Figure 1. Heat-tracing control
Circuit1
Circuit2
GØØ
Heating
cable
Power
connection
Thermostat bulb
(see "Positioning"
instructions above
for mounting details)
Braid
Control
thermostat
Relay
GFEPD
Power supply
208-V or 240-V supply – 240-V heater
GØØ
WIRING
INSTALLING THE THERMOSTAT
1. Verifythatthethermostat
is suitable for the area
where it is to be installed.
2. Checkthelinevoltageand
the heat-tracing load to
ensure that the thermostat
ratings are not exceeded.
3. Mounttheunitusingunistrutortheuniversalmounting
bracket(UMB-263757)inapositionthatpreventscondensation
from draining into the enclosure from the connecting conduit
(seediagramabove).
pOSITIONING THE SENSOR BULB
4. Position the bulb in the
lower quadrant of the pipe
as shown in the diagram
to the left. Place the bulb
at least three feet from
pipesupports,valves,or
other heat sinks; protect
the capillary from kinks or
bends less than 1⁄2 inch in
radius.
5. TapethebulbfirmlytothepipewithAT-180aluminumtape,
making sure there is no air space between the bulb and pipe.
Donotoverlapthebulbandheatingcablewiththesamepiece
ofAT-180tape.
6. For metal-tank-wall sensing, use the BCK-35 bulb clamp
(purchased separately from Pentair Thermal Management)
andinstalltheclamppertheinstructionsprovided.Makesure
there is no air space between the tank wall and the bulb.
For installation on plastic tanks, contact Pentair Thermal
Managementat(800)545-6258.
SETTING THE THERMOSTAT
7. Setthethermostatdialtothedesiredtemperature,thenfinish
wiring.
8. Completeinsulating.Donotturnthesystemonuntilthebulbis
coveredwiththermalinsulation.
9. Fill the piping or tank. Once the thermostat has begun to cycle,
check the fluid temperature with an immersed thermostat
(best for plastic systems) or an accurate temperature indicator.
Adjust the dial setting, if necessary.
Conduit
drain
90 Heating cable
Control thermostat bulb
AT-180 tape
AT-180 tape
Heating cable
Control thermostat bulb
Double traced
Single traced