3Issue 1.0
Installation
1. IMPORTANT: ensure all electrical connections are isolated before commencing any work on the
unit.
2. The unit is designed to be mounted in any single-gang British Standard pattress box (surface or
ush mounted) which has a minimum internal depth of 20mm.
3. Ensure best-practices are used when choosing a location for the thermostat so that optimal
thermostatic control is achieved. Do not mount near drafts, heaters, radiators, air conditioners,
in direct sunlight or any other place where the sensed room temperature may be unnaturally
inuenced. A good mounting height is typically between 1m and 2m from the oor.
4. Connect the wiring as shown in the diagram (or any suitably appropriate form) via the screw-
terminals. Make sure to choose the correct output terminals that are suitable to your application.
5. Adjust the internal thumbwheels to suit the desired operational requirements (see below).
6. Afx the thermostat to the pattress box using the supplied M3.5 raised-countersunk screws then
nally insert the screw-caps for a neat nish.
7. The screw caps may be removed without damage using a sticky putty such as blu-tack.
Operation
1. IMPORTANT: ensure all electrical connections are isolated before commencing any work on the
unit.
2. Adjust the “SETPOINT” dial to the temperature the room is to be maintained at when the boost
mode is activated via the pushbutton (typically 21ºC).
3. Adjust the “SETBACK” dial to the temperature required below the setpoint when in setback mode
(typically 3°C to 6°C). NOTE: The setback temperature is subtracted from the setpoint. It is NOT
an absolute temperature.
4. Adjust the “TIMEOUT” to the number of minutes/hours that the boost mode should last for.
5. Example set-up:
SETPOINT set to 21ºC, SETBACK set to 4ºC, TIMEOUT set to 2 hours:
BOOST mode (RED led is ON)
The room temperature will be maintained at 21°C
After 2 hours (or the pushbutton is pressed) the unit will switch to SETBACK mode
SETBACK mode (RED led is OFF)
The room temperature will be maintained at 21 - 4 = 17°C
The pushbutton may be pressed to switch to BOOST mode
Technical Specication
Power supply: 220V - 240V AC 50Hz (live/neutral)
22V - 26V AC or DC (“/24V” variant only)
Output switch rating: 10A, 250V AC 50Hz (resistive)
Output switch type: Changeover relay (volt-free)
Temperature setpoint: +12°C to +26°C
Temperature differential: Fixed at 1°C (+/- 0.5°C)
Temperature setback: 0°C to 14°C below the setpoint
Timeout period: 15 minutes to 8 hours
Sensor accuracy: ±0.2°C
Sensor drift: 0.15°C over 5 years
Guarantee: 5 Years
Weight: 88g
Dimensions: 86mm x 86mm x 26mm