4.5. Settingaddresses(Fig.4-4)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
1How to set addresses
Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match
SW11 (for 1 to 9) with “3”.
2 How to set branch numbers SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC controller’s end connection
number.
Remain other than series R2 at “0”.
• The rotary switches are all set to “0” when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
Note:
PleasesettheswitchSW5accordingtothepowersupplyvoltage.
• SetSW5to240Vsidewhenthepowersupplyis230and240volts.
• Whenthepowersupplyis220volts,setSW5to220Vside.
AAddress board
4.6. Sensingroom temperaturewith the built-insen-
sorinaremotecontroller(Fig.4-4)
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the airow at a time when the heating
thermometer is OFF.
5.1. Checking the contents (Fig. 5-1)
• This kit contains the following parts.
Accessory name Q’ty Remark
1Grille 1
2Screw 6 M5 × 0.8 × 16
3Screw 1 4 × 16
4.4. Connectingremotecontroller,indoorandoutdoor
transmissioncables(Fig.4-3)
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The “S” on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
•
Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller’s transmission cable within 10 m using a 0.75 mm2
core cable. If the distance is more than 10 m, use a 1.25 mm2 junction cable.
1MA Remote controller
• Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2 M-NET Remote controller
• Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller.
(Non-polarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable
CRemote controller
4.3.Typesofcontrolcables
1.Wiringtransmissioncables
Types of transmission cable Shielding wire CVVS or CPEVS
Cable diameter More than 1.25 mm²
Length Less than 200 m
2.M-NETRemotecontrolcables
Types of remote control cable Shielding wire MVVS
Cable diameter 0.5 to 1.25 mm²
Length Add any portion in excess of 10 m to within the
longest allowable transmission cable length 200 m
3.MARemotecontrolcables
Types of remote control cable 2-core cable (unshielded)
Cable diameter 0.3 to 1.25 mm²
Length Less than 200 m