3. Selecting an installation site & accessories
•Select a site with sturdy fixed surface that is strong enough to support the weight of
unit.
•Before installing unit, the routing to carry in unit to the installation site should be
determined.
•Select a site where the unit is not affected by entering air.
•Select a site where the flow of supply and return air is not blocked.
•Select a site where refrigerant piping can easily be installed to the outside.
•Select a site which allows the supply air to be fully distributed in a room.
•Do not install unit at a site near a lot of oil or steam.
•Do not install unit at a site where combustible gas may generate, flow in, stagnate
or leak.
•Do not install unit at a site where there is equipment generating high frequency
waves (a high frequency wave welder for example).
•Do not install unit at a site where fire detector is located at the supply air side. (Fire
detector may operate erroneously due to the heated air supplied during heating
operation.)
•If there are chemicals in the area, such as chemical plants and hospitals, full inves-
tigation is required before installing unit. (The plastic components may be damaged
depending on the chemical product applied.)
•If the unit runs for long hours when the air above the ceiling is at high temperature/
high humidity (due point above 79 °F [26 °C]), condensation may be produced in
the indoor unit. Add insulation material (10-20 mm [13/32 to 13/16 in]) to the entire
surface of the indoor unit to avoid condensation.
3.1. Install the indoor unit on a ceiling strong enough
to sustain its weight
[Fig. 3-1] (P.2)
AAccess door BElectrical parts box
CAir inlet DAir outlet
ECeiling surface FService space (viewed from the side)
GService space (viewed from the direction of arrow)
1600 mm [23-5/8 in] or more 2100 mm [3-15/16 in] or more
310 mm [13/32 in] or more 4300 mm [11-13/16 in] or more
Warning:
The unit must be securely installed on a structure that can sustain its weight. If
the unit is mounted on an unstable structure, it may fall down, causing injuries.
3.2. Securing installation and service space
•Select the optimum direction of supply airflow according to the configuration of the
room and the installation position.
•As the piping and wiring are connected at the bottom and side surfaces, and the
maintenance is made at the same surfaces, allow a proper space properly. For the
efficient suspension work and safety, provide a space as much as possible.
3.3. Outdoor unit
Ventilation and service space
Units should be installed by licensed contractor accordingly to local code require-
ments.
For outdoor units to be connected, refer to the Installation Manual that comes with
the units.
3.4. Indoor unit accessories
The unit is provided with the following accessories:
ytitnauQemaN.oN
1
Pipe cover (for refrigerant piping joint) 120 mm [3/4 in] Small diameter
1
2
Pipe cover (for refrigerant piping joint) 120 mm [3/4 in] Large diameter
1
37dnabeiT
4W 8)gnignahrof(rehsa
51esohniarD
61]ni8/3[mm06)esohniarDrof(rev
ocepiP
71]ni61/3[mm03)esohniarDrof(revocepiP
8W 2)gniriwecruosrewoprof(rehsa
4. Fixing hanging bolts
4.1. Fixing hanging bolts
[Fig. 4-1] (P.2)
ACenter of gravity
Hanging structure
•Ceiling: The ceiling structure varies from building to one another. For detailed infor-
mation, consult the construction company.
5. Installing the unit
5.1. Hanging the unit
ss
ss
sTransport the indoor unit to the site in its original packing material.
ss
ss
sTo hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.
[Fig. 5-1] (P.2)
AUnit
BLifting machine
[Fig. 5-2] (P.2)
CNuts (field supplied)
DWashers (accessory)
EM10 hanging bolt (field supplied)
5.2. Confirming the unit’s position and fixing hanging
bolts
ss
ss
sEnsure that the hanging bolt nuts are tightened to fix the hanging bolts.
ss
ss
sTo ensure that drain is discharged, be sure to hang the unit at level using a
level.
Caution:
Install the unit in horizontal position. If the side with drain port is installed
higher, water leakage may be caused.
Center of gravity and Product Weight
Model name
NTXDKS09A112AA
NTXDKS12A112AA
NTXDKS15A112AA
NTXDKS18A112AA
W (mm [in])
625 [24-5/8]
625 [24-5/8]
625 [24-5/8]
625 [24-5/8]
L (mm [in])
752 [29-5/8]
952 [37-1/2]
952 [37-1/2]
1152 [45-3/8]
X (mm [in])
263 [10-3/8]
286 [11-9/32]
280 [11-1/32]
285 [11-1/4]
Y (mm [in])
351 [13-27/32]
448 [17-21/32]
437 [17-7/32]
527 [20-3/4]
Z (mm [in])
106 [4-3/16]
104 [4-1/8]
104 [4-1/8]
104 [4-1/8]
Product Weight (kg [Ib])
19 [42]
22 [49]
23 [51]
26.5 [59]
•If necessary, reinforce the hanging bolts to protect against earthquakes.
*Use M10 for hanging bolts and reinforcements to protect against earthquake
(field supplied).
1Ceiling reinforcement (edge beam, etc.) must be required to keep the ceiling level
and to prevent it from vibrating.
2Cut and remove the ceiling beams.
3Reinforce the ceiling, and add other beams for fixing the ceiling boards.
10_VN79D601H01_en.p65 18.9.3, 13:369
8
Warning:
•Do not use refrigerant other than the type indicated in the manuals provided
with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during
use, during repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC TRANE HVAC US LLC cannot be held responsible for
malfunctions or accidents resulting from the use of the wrong type of refrigerant.
•When handling this product, always wear protective equipment.
EG: Gloves, full arm protection namely boiler suit, and safety glasses.
- Improper handling may result in injury.
•Do not install it by yourself (customer).
Incomplete installation could cause injury due to fire, electric shock, the unit
falling or leakage of water. Consult the dealer from whom you purchased the
unit or special installer.
•Install the unit securely in a place which can bear the weight of the unit.
When installed in an insufficient strong place, the unit could fall causing in-
jured.
•Use the specified wires to connect the indoor and outdoor units securely and
attach the wires firmly to the terminal board connecting sections so the stress
of the wires is not applied to the sections.
Incomplete connecting and fixing could cause fire.
•Do not use intermediate connection of the power cord or the extension cord
and do not connect many devices to one AC outlet.
It could cause a fire or an electric shock due to defective contact, defective
insulation, exceeding the permissible current, etc.
•Check that the refrigerant gas does not leak after installation has completed.
•Perform the installation securely referring to the installation manual.
Incomplete installation could cause a personal injury due to fire, electric shock,
the unit falling or leakage of water.
•Perform electrical work according to the installation manual and be sure to
use an exclusive circuit.
If the capacity of the power circuit is insufficient or there is incomplete elec-
trical work, it could result in a fire or an electric shock.
•Attach the electrical part cover to the indoor unit and the service panel to the
outdoor unit securely.
If the electrical part cover in the indoor unit and/or the service panel in the
outdoor unit are not attached securely, it could result in a fire or an electric
shock due to dust, water, etc.
•Be sure to use the part provided or specified parts for the installation work.
The use of defective parts could cause an injury or leakage of water due to a
fire, an electric shock, the unit falling, etc.
•Ventilate the room if refrigerant leaks during operation.
If the refrigerant comes in contact with a flame, poisonous gases will be re-
leased.
1. Safety precautions
•Please report to or take consent by the supply authority before connection
to the system.
•Be sure to read “Safety precautions” before installing the air conditioner.
•Be sure to observe the cautions specified here as they include important
items related to safety.
•The indications and meanings are as follows.
Warning:
Could lead to death, serious injury, etc.
Caution:
Could lead to serious injury in particular environments when operated incor-
rectly.
•After reading this manual, be sure to keep it together with the instruction
manual in a handy place on the customer’s site.
Symbols put on the unit
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts.
: Indicates that the main switch must be turned off before servicing.
: Beware of electric shock.
: Beware of hot surface.
Warning:
Carefully read the labels affixed to the main unit.
Caution:
•Ground the unit.
Do not connect the ground wire to a gas pipe, water pipe arrester or telephone
ground wire. Defective grounding could cause an electric shock.
•Do not install the unit in a place where an inflammable gas leaks.
If gas leaks and accumulates in the area surrounding the unit, it could cause
an explosion.
•Take measures to prevent electrical leakage as required.
•Perform the drainage/piping work securely according to the installation
manual.
If there is a defect in the drainage/piping work, water could drop from the unit
and household goods could be wet and damaged.
•Fasten a flare nut with a torque wrench as specified in this manual.
When fastened too tight, a flare nut may broken after a long period and cause
a leakage of refrigerant.
2.2. Outdoor unit
•Where it is not exposed to strong wind.
•Where airflow is good and dustless.
•Where it is not exposed to rain and direct sunshine.
•Where neighbours are not annoyed by operation sound or hot air.
•Where rigid wall or support is available to prevent the increase of operation sound
or vibration.
•Where there is no risk of combustible gas leakage.
•When installing the unit at a high level, be sure to fix the unit legs.
•Where it is at least 3 m [10 ft] away from the antenna of TV set or radio. (Otherwise,
images would be disturbed or noise would be generated.)
•Install the unit horizontally.
Caution:
Avoid the following places for installation where air conditioner trouble is li-
able to occur.
•Where there is too much machine oil in the air.
•Salty environments as seaside areas.
•Hot-spring areas.
•Where sulfide gas exists.
•Other special atmospheric areas.
2. Selecting the installation location
2.1. Indoor unit
•Where airflow is not blocked.
•Where cool air spreads over the entire room.
•Where it is not exposed to direct sunshine.
•At a distance 1 m [39-3/8 in] or more away from a TV and radio (to prevent picture
from being distorted or sound from being generated).
•In a place as far away as possible from fluorescent and incandescent lights (so the
infrared remote control can operate the air conditioner normally).
•Where the air filter can be removed and replaced easily.
Warning:
Mount the indoor unit into a ceiling strong enough to withstand the weight of
the unit.
Contents
1. Safety precautions ................................................................................... 8
2. Selecting the installation location ............................................................. 8
3. Selecting an installation site & accessories ............................................. 9
4. Fixing hanging bolts ................................................................................. 9
5. Installing the unit ...................................................................................... 9
6. Refrigerant piping work .......................................................................... 10
7. Duct work ............................................................................................... 12
8. Electrical work ........................................................................................ 12
9. Test run .................................................................................................. 14
10. Easy maintenance function .................................................................... 17
11. Maintenance .......................................................................................... 17
10_VN79D601H01_en.p65 18.9.3, 13:368