
Page 9
HOW TO LOCATE CHIMNEY EXIT, AND INSTALLATION
Residential Installation, and Alcove: Vertical Exit using (6" Single Wall minimum 24 ga. blued or
black pipe, or 6” DVL Close Clearance pipe and any Listed 2100° UL 103 HT. chimney). With and, without
close clearance shields.
SECTION’S:
A.
Vertical Exit 6" Single Wall minimum 24 ga. blued or black pipe
without close clearance shields.
NOTE:
For minimum clearances (See Page 10, Figure 2)
B.
Vertical Exit 6" Single Wall minimum 24 ga. blued or black pipe
with close clearance shields.
NOTE:
For minimum clearances (See Page 11, Figure 4)
C.
Vertical Exit 6” DVL Close Clearance pipe
with close clearance shields.
NOTE:
For minimum clearances (See Page 12, Figure 6)
D. Vertical Alcove Exit 6” DVL Close Clearance pipe
with close clearance shields
NOTE:
For minimum clearances (See Page 13, Figure 8)
1
.
Suspend a plumb bob from the ceiling above the unit so that the weight is hanging in the center of the flue exit.
(A small weight on a string will serve as a plumb bob.) Mark the ceiling where the string is suspended to locate
the center of the chimney.
2. After locating the center of the hole, install the ceiling support box, chimney or chimney connector, flashing, and
rain cap per the chimney manufacturer’s instructions, and local building codes for installation through
combustible walls or ceilings.
3. Now connect the stove and ceiling support box
(See Page 10, Figure 3)
using
6" Single Wall minimum 24 ga. blued
or black
pipe (DO NOT USE GALVANIZED PIPE). Connect each section so the crimped end faces downward,
and secure each section to each other using at least three (3) sheet metal screws or rivets. Single wall pipe is to
be connected with (3) sheet metal screws or rivets to connector collar on heater.
(See Page 22, Figure 25).
Residential Installation: Vertical Wall Exit using (6"SingleWall minimum24 ga.bluedorblack pipe,
or 6” DVL Close Clearance pipewith elbow, and any Listed 2100° UL HT chimney and Listed 2100° UL HT.
T-Box assembly). With and, without close clearance shields.
E.
Vertical Wall Exit To Masonry Chimney Through combustible Wall - Using (SECTIONS F. and G.)
(See Page 14)
F. Vertical Wall Exit 6" Single Wall minimum 24ga. blued or black pipe
without close clearance shields.
NOTE:
For minimum clearances (See Page 17, Figure 14)
G. Vertical Wall Exit 6" Single Wall minimum 24ga. blued or black pipe
with close clearance shields.
NOTE
: For minimum clearances (See Page 18, Figure 16)
H. Vertical Wall Exit 6” DVL Close Clearance pipe
with close clearance shields.
NOTE
: For minimum clearances (See Page 19, Figure 18)
1. Mark the plumb line on the wall directly behind the center of the heater. (See Page 17, Figure 15).
NOTE: When using 6" Single Wall minimum 24ga. blued or black pipe,“ maintain 18" minimum
clearances" between pipe and ceiling ”.
2. Place the vertical portion of the heater pipe and the elbow in position and project a point onto the plumb
line level with the center of the elbow.
3. Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe, maintaining clearances to
the ceiling as noted in (Page 17,Figure 15). This will give you the center of the hole for the chimney
penetration.
4. After locating the center of the penetration, install the tee-box and chimney as per the chimney
manufacturer's specifications.
5. Connect the chimney collar to the tee-box using
6" Single Wall minimum 24 ga. Blued or black pipe
.
(DO NOT USE GALVANIZED PIPE). Connect each section so the crimped end faces downward,
and secure each section to each other using three (3) sheet metal screws or rivets. Single wall pipe is to be
connected with three (3) sheet metal screws rivets to connector collar on heater.
(See Page 22, Figure 25).