
Mueller Compact Chiller Models CP2-10 and CP2-20 Effective May 15, 2009
Installation and Operation Manual, Part No. 8826238 Revised January 31, 2019
5.1 SYS EM EVACUA ION
With refrigerant piping completed and leak tested, equipment is ready to evacuate. A quality vacuum pump capable
of 500 micron vacuum is necessary for adequate and dependable system evacuation. Moisture in a refrigeration
system can cause corrosion, expansion valve freeze-up, and oil sludge.
Attach vacuum pump to both high and low side of system through compressor service valves and evacuate to 500
microns. (All service valves, hand valves, and solenoids must be open during evacuation.)
NOTE: Service valves are back seating valves and must be in mid-position to open both sides of the system to the
evacuation pump.
IMPORTANT: As a fi al leak test, close the valve to the vacuum pump a d e sure vacuum is mai tai ed
below 1,000 micro s for five mi utes.
5.2 SYS EM CHARGING (ALSO REFER O CONDENSING UNI MANUAL)
With the system wired, plumbed, and evacuated, the unit is ready to charge with the appropriate refrigerant. All
charging lines and manifolds must be evacuated prior to admitting refrigerant into the system to prevent
contaminating the system with non-condensable.
1. Place the rotary switch in the pump position and ensure liquid solution circulation through the brazed plate
evaporators. Admit liquid refrigerant into the evacuated system until low and high side pressure is above the
freeze point of the liquid solution or 32°F.
2. With the charging line connected to the receiver service valve, admit liquid refrigerant into the high side of the
system until the flow stops due to pressure equalization between high side and the refrigerant drum. Back seat
service valve, close manifold valve, and disconnect charging line.
3. Energize equipment and continue to admit liquid into the low side of system until the liquid line sight glass
clears, indicating a fully charged system (it may be necessary to bypass the low pressure control on initial start
to prevent nuisance trips until low side pressure is above cut-out point of control).
NOTE: If utilizing a Mueller E-Star HiPerForm condensing unit, liquid may be charged upstream of the
accumulator/heat exchanger. Refer to E-Star condensing unit manual for more detailed charging instructions.
5.3 SYS EM S AR -UP
This is a continuation of system charging and must be performed before equipment can be left operating and
unattended. This will involve checking and ad usting all safety and operating controls. Do not attempt to function
safety controls without some means of stopping compressor in the event of extreme high or low pressure
conditions that could damage the equipment. If controls fail to function at setpoints, determine the cause and
correct.
CAUTION: Bypassi g a y safety co trol step, other tha for testi g purposes, is da gerous to perso el
a d equipme t a d ullifies equipme t warra ty.
NOTE: Energize crankcase heaters and allow a minimum of four hours of operation before a compressor start-up.
9
Sectio 5.0 – Evacuatio , Chargi g, a d Start-Up of System