18 TC U °C -200/400 -199.9/400.0
19 TC U °F -328/752 -199.9/752.0
20 TC G °C 0/2300 0.0/999.9
21 TC G °F 32/4172 32.0/999.9
22 TC D °C 0/2300 0.0/999.9
23 TC D °F 32/4172 32.0/999.9
24 TC C °C 0/2300 0.0/999.9
25 TC C °F 32/4172 32.0/999.9
26 Ni-Ni18Mo °C 0/1100 0.0/999.9
27 Ni-Ni18Mo °F 32/2012 32.0/999.9
28 TC CUSTOM CUSTOM
29 TC CUSTOM CUSTOM
30 PT100 °C -200/850 -199.9/850.0
31 PT100 °F -328/156 2 -199.9/999.9
32 JPT100 °C -200/600 -199.9/600.0
33 JPT100 °F -328/1112 -199.9/999.9
34 PTC °C -55/120 -55.0/120.0
35 PTC °F -67/248 -67.0/248.0
36 NTC °C -10/70 -10.0/70.0
37 NTC °F 14/158 14.0/158.0
38 0...60 mV -1999/9999 -199.9/999.9
39 0...60 mV Custom scale Custom scale
40 12...60 mV -1999/9999 -199.9/999.9
41 12...60 mV Custom scale Custom scale
42 0...20 mA -1999/9999 -199.9/999.9
43 0...20 mA Custom scale Custom scale
44 4...20 mA -1999/9999 -199.9/999.9
45 4...20 mA Custom scale Custom scale
46 0...10 V -1999/9999 -199.9/999.9
47 0...10 V Custom scale Custom scale
48 2...10 V -1999/9999 -199.9/999.9
49 2...10 V Custom scale Custom scale
50 0...5 V -1999/9999 -199.9/999.9
51 0...5 V Custom scale Custom scale
52 1...5 V -1999/9999 -199.9/999.9
53 1...5 V Custom scale Custom scale
54 0...1 V -1999/9999 -199.9/999.9
55 0...1 V Custom scale Custom scale
56 200mv..1V -1999/9999 -199.9/999.9
57 200mv..1V Custom scale Custom scale
58 Cust10 V-20mA -1999/9999 -199.9/999.9
59 Cust10 V-20mA Custom scale Custom scale
60 Cust 60mV -1999/9999 -199.9/999.9
61 Cust 60mV Custom scale Custom scale
62 PT100-JPT CUSTOM CUSTOM
63 PTC CUSTOM CUSTOM
64 NTC CUSTOM CUSTOM
• InP
tyP. Probe type, signal, enable custom linearization,
and main input scale
InP Input settings
+2 set gradient in digit / sec
FLt
FLd
dP.S
Lo.S
Hi.S
oFS.
Ft.2
Digital filter on input
(if = 0 excludes averaging filter on
sample value)
(*) not available for TC, RTD,
PTC and NTC scales
Digital filter on input
display
Decimal point position for
input scale
Minimum limit of main
input scale
Maximum limit of main
input scale
Offset correction
of main input
Digital filter
aux. input
0.0 ... 20.0 sec
0 ... 9.9
scale points
dP_S Format
0 xxxx
1 xxx.x
2xx.xx (*)
3x.xxx (*)
min...max input range
selected in tyP
min...max input range
selected in tyP
-999 ... 999
scale points
0.0 ... 20.0 sec
SP.rDef. remote setpoint
Val. Type of remote setpoint Absolute Relative
0 Digital Absolute
(from serial line)
1 Digital Reletive to
(from serial line) local setpoint
For custom linearization:
- LO signal is generated with variable below Lo.S or at minimum calibration
value
- HI signal is generated with variable above Lo.S or at maximum calibration
value
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as
deviation from theoretical
value and is expressed as
percentage of full scale (in
°C).
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other
range; error < 0.5% f.s.
Terror < 0.2% f.s. (t > -150°C)
Brange 44...1800°C; error < 0.5% f.s. (t > 300°C) / range
44,0...999,9; error < 1% f.s. (t > 300°C)
Urange -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other
range; error < 0.2% f.s. (t > -150°C)
Gerror < 0.2% f.s. (t > 300°C)
Derror < 0.2% f.s. (t > 200°C)
Crange 0...2300; error < 0.2% f.s. / for other range;
error < 0.5% f.s.
NTC error < 0.5% f.s.
Tc: J, K, E, N, L error < 0,2% f.s.
JPT100 and PTC error < 0,2% f.s.
PT100 scale -200...850°C
Precision better than 0,2% f.s. at 25°C
In range 0...50°C:
• Precision better than 0,2% f.s. in range -200...400°C
• Precision better than 0,4% f.s. in range +400...850°C
(where f.s. refers to range -200... +850°C)
8