Issue 1.0 3
Installaon
1. The unit is designed to be mounted in any single-gang Brish Standard paress box (surface or ush mounted)
which has a minimum internal depth of 20mm.
2. Ensure best-pracces are used when choosing a locaon for the thermostat so that opmal thermostac control
is achieved. Do not mount near dras, heaters, radiators, air condioners, in direct sunlight or any other place
where the sensed temperature may be unnaturally inuenced. A good mounng height is typically between 1m
and 2m from the oor.
3. Connect a wiring as shown in Figure 1 (or any suitably appropriate form) via screw-terminals. Make sure to choose
the correct output terminals that are suitable to your applicaon.
4. Adjust the internal thumbwheels to suit the desired operaonal requirements (see below).
5. Ax the thermostat to the paress box using the supplied M3.5 raised-countersunk screws then nally insert the
screw-caps for a neat nish.
6. The screw caps may be removed without damage using a scky puy such as blu-tack.
Operaon
1. Adjust the setpoint (“Setpoint”) dial to the temperature the room is to be regulated to in the ‘Med’ mode
(typically 20°C).
2. Adjust the set-back/set-forward (“S’Bck/S’Fwd”) dial to the number of °C either side of the ‘Med’ temperature
that the ‘Low’ and ‘High’ temperatures are to be (typically 2°C).
3. Set the dierenal (“Di.”) to the total temperature swing either side of the resulng setpoint that the room
temperature is required to keep within (typically 1°C).
4. Example set-up:
Setpoint set to 20°C, Dierenal set to 1°C, Set-Back/Set-Forward set to 2°C.
Low mode - The unit will maintain the temperature between 17.5°C and 18.5°C
Med mode - The unit will maintain the temperature between 19.5°C and 20.5°C
High mode - The unit will maintain the temperature between 21.5°C and 22.5°C
Notes
1. Applying power for the rst me: The output of the thermostat may not switch in response to temperature for
up to 60 seconds aer rst powering on. This is normal behaviour due to a necessary inialisaon phase - please
wait unl this is completed before aempng to test the thermostat. Normal operaon will resume as soon as
the inialisaon phase has completed.
If the unit has already completed inialisaon then short interrupons of power of up to 5 minutes will not trigger
the inialisaon phase and the humidistat will resume normal operaon immediately within a couple of seconds.
Power interrupons longer than 5 minutes may trigger the inialisaon phase again.