Multilink 010-505-10 User manual

INSTALL AND OPERATION
Copyright © 2020 Multilink Inc. • All rights reserved • Specifications subject to change without notice • Rev. March 25, 2020 11:46 AM
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Installation and Operation Manual
Safety Automatic Transfer Switch
Documented Power Supply Models
MODEL PART NUMBER INPUTS OPTIONS
Safety Automatic
Transfer Switch
010-505-10 120 VAC 60Hz Mates with EDP
Series Only
Safety Automatic
Transfer Switch
010-505-20 120 VAC 60Hz Universal with
Line Interactive
UPS’

2
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
s
Section 1: Critical Safety Issues 3
Safety Admonishments................................................................................................................................................................................................... 3
Emergency Shutdown..................................................................................................................................................................................................... 4
General Safety Issues........................................................................................................................................................................................................ 4
Safety Issues with the SATS Installation & Use....................................................................................................................................................... 4
Multiple Power Sources................................................................................................................................................................................................... 5
Enclosure Safety Issues.................................................................................................................................................................................................... 5
Section 2: Introduction 6
Safety Automatic Transfer Switch Overview of Operation................................................................................................................................. 6
Features................................................................................................................................................................................................................................. 6
Unpacking & Inspection.................................................................................................................................................................................................. 6
Missing or Damaged Items............................................................................................................................................................................................ 7
Original Shipping Container.......................................................................................................................................................................................... 7
Section 3: Front Panel Controls & Connections 8
Controls................................................................................................................................................................................................................................. 8
Connections ........................................................................................................................................................................................................................ 8
Section 4: Installation and Setup 9
Preparation .......................................................................................................................................................................................................................... 9
Grounding............................................................................................................................................................................................................................ 9
Placement in the Enclosure.........................................................................................................................................................................................10
Wiring ..................................................................................................................................................................................................................................11
Section 5: Startup & Operation 13
Operating Modes.............................................................................................................................................................................................................13
Section 6: Shutdown 15
Section 7: Replacement Parts 15
Part List...............................................................................................................................................................................................................................15
Section 8: Troubleshooting 16
Section 9: Specications 17
Parameter Specications & Notes .............................................................................................................................................................................17

3
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
EMI / RFI STATEMENT
This device has been designed and manufactured to comply with the EMI / RFI emission limits and
immunity characteristics as set forth in Standards EN 55022 and EN 55024. These limits are designed
to provide reasonable protection against harmful interference when this equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy and,
if not installed in accordance with this instruction manual, may cause harmful interference to radio
communications.
Critical Safety Issues
Section 1: Critical Safety Issues
SAFETY ADMONISHMENTS
Three dierent levels of safety admonishments are used within this instruction manual; specically
DANGER, WARNING, and CAUTION.
Trois niveaux diérents d’avertissements de sécurité sont utilisés dans ce mode d’emploi; spéciquement DAN-
GER, AVERTISSEMENT et ATTENTION.
DANGER
The statement following the DANGER heading alerts the equipment user of a potentially life or
health-threatening situation unless precautions are taken against it. Admonishments of this nature
usually entail the hazards of electrical shock or those encountered that may result in physical injury.
La déclaration sous la rubrique DANGER avertit l’utilisateur de l’équipement d’une situation potentiellement
mortelle ou mortelle, sauf si des précautions sont prises contre lui. Les admonistances de cette nature entraî-nent
habituellement les dangers d’un choc électrique ou ceux rencontrés qui peuvent entraîner des blessures phy-
siques.
WARNING / AVERTISSEMENT
The statement following the WARNING heading alerts the equipment user of a condition or procedure that
could result in interruption of service to the users or subscribers of the service receiving power from this
product.
La déclaration sous le chapitre AVERTISSEMENT avertit l’utilisateur de l’équipement d’une condition ou d’une
procédure qui pourrait entraîner une interruption de service pour les utilisateurs ou les abonnés du service qui
reçoit l’alimentation de ce produit.
s
Section 1: Critical Safety Issues 3
Safety Admonishments................................................................................................................................................................................................... 3
Emergency Shutdown..................................................................................................................................................................................................... 4
General Safety Issues........................................................................................................................................................................................................ 4
Safety Issues with the SATS Installation & Use....................................................................................................................................................... 4
Multiple Power Sources................................................................................................................................................................................................... 5
Enclosure Safety Issues.................................................................................................................................................................................................... 5
Section 2: Introduction 6
Safety Automatic Transfer Switch Overview of Operation................................................................................................................................. 6
Features................................................................................................................................................................................................................................. 6
Unpacking & Inspection.................................................................................................................................................................................................. 6
Missing or Damaged Items............................................................................................................................................................................................ 7
Original Shipping Container.......................................................................................................................................................................................... 7
Section 3: Front Panel Controls & Connections 8
Controls................................................................................................................................................................................................................................. 8
Connections ........................................................................................................................................................................................................................ 8
Section 4: Installation and Setup 9
Preparation .......................................................................................................................................................................................................................... 9
Grounding............................................................................................................................................................................................................................ 9
Placement in the Enclosure.........................................................................................................................................................................................10
Wiring ..................................................................................................................................................................................................................................11
Section 5: Startup & Operation 13
Operating Modes.............................................................................................................................................................................................................13
Section 6: Shutdown 15
Section 7: Replacement Parts 15
Part List...............................................................................................................................................................................................................................15
Section 8: Troubleshooting 16
Section 9: Specications 17
Parameter Specications & Notes .............................................................................................................................................................................17

4
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
CAUTION / ATTENTION
The statement following the CAUTION heading alerts the equipment user of a condition that could
result in damage to the subject equipment or ancillary equipment if care is not exercised during
certain maintenance or operating procedures.
La déclaration suivant la rubrique ATTENTION avertit l’utilisateur de l’équipement d’une condition qui
pour-rait endommager l’équipement concerné ou l’équipement auxiliaire si les soins ne sont pas exercés
pendant certaines procédures de maintenance ou d’exploitation.
Emergency Shutdown Procedure
DANGER
Exercise extreme caution when performing the following procedure. Carry out the steps pre-
cisely in the order given to avoid the possibility of personal injury or equipment damage.
Perform the following procedure if the Safety Automatic Transfer Switch (SATS) must be shut down
and disconnected on an emergency basis:
1. Open the upstream AC utility input circuit breaker servicing the cabinet.
2. If a generator is in use, disconnect the generator from its outside cabinet generator con-
nector to complete shutdown of power to the load.
3. If using the SATS with a Multilink EDP series UPS, turn o the AC circuit breaker and discon-
nect the battery harness from the front of the UPS. The EDP series accepts multiple sources
of power and all must be removed to safety shut down the SATS.
4. If using the SATS with a Line Interactive UPS, open both the AC circuit breaker and DC cir-
cuit breaker on the UPS.
General Safety Issues
The Safety Automatic Transfer Switch that is documented in these instructions has been designed,
tested, and produced to ensure safe, trouble-free operation. Personnel installing or using this SATS
should completely read and fully understand the following safety instructions. They are provided
here as informational guidelines for your continued safety in the usage of this product.
Safety Issues with the Safety Automatic Transfer Switch Installation and Use
The SATS has been designed and built to power Department of Transportation and Intelligent Trac
Systems equipment. It is not intended for any other usage and provides output voltages suitable
only for its intended application. Please contact Multilink if use of this product falls outside of DOT/
ITS equipment.

5
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
DANGER
This SATS operates from an AC source ranging from 55 to 155 volts. DO NOT open any covers
or panels or attempt to perform any service to the SATS without rst removing and discon-
necting all external AC power sources. Only trained, qualied personnel should attempt
service and repair work on the Safety Automatic Transfer Switch.
Multiple Power Sources
The SATS documented in this instruction manual uses more than one source of power. AC utility
line, UPS output power, and AC Generator power may all be connected and provide power to the
SATS at any given moment.
Enclosure Safety Issues
The enclosure and the SATS must be installed by qualied technicians or installers only, using
appropriate mounting hardware in accordance with local codes and construction practices. The
SATS must be installed within a grounded NEMA rated metal enclosure suitable for accommodating
DOT/ITS SATS. Additionally, the enclosure must aord adequate ventilation for the SATS such that a
minimum free air space of 52 mm (2 inches) remains around all sides and the top of the SATS. Tem-
perature of the air owing around the SATS may be rated up to 74° C (165° F). Air intake and exhaust
openings within the enclosure must not be less than what is required to maintain this temperature
requirement. If these temperature limits are routinely exceeded or ventilation requirements cannot
be attained, a suitable forced-air cooling system may be required within the enclosure.
Fig. 1-1 Typical DOT/ITS SATS Enclosure

6
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Introduction
Section 2: Introduction
Overview of Operation
The Safety Automatic Transfer Switch (SATS) is an integral part of an Uninterruptible Power Supply
(UPS) or Battery Backup system. Its intended usage is to provide multiple sources of AC power in
order to operate trac signals, conict monitors, camera equipment, lighting, and additional appli-
cations used in Departments of Transportation and Intelligent Trac Systems (DOT/ITS). With utility
line voltage applied and an UPS activated, the SATS will automatically begin to power the load with
the UPS’regulated output voltage. It also allows the technician to perform utility line, UPS, or gen-
erator maintenance without disrupting power to the trac equipment. By utilizing AC utility power,
UPS power, and AC Generator power, the SATS will automatically determine which power source
to use to continuously power the load. In the event the AC utility line voltage is missing, and UPS
battery backup power has been depleted, an AC generator may be used to automatically power the
load. Normal operation will delay the use of generator power for 30 seconds after AC utility line and
UPS power loss to allow for AC generator initialization and startup. This allows the output voltage of
the generator to stabilize before use. The SATS comes in two models, one which mates specically
to Multilink’s EDP Double Conversion UPS’, and another universal model which mates to Line Inter-
active UPS’.
Safety Automatic Transfer Switch features:
• 120VAC/60Hz output.
• Duplex Outlet with 120V/60Hz/6Amp max to allow for additional equipment to be attached.
• Dry Contact relays to allow for monitoring of Utility line voltage and Generator power.
• UL/CSA and EMI/RFI Compliant.
All Safety Automatic Transfer Switches include:
• 1 SATS, ready for installation in cabinet
• 1 Power harness (four-wire for EDP series, six-wire for universal/Line Interactive)
• 1 7-position dry contact relay connector
• 1 User manual and instruction guide
Unpacking and Inspection
Before installing this equipment, inspect the SATS for shipping damage or missing components. If
the SATS or other items were damaged in shipment, le a damage claim with the shipping company
and contact your Multilink representative immediately. Be sure to retain the original shipping carton
and all packing material for the SATS until you are certain that warranty return will not be required.

7
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Missing or Damaged Items
If items are found to be damaged or missing, contact the shipping company and your Multilink
representative immediately. All damage claims must be led with the shipping company convey-
ing your equipment. Your Multilink representative will be able to assist with immediate equipment
needs if necessary.
Original Shipping Container
When returning a unit for service, use its original shipping container and all original packing ma-
terials. Items damaged as a result of improper packaging will not be covered under provisions of
warranty service.
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and main-
tenance of the Safety Automatic Transfer Switch.

8
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Front Panel Control and Connections
Section 3: Front Panel Control and Connections
The front panel of each Safety Automatic Transfer Switch contains various connections. These items are
described as follows. See gure 3-1, 4-1, and 4-2 for connector locations. Further details regarding use of
control and operation may be found in the Startup and Operation section of this manual.
Control
AUTO/BYPASS SWITCH: This switch allows the SATS to either automatically select the AC power source
when necessary or to Bypass the UPS and generator power sources and utilizes the AC utility voltage to
power the trac equipment during UPS and generator maintenance. LED indicator illuminates in “Bypass”
mode.
UPS INPUT CIRCUIT BREAKER: 20A magnetic circuit breaker for UPS input voltage. This circuit breaker is
used to open or close input power to the UPS and allow for UPS maintenance and removal without discon-
necting power to the load.
Connections
POWER HARNESS: The SATS contains a UPS power harness to connect either the EDP double conversion
UPS or a Line Interactive UPS to the SATS. This harness is model dependent, with the EDP series containing
four, labeled wires, and the Line Interactive model containing six, labeled wires.
MAINS/LOAD/GEN: 3, WECO 324-HDS screw type terminals provide the attachments of “MAINS”AC utility
line voltage, the“LOAD” of the cabinet trac equipment, and the“GEN”generator attachment to the out-
side cabinet generator connector. Max torque of 7.0 lbs-in.
RELAY CONNECTOR: OnShore Tech OSTTJ® 7 pin terminal blocks allow for external alarm reporting to a
conict monitor for both the MAINS and GEN AC power through dedicated dry contacts relays. Each re-
lay has a set of 2 pins. NOTE: The rst set of pins is marked“AUX” and are place holders for UPS’utilizing a
48VDC control wires. Max torque of 5.0 lbs-in.
DUPLEX OUTLET: Provides 120VAC/60Hz power up to 6.0 Amps for additional equipment to be attached.
Fig. 3-1 SATS Front Panel Detail
MAINS/LOAD/GEN
CONNECTORS
DEDICATED DRY
CONTACT RELAYS
6.0A DUPLEX
OUTLET
UPS POWER
HARNESS
BYPASS SWITCH
AND UPS INPUT CIRCUIT
BREAKER

9
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Installation and Setup
Section 4: Installation and Setup
Installing and wiring the Safety Automatic Transfer Switch into an enclosure may be accomplished by con-
necting the utility AC input wires and cabinet load wires to the appropriate connectors of the SATS. If in use,
the generator wires from the outside generator cabinet connector may also be wired to the appropriate
connector. The UPS power harness shall be used to connect the SATS to the UPS according to the wiring dia-
gram. The 7-position dry contact relay connector may be wired to sense the presence of power and report
this to a conict monitor when MAINS or GEN power is currently active or inactive.
In all installations, the following conditions apply and must be observed:
• A service disconnect switch containing over-current protection devices such as circuit breakers or
fuses with appropriate AIC (amperes – interrupting capacity) rating should be placed between the
AC utility source and the service entrance device for the SATS. Where used, the disconnect switch
must be installed in compliance with all national, state and local codes as required.
• For outdoor installations, the AC utility conductors connected to the cabinet service entrance de-
vice shall be physically protected through an appropriate restraining device and conduit, consistent
with local codes and practices.
• Permission to mount the SATS enclosure at any site shall be made in accordance with all legal re-
quirements and local practices of the area.
This SATS is designed for use in both existing and new ground-mount enclosures. Observe the following
procedures during installation of any SATS.
Preparation
e Safety Automatic Transfer Switch has been factory assembled, tested and prepared as a complete
product ready for installation within an enclosure. e installer must verify that the correct type of AC
power receptacle is installed in the enclosure for the input service and SATS selected for use at any giv-
en site. SATS ratings may be veried from the nameplate on the top of the SATS near the duplex outlet.
Grounding
Safety ground and earth ground connections must be in place for the SATS and enclosure for both per-
sonal safety and operational considerations. During SATS and/or enclosure installation, the following
grounding connections must be provided or veried.

10
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
CAUTION
Failure to provide and connect adequate safety and earth grounds at each installation site may result in im-
proper SATS operation or permanent damage to the SATS itself. Grounding facilities and connections must
conform to appropriate national codes and/or local practices.
1.The AC utility conductors installed in the service entrance box must contain a safety ground conduc-
tor. The SATS installer should verify that this grounding conductor is in place, having been installed
along with the AC utility input.
2.A separate enclosure ground wire must be connected between the enclosure ground lug and an
earth ground connection provided by a ground rod installed at the SATS site. In most cases, one
copper or copper-clad steel ground rod of 2.5 meter (8 feet) length driven into the earth will be
sucient to provide the ground connection required. In some instances, a more elaborate ground-
ing method (such as a ring ground) may be required; however, this may be dictated by state or local
codes and depends on conductivity of the soil within the installation area.
3.The dead metal of the service entrance box must be bonded to the metal enclosure that houses the
SATS. Additionally, the ground bar within the service entrance box should be bonded to the metal
enclosures; however, this requirement may be subject to local codes and practices.
4.The grounding wire connected between the SATS enclosure and the earth ground rod should be no
smaller in area than 13 mm² (6 AWG) copper. Both ends of the ground wire should be sealed with an
appropriate anti-oxidation compound.
5.An optional ground bonding connection exists on the 7-position dry contact connector.
Placement in the Enclosure
This SATS has been designed primarily for use within a cabinet or enclosure oering protection from out-
door weather, entry of excessive dust, dirt or moisture, and from unauthorized contact by untrained person-
nel. If used in a controlled environment, the SATS may be located within an indoor equipment cabinet or
may be mounted on a rack shelf. Place the SATS within 36 inches of the line and load terminal block buses
inside the cabinet.
The SATS should be mounted on a ventilated shelf or rack that allows free air circulation, especially through
the right and left side panels of the SATS cabinet. Clearance of at least 1RU or 1.75 inches must be main-
tained around all surfaces of this SATS for unobstructed airow. Temperature of the air entering the SATS
should not exceed 74°C (165° F). System de-rating will occur at 55°C. See Specications.

11
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Wiring
Connect the MAINS, LOAD, GEN, and monitor wiring to the SATS according to the following procedure. Re-
fer to Figs. 4-1 and 4-2 for control and connector positions.
CAUTION
To reduce the risk of re, connect only to a circuit provided with 20A maximum branch circuit over-
current protection in accordance with the National Electrical code, ANSI/NFPA 70 and the Canadian
Electrical Code, Part 1, C22.1
1. Operate the AC line circuit breaker in the service entrance box to the OFF position. If the SATS is
located at a head end or other customer premise site, ensure that the branch circuit breaker chosen
to protect the AC receptacle for the SATS is operated to the OFF position.
2. Operate the UPS Input circuit breaker on the SATS to the OFF position.
3. Wire the SATS as shown in Fig 4-1. Recommended wire strip length of 7mm. Secure the screw termi-
nal contacts with a max torque of 7.0Lbf-in.
Fig. 4-1 SATS and EP1100 (Line Interactive) wiring example

12
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
4. Connect the power harness to the input/output connectors on the UPS.
5. If desired, wire the 7-position dry relay connector. Recommended wire strip length is 7mm, with a
max torque of 5Lb-in. as shown in Fig 4-2 for reporting to the trac controller.
Fig. 4-2 7-position connector wiring example
When using the 7-position MAINS/GEN sense relay connector, please note operation as follows:
1. The rst 2 positions on the left of the connector labeled “AUX’are intended for use with UPS systems
that have external control wires to operate that system’s respective transfer switch. These two posi-
tions are to be used to safely secure those wires. The control wires will not be used by the SATS.
2. Positions 3 and 4 are used to report the presence of AC utility line power. When AC utility line volt-
age is present, the dry relay contacts of these 2 positions will close. When AC utility line voltage is
absent, the dry relay contacts will open.
3. Positions 5 and 6 are used to report the presence of AC Generator power. When AC Generator volt-
age is present, the dry relay contacts of these 2 positions will close. When AC Generator voltage is
absent, the dry relay contacts will open.
4. Position 7 is an additional grounding point.

13
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Startup and Operation
Section 5: Startup and Operation
The SATS is ready to be placed into operation after it has been installed in its enclosure and all input and
output connections have been made. Ensure that AC utility line power is available to the SATS and then
perform the following steps in sequence.
CAUTION
The following steps in these startup and operating procedures MUST be performed exactly as presented;
otherwise, permanent damage to the SATS may result.
For Normal Operation, perform the following procedure:
1. Verify that all connections and initial wiring is complete, as previously outlined and described.
2. Operate the AUTO/Bypass switch to the“AUTO”position.
3. Operate the upstream AC utility line circuit breaker serving the SATS to the ON position.
4. The SATS is now operating in its normal mode, assuming application of appropriate AC line power.
The load is now being powered from AC utility line voltage. NOTE: This voltage is not regulated.
5. If an UPS is in use, operate the UPS Input circuit breaker on the SATS to the ON position and then
operate the UPS’ respective input circuit breaker in the ON position. After its initial startup, the UPS
will automatically begin to power the load with regulated voltage.
For Maintenance or Bypass mode, perform the following procedure:
1. Verify AC utility line voltage is present, and the upstream AC utility line circuit breaker is in the ON
position.
2. Place the AUTO/Bypass switch in the“Bypass”mode. The LED shall illuminate when in Bypass mode.
This will disconnect the load from the UPS and power the load directly from utility power.
3. Verify the SATS is maintaining the load with AC utility line voltage. NOTE: This voltage is not regulat-
ed.
4. Remove the battery harness from the UPS or operate the DC circuit breaker to the OFF position.
5. Place the AC circuit breaker on the UPS to the OFF position.
6. Place the UPS Input circuit breaker on the UPS to the OFF position.
7. The UPS and battery string may now be maintained by a qualied technician.

14
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Alternative Mode
An alternative operating mode is available to perform authorized AC utility voltage shutdown, with the use
of an AC generator, without interrupting the load. This mode must be congured before the SATS is in oper-
ation and shall not be performed when in use. To use this mode, the SATS internal jumper on JMP-P must be
placed on pins 1 and 2.
DANGER
The following steps in this alternative mode procedure MUST be performed exactly as presented; otherwise,
injury or death and damage to the SATS may result. Please note that with the SATS removed, AC power will
not be available for the trac equipment.
1. If the SATS is currently in operation, the SATS must be removed prior to selecting this alternative
mode. Do not attempt this procedure if the SATS is currently in use. If the SATS in not yet in use,
jump to step 4.
2. Operate the UPS’ DC circuit breaker to the OFF position or disconnect the battery harness from the
UPS.
3. Operate the AC circuit breaker on the UPS to the OFF position.
4. Operate the UPS Input circuit breaker on the SATS to the OFF position.
5. Operate the upstream AC utility line circuit breaker to the OFF position.
6. Remove all wiring attached to the SATS and disconnect power harness from the UPS.
7. With the SATS removed, remove the top 8 screws from the top cover and the 2 top screws on the
face plate.
8. Place the jumper on JMP-P to pins 1 and 2 for Alternative Mode.
9. Replace the top cover of the SATS and reinstall the SATS into the cabinet as shown in Section 4.
10. Perform the startup procedure in Section 5.
PIN 1

15
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Safety Automatic Transfer Switch Shutdown
Section 6: Safety Automatic Transfer Switch Shutdown
If SATS shutdown becomes necessary at any time, observe the following procedure:
1. Operate the upstream AC utility input circuit breaker servicing the enclosure to the OFF position.
2. Operate the UPS’ DC and AC breakers to the OFF position and disconnect the battery harness.
3. Operate the UPS Input circuit breaker on the SATS to the OFF position.
4. If a generator is in use, disconnect the generator from the outside cabinet generator connector.
Replacement Parts
Section 7: Replacement Parts
If parts become damaged or lost during operation, replacement parts are available from Multilink.
535-037-10: 7-position terminal block plug.
540-020-10: 2-position jumper .025sq post for JMP-P, JMP-G, and JMP-M.
870-242-20: Power harness for EDP series UPS.
870-252-20: Power harness for Universal/Line Interactive UPS.
Fuses: F1: 1/2 Amp, Fast-Blow, Cartridge Style, 5mm x 20mm.
F2, F3, F4: 2 Amp, Fast-Blow, Cartridge Style, 5mm x 20mm.
F5, F6, F7: 1 Amp, Slow-Blow, Cartridge Style, 5mm x 20mm.
F8: 6 Amp, Fast-Blow Cartridge Style, 5mm x 20mm.

16
© Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
Troubleshooting
Section 8: Troubleshooting
This troubleshooting guide has been designed to help you quickly locate and resolve common powering
problems. The table assumes normal operation and conguration of the SATS at any given time. If you still
cannot solve the problem, replace the SATS with a known, functional unit.
CAUTION
There are various fuses inside the SATS to protect against over current conditions. These items are not
eld-serviceable. The enclosure cover shall not be removed while in operation. Repair must be done by
certied technicians. Additionally, when replacing the SATS when in use at a live intersection, use of law
enforcement may be required to direct trac during maintenance.
Operating Conditions Corrective Actions
No output voltage to load • Verify wiring is correct to all SATS terminal strips. Tighten contacts.
• Verify the upstream AC utility line circuit breaker to CLOSED.
• Verify the UPS Input circuit breaker is closed, and voltage is available at
the input of the UPS.
• Verify the UPS is operating in Line mode, otherwise, inspect UPS for
output alarms or faults.
• Verify AC utility line voltage is present.
• If no audible relay closure is heard when applying AC utility line volt-
age, replace SATS.
Bypass Mode not operational • Verify AC utility line voltage is present.
• Verify the LED illuminates when the switch is placed in Bypass Mode.
• If LED does not illuminate, replace SATS.
No outpute voltage at duplex outlet • Verify the AC utility line circuit breaker to CLOSED.
• Verify AC utility line voltage is present.
• F8, 6Amp fuse failure. Replace fuse with 6Amp fuse.
No output voltage with Generator • Verify wiring to the SATS GEN terminal strip is correct. Tighten contacts.
• Verify switch is in AUTO Mode.
• Verify generator AC output voltage is present.
MAINS/GEN Sense relays not reporting • F2, F3 open. Replace fuses.

17
© Multilink Inc. 2020 •All Rights Reserved © Multilink Inc. 2020 •All Rights Reserved
Multilink Inc. 580 Ternes Ln. | Elyria,OH 44035 | 440.366.6966 | www.gomultilink.com
SATS Specications
Section 9: SATS Specications
Specications for the Safety Automatic Transfer Switch are listed below.
Parameter Specications Notes
Output Capacity 2kW Continuous Load
Cooling System Convection
Operating Temperature -37°C - + 74°C Output capacity de-rated to 1.6kW between
55-74°C
Mechanical (W x H x D) 19” x 3.5” x 10” 2-RU Rack Mount
AC Input
Connection Terminal Blocks 7.0 Lbf-in mas
Phase Single Phase 3-wire
Voltage 120VAC Nominal 55V to 155V
< 1.0VAC Back-feed voltage
Frequency 60Hz ±5%
Input Power Factor 0.98-1.0 Load dependent
Power Consumption 3W Power source dependent
AC Output
Output Power Connection Terminal Block 7.0 Lbf-in max
Phases Single phase 3-wire
Voltage 120VAC Nominal When UPS is activated
Voltage Regulation Rated Voltage ±5% ±15% with Generator
Current Capacity 16.67A @ 120VAC
Rated Frequency 60Hz
Voltage Waveform Sine Wave Regulated by UPS, when used.
Transient Voltage
Variation
Rapid Load Change
Rated Voltage ±5%
0% ↔100% at transient or output switch
Power Outage Recovery At rated output
Rapid Input Voltage Charge ±15% variation
Transfer Time 5 Cycles or less
Typically, 5-10ms when using Bypass switch
in either mode. Approx. 55ms with abrupt
power disruption between generator and
utility power.
Load Power Factor 0.7-1.0 Variation range 0.7 to 1.0 dependent on AC
source
Over Current Protection 20A UPS Input Circuit Breaker
and Internal Fuses High impedance magnetic breaker.
Fuses are replaceable
Overload Capability 150% 0.05 seconds or rated circuit breaker release
time or UPS overload conditions handling.
Transfer Relays
Output Transfer Relay 30A/277VAC
MAINS/GEN Power Relay 30A/277VAC Open frame
Dry Contact Sense Relays
Switching Power 60W
Minimum contact rating:
10mVdc, 10μA.
5.0 Lbf-in max
Switching Voltage 12VDC
Max Switching Current 5A
Carrying Current 2A

youtube.com/GoMultilink
Document No. SATS
INSTALL AND OPERATION
Copyright © 2020 Multilink Inc. • All rights reserved • Specifications subject to change without notice • Rev. March 25, 2020 11:46 AM
Page 18
Contact Us |
North America
Tel: +1 440 366 6966
Fax: +1 440 366 6802
Email: engsupport@gomultilink.com
Tel: +1 440 366 6966
Fax: +1 440 366 6802
Email: engsupport@gomultilink.com
Tel: +1 440 366 6966
Mobile: +1 440 366 6802
Email: lasupport@gomultilink.com
Europe, Middle East & Africa Latin & South America
Visit gomultilink.com for new product releases!
Multilink, Inc
580 Ternes Ln
Elyria, OH 44035
Tel: (440) 366-6966
Fax: (440) 366-6802
Scan
QR for
website.
facebook.com/GoMultilink1 twitter.com/GoMultilink
This manual suits for next models
1
Table of contents
Other Multilink Switch manuals
Popular Switch manuals by other brands

TSI Instruments
TSI Instruments 8694 Installation instructions & owner's manual

Flaming River
Flaming River FR1003 installation instructions

BD Sensors
BD Sensors DM 200 Mounting instructions

SMC Networks
SMC Networks IS3000-02 Installation and maintenance manual

Cisco
Cisco CGS 2520 Hardware installation guide

ATEN
ATEN CL5808 Specifications