- 4 -
4 Setup the primary current
(
All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4
)
(1)In 4-1, Push the ▲or ▼key, and move the cursor to the “3 A rate”.
(2)Push the / Phase key.
(3)4-2 will be displayed.
[Sensor]:Direct⇔5A⇔
When “Direct” setting
[PRI A]:50A⇔100A
When “5A” setting
⇔250A⇔400A⇔600A⇔
[PRI A]:5A⇔6A⇔7.5A⇔8A⇔10A⇔12A⇔15A⇔20A⇔25A⇔
30A⇔40A⇔50A⇔60A⇔75A⇔80A⇔100A⇔120A⇔
150A⇔200A⇔250A⇔300A⇔400A⇔500A⇔600A⇔
750A⇔800A⇔1000A⇔1200A⇔1250A⇔1500A⇔
1600A⇔2000A⇔2500A⇔3000A⇔4000A⇔5000A⇔
6000A⇔7500A⇔8000A⇔10000A⇔12000A⇔
20000A⇔25000A⇔30000A⇔SP⇔
[SP.PRI.A] :5.0~30000A(100A
10A less than,the upper two digits.
)
10A or more is possible to set the upperthree digits.
(
)
“
”
(2)Push the +or -key, and select sensor type.
(3)Push the ▲or ▼key, and move the cursor to the “PRI A”side.
(4)Push the +or -key, and change the primary current value.
(5)Push the / Phase key, and confirm the setting value.
(6)Transition to the following screen by the setting wiring type and primary current value.
[SP]setting →To 4-3
(
)Push the ▲▼+ -
key, and change the set value.
(2)Push the / Phase key, and confirm the setting value.
(3)4-1 will be displayed.
5 Setup the display mode
(
All models except for EMU4-LG1-MB, EMU4-PX4 and EMU4-AX4
)
5-1. (1)In 5-1, push the ▲or ▼key, and move the cursor to the “4 DISP.Mode”.
(2)Push the / Phase key.
(3)5-2 will be displayed.
Set the measurement elements to be displayed in the display unit.
(1)Push the ▲or ▼key, and select the display mode.
(2)Push the / Phase key.
(3)Transition to the following screen by the selection of measurement mode.
[Wh+A+4] setting →To 5-3
[Harmonics] setting → To 5-4
[DISP.Mode]:Wh+A+4
*In case of the model EMU4-BM1-MB, the “Harmonics”
displayed.
⇔Harmonics⇔
Wh+A+4…In addition to the active energy and current,
items can be displayed by selection.
(The harmonics data is only about total.)
Harmonics…It can display about harmonic data at each order.
(1)Push the ▲or ▼key, and move the cursor to target element.
(In the actual display, it will be scrolling display of each three elements in one screen.)
(2)Push the +or -key, and choose the selected or desselected.
(3)When selecting the other measurement item, repeat the operation from (1)to (2).
(4)Push the / Phase key, and determine the setting.
(5)Transition to the following screen by the selection of measureme nt mode.
Not check “HA”and “HV”→To 5-1
“
”
“
”
[Element]:V, W, var, VA, PF, Hz, CONV.Wh, PRD.Wh,
OP.Time, REG.Wh, varh, CONV.PLS, UNB.V, HA, HV
(Deselected),(Selected)
*The selectable number of elements is up to
4. So, change the
selection at the statethat already 4 items are selected,
deselectthe items before changing.
* Elements can't select in follow table.
In the case can not select
UNB.A
In the case of setting simplicity measuring
Wh
In the case of EMU4-BM1-MB, EMU4-A2,
EMU4-VA2.
External input is not contact input.
Pulse In the case EMU4-BM1-MB, EMU4-A2,
EMU4-VA2.
Pulse input is not contact input.
HA
In the case EMU4-BM1-MB.
Wiring is 1P2W,1P3W or 3P3W
Wh
converted
In the case EMU4-BM1-MB
*Elements is showed follow.
V:Voltage
W:Electric power
var:reactive power
VA:apparent power
PF:Power factor
Hz:frequency
Wh converted value:Electric energy (converted)
Periodic Wh:Electric energy (regeneration)
Regenerated Wh:Periodic electric energy
varh:Reactive energy (consumption lag)
PULSE:Pulse count value and pulse converted value
UNB.A:Current unbalance rate
UNB.V:Voltage unbalance rate
HA:Harmonics current
HV:Harmonics voltage
(1)Push the ▲or ▼key , and change the “HA,HV”value.
(2)Push the / Phase key.
(3)5-1 will be displayed.
[HA,HV]:r.m.s.
*In case of the model EMU4-BM1-MB, “HA,HV” can not be set.
⇔%
r.m.s.… to display the RMS value of harmonic
harmonic voltage. (The “%” not be displayed.)
%… to display the distortion rate and
content rate of harmonic
current or harmonic voltage. (The “r.m.s.”
6(1) Setup the measurement mode
(
EMU4-LG1-MB only
)
6(1)-1. (1)In 6(1)-1, push the ▲or ▼key, and move the cursor to the “5 MEA.Mode”.
(2)Push the / Phase key.
(3)6(1)-2 will be displayed.
Setup the measurement mode of “Io” or ”Ior”.
(1)Push the ▲or ▼key, and select the measurement mode.
(2)Push the / Phase key.
(3)6(1)-1 will be displayed.
[MEA.Mode]:High SENS.⇔Low SENS.⇔
Low SENS.…0~1000mA 1mA step
High SENS.…0.00~100mA 0.01mA step
6(2) Setup the measurement mode
EMU4-AX4 only
6(2)-1. (1)In 6(2)-1, push the ▲or ▼key, and move the cursor to the “5 MEA.Mode”.
(2)Push the / Phase key.
(3)6(2)-2 will be displayed.
Setup the measurement mode of AD converted.
6(2)-2. (1)Push the ▲or ▼key, and select the measurement mode.
(2)Push the / Phase key.
(3)6(2)-1 will be displayed.
[MEA.Mode]:50ms SAMP.⇔1ms SAMP.⇔
50ms SAMP.…AD converted in a cycle of 50ms.
1ms SAMP.…AD converted in a cycle of 1ms.
50ms SAMP.
1ms SAMP.
[Measure]
3A rate
4DISP.Mode
5MEA.Mode
High SENS.
Low SENS.
[Measure]
3A rate
4DISP.Mode
5MEA.Mode
r.m.s.
V
W
var
VA
PF
Hz
CONV.Wh
PRD.Wh
OP.Time
REG.Wh
varh
PLS
UNB.A
UNB.V
HA
HV
Wh+A+4
Harmonics
2V rate
3A rate
001000A
[1]
Direct
[PRI A]
1Wiring
2V rate