En-1
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
1-2. SPECIFICATIONS
nDo not install the unit by yourself (user).
Incompleteinstallationcouldcausereorelectricshock,injuryduetotheunit
falling, or leakage of water. Consult the dealer from whom you purchased
theunitoraqualiedinstaller.
nPerform the installation securely referring to the installation manual.
Incompleteinstallationcouldcausere,electricshock,injuryduetothe
unit falling, or leakage of water.
nWhen installing the unit, use appropriate protective equipment and
tools for safety.
Failure to do so could cause injury.
nInstall the unit securely in a place which can bear the weight of the
unit.
If the installation location cannot bear the weight of the unit, the unit could
fall causing injury.
n Electrical work should be performed by a qualied, experienced electri-
cian, according to the installation manual. Be sure to use an exclusive
circuit. Do not connect other electrical appliances to the circuit.
If the capacity of the power circuit is insufcient or there is incomplete
electricalwork,itcouldresultinareoranelectricshock.
n Do not damage the wires by applying excessive pressure with parts
or screws.
Damagedwirescouldcausereorelectricshock.
n Be sure to cut off the main power in case of setting up the indoor P.C.
board or wiring works.
Failure to do so could cause electric shock.
n Use the specied wires to connect the indoor and outdoor units
securely and attach the wires rmly to the terminal block connecting
sections so the stress of the wires is not applied to the sections. Do
not extend the wires, or use intermediate connection.
Incompleteconnectingandsecuringcouldcausere.
n Do not install the unit in a place where inammable gas may leak.
If gas leaks and accumulates in the area around the unit, it could cause an
explosion.
n Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshockduetodefectivecontact,defective
insulation, exceeding the permissible current, etc.
n Be sure to use the parts provided or specied parts for the installation
work.
The use of defective parts could cause an injury or leakage of water due
toare,anelectricshock,theunitfalling,etc.
n When plugging the power supply plug into the outlet, make sure that
there is no dust, clogging, or loose parts in both the outlet and the
plug. Make sure that the power supply plug is pushed completely into
the outlet.
If there is dust, clogging, or loose parts on the power supply plug or the
outlet,itcouldcauseelectricshockorre.Ifloosepartsarefoundonthe
power supply plug, replace it.
n Attach the electrical cover to the indoor unit and the service panel
to the outdoor unit securely.
If the electrical cover of the indoor unit and/or the service panel of the
outdoorunitarenotattachedsecurely,itcouldresultinareoranelectric
shock due to dust, water, etc.
n When installing, relocating, or servicing the unit, make sure that no
substance other than the specied refrigerant (R410A) enters the
refrigerant circuit.
Any presence of foreign substance such as air can cause abnormal pres-
sure rise and may result in explosion or injury. The use of any refrigerant
otherthanthat speciedforthesystemwill causemechanicalfailure,
system malfunction, or unit breakdown. In the worst case, this could lead
to a serious impediment to securing product safety.
n Do not discharge the refrigerant into the atmosphere. If refrigerant
leaks during installation, ventilate the room.
Ifrefrigerantcomesincontactwithare,harmfulgascouldbegener-
ated. Refrigerant leakage may cause suffocation. Provide ventilation in
accordance with EN378-1.
n Check that the refrigerant gas does not leak after installation has
been completed.
Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeame
of a fan heater, space heater, stove, etc., harmful substances will be
generated.
n Use appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times more than R22. Not using appropriate
tools or materials and incomplete installation could cause the pipes to
burst or injury.
n When pumping down the refrigerant, stop the compressor before
disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running
and the stop valve is open, air could be drawn in and the pressure in the
refrigeration cycle could become abnormally high. This could cause the
pipes to burst or injury.
n When installing the unit, securely connect the refrigerant pipes
before starting the compressor.
If the compressor is started before the refrigerant pipes are connected
and when the stop valve is open, air could be drawn in and the pressure
in the refrigeration cycle could become abnormally high. This could cause
the pipes to burst or injury.
n Fasten a are nut with a torque wrench as specied in this manual.
Iffastenedtootight,aarenutmaybreakafteralongperiodandcause
refrigerant leakage.
n The unit shall be installed in accordance with national wiring regula-
tions.
nEarth the unit correctly.
Do not connect the earth to a gas pipe, water pipe, lightning rod or tele-
phone earth. Defective earthing could cause electric shock.
nBe sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shock or
re.
nPerform the drainage/piping work securely according to the installation
manual.
If there is defect in the drainage/piping work, water could drop from the unit,
soaking and damaging household goods.
n Do not touch the air inlet or the aluminum ns of the outdoor unit.
This could cause injury.
nDo not install the outdoor unit where small animals may live.
If small animals enter and touch the electric parts inside the unit, it could
causeamalfunction,smokeemission,orre.Also,adviseusertokeep
the area around the unit clean.
WARNING (Could lead to death, serious injury, etc.)
*1 Connect to the power switch which has a gap of 3 mm or more when open
to interrupt the source power phase. (When the power switch is shut off, it
must interrupt all phases.)
*2 Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoor
connectingwireinconformitywiththewirespecicationsspeciedinthe
installation manual of the indoor unit.
*3 Neverusepipeswiththicknesslessthanspecied.Thepressureresistance
willbeinsufcient.
*4 Use a copper pipe or a copper-alloy seamless pipe.
*5 Be careful not to crush or bend the pipe during pipe bending.
*6 Refrigerant pipe bending radius must be 100 mm or more.
*7 Insulationmaterial:Heatresistingfoamplastic0.045specicgravity
*8 Besuretousetheinsulationofspeciedthickness.Excessivethickness
maycauseincorrectinstallationoftheindoorunitandinsufcientthickness
may cause dew drippage.
*
9
If the outdoor unit is installed higher than the indoor unit, max. height
difference is reduced to 10 m.
*
10
If pipe length exceeds 20 m, additional refrigerant (R410A) charge is re-
quired. (No additional charge is required for pipe length less than 20 m.)
Additional refrigerant = A × (pipe length (m) - 20)
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
Torque wrench
Wrench (or spanner)
4 mm hexagonal wrench
Flare tool for R410A
GaugemanifoldforR410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer
ENGLISH
CONTENTS
1. BEFORE INSTALLATION ............................................................1
2. OUTDOOR UNIT INSTALLATION ...............................................3
3.FLARINGWORKANDPIPECONNECTION...............................3
4.PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN......... 4
5.PUMPINGDOWN ........................................................................ 5
Model
Power supply *1 Wirespecications*2 Pipe length and height difference
*3, *4, *5, *6, *7, *8 Outdoor Noise level
Rated
Voltage
Fre-
quency
Breaker
capacity Power supply
Indoor/
outdoor con-
necting wire
Max. pipe
length per
indoor unit / for
multi-system
Max. height
difference
*9
Max. no. of
bends per
indoor unit / for
multi system
Refrigerant
adjustment
A *10
Cooling Heating
MXZ-2DM40VA 230 V 50Hz 15 A 3-core 2.0 mm24-core
1.0/1.5 mm220 m / 30 m 15 m 20 / 30 20 g/m 48 dB (A) 52 dB (A)
CAUTION (Could lead to serious injury in particular environments when operated incorrectly.)