Newasia Motor Protector Series User manual

1
Motor Protector Series Operating Instruction (V1.0)
(NA704L、NA708L、NA712L)
Main Functions
Current display:display three average current, press key to display A、B、C phase current
respectively.
Underload protecting:when three phase average current lower then setting current, circuit
protects and load opens.
Overload protecting: when three phase average current exceed rated current, circuit protects and
load opens.
Deficient-phase protecting:when testing deficient-phase or three phase current unbalance, circuit
protects and load opens.
Auto reset: when circuit protects and load opens, can set “reset automatically” degree and time,
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset
manually.
¤Main Technique Index
Current display range: 0~50A (NA704L),0~100A (NA708L),
0~120A (NA712L),precision ±2%
Rating current range:
Sort
Min(A)
Max(A)
NA704L
1.0
40.0
NA708L
2
80
NA712L
2
120
Underload protect action time: 0.5~30s (adjustable)
Overload protect action time: 0.5~30s (adjustable)
deficient-phase protect action time: 0.5~30s (adjustable)
Power supply:AC 220V±10%)
Operating environment: temperature -10℃~45℃,humidity≤85%.
Relay contact capability: 2A/250VAC (pure resistive load)
Executive standard: Q/320585 XYK 03
Operating Guide
The meaning of the LED:
LED
light
flash
phase A
Display the current of phase A
-
A、B、C LED no light means
display three phase average
current
phase B
Display the current of phase B
-
phase C
Display the current of phase C
-
Alarm
Circuit protecting, Load
opens
Circuit protects ever, but
already reset automatically
The meaning of the nixietube display:
In normal, controller displays three phase average current(unit:A), press “SEL()”, then display
A、B、C phase current respectively. In the alarm state, it displays alarm code.
Alarm codes:
Code
Meaning
Explanation
OL. overflow Current exceed measure range(NA704L measure range 50A,
NA708L measure range 100A, NA712L measure range 140A)
LAC
underload
Load current lower than setting current
OVL overload Load current exceed rated current
PHA deficient-phase
Deficient-phase or three phase current unbalance
How to displayA、B、C phase current?
Press “SEL()”then display A、B、C phase current respectively, the correspond LED lights. If
A、B、C three LED is unlighted, mean that controller display three average current.
How to reset from the alarm state?
When overload or deficient-phase protection occurs, alarm LED lights, and protection circuit
activates, the load opens, finally the state of open locks. You can set “reset automatically” degree and time,
after some time, switch on load again, if circuit still has malfunction, try several times, then must reset
manually. In any time, if press “RST()”, reset from the alarm state.
How to set the parameter?

2
The Micro-controller can change the parameter, in order to fit different needs. Using the password can
enter into the menu, password is “up down up down up up down”, according to this gradation, in normal
temperature state ,press “” “” during 3 seconds, if the password is right, the screen displays “Fxx”,
“xx” is two numbers, means parameter’s code.
Press “”or“”for choosing parameter’s code, press “”“” at the same time for confirming, then
press “”or“”in order to changing the parameter, when the parameters have been adjusted ,press “”
“”to confirm.(after adjusted the parameter ,press“” “” to return to “Fxx” synchronously, the
adjusted parameter is saved.)
Another way is that press “”“” simultaneously at least 5 seconds, then also enter into parameter
setting.
Parameter code is showing below:
Sort Code Parameter Name Range Factory
Setting
Unit Remark
Rating
parameter
F10
NA704L
Underload Current:: NA708L
NA712L
1.0 – 40.0
2 – 80
2 – 120
1.0
2
2 A
F11
NA704L
Rated Current:: NA708L
NA712L
1.0 – 40.0
2 – 80
2 – 120
20.0
40
120
A
F12
Overload acts time
0.5 – 30.0
3.0
sec
F13
Deficient-phase acts time
0.5 – 30.0
2.0
sec
F14 Underload acts time
OFF
1 -- 30
OFF min
OFFmeans no underload
function
Reset
automatically
F21
Reset automatically degree
0 -- 10
1
degree
0 means no “Auto Reset”
F22 Reset automatically time 1 -- 60 5 min
F00
Exit the parameter setting
-
Basic Operating Principle
Current Testing
Through mutual inductor tests load current, the motor’s three phase wire must be through mutual
inductor’s three holes.
Underload protection
when three phase average current lower then setting current (parameter F10), also reach the
“Underload acts time” (parameter F14), circuit protects and load opens.
Overload protection
When three phase average current exceeds rated current (parameter F11), also reach the “Overload
acts time” (parameter F12), circuit protects and load opens. In order to prevent the motor startup current,
“Overload acts time” must be longer than motor startup time.
Deficient-phase protection
Testing the load current, When the maximum current of the three phase is double than the minimum,
controller considers deficient-phase, circuit protects and load opens. But if the load current is less than
0.5A(NA704L)or 1A(NA708L/712L), controller don’t test phase, in order to prevent the error action in
the no load state.
“Deficient-phase acts time” can be adjustable through parameter F12.
Reset automatically
After circuit protects and load opens, controller can set reset automatically degree (parameter F21)
and time (parameter F22).
Wiring Diagram:
NA704L NA708L NA712L
Notice:
1. The earth terminal of the controller should be connected with the earth terminal of the electric
cabinet reliably,be sure to connect the earth well.
2. Please use mutual inductor which are supplied by our company.
This manual suits for next models
3
Table of contents
Popular Protection Device manuals by other brands

Tsubaki
Tsubaki SHOCK RELAY TSBSA Series instruction manual

KELCO
KELCO IPG20 Mk2 Installation & programming manual

Segen Solar
Segen Solar ACDB-250A-1000A-4-1-1 installation manual

COVANA
COVANA Evolution installation manual

MULTISPAN
MULTISPAN MPD-152 quick start guide

THORLABS
THORLABS IO-F-SLD100-1064 user guide