Nittan CPC-4A Instruction Manual

January, 2020
54-5, 1-CHOME, SASAZUKA SHIBUYA-KU, TOKYO 151-8535 JAPAN
TEL 03-5333-7021 (Overseas Business Department)
We highly appreciate your purchasing of NITTAN product.
Before operation, please read this “Operating Instruction Manual” and use the equipment in proper manner.
Smoke Detector Control Panel (CPC-4A)
Operating Instruction Manual
AC 100V
-
240V Specification

- 1 -
1. Product
The Smoke Detector Control Panel is a fire detection system to be used by connecting with a designated smoke detector (0KB3).
When fire breaks out, the panel receives fire signal from smoke detector and indicates operating smoke detector address and
starts to sound buzzer alarm. Signal transfer function of non-voltage c contact is equipped with the panel. Also, the panel detects
smoke detector abnormality (sensitivity calibration limit and non-response) by regular self -diagnosis function.
2. For your safe and proper use
This instruction manual contains various symbols indicating precautions in order to prevent safety hazard to our clients and
other public as well as damages to properties. Please read the text after you have understood the symbols.
There is a risk of endangering the health or life of the user, or causing a
significant damage to the equipment when the product is mishandled.
MUST
PROHIBITED
Mandatory Action or Instruction
There is a risk of causing minor injuries or damage to the equipment when the
product is mishandled.
Action prohibited
WARNING
CAUTION
DANGER
In case of improper handling, dangerous condition is anticipated where death
or serious injury to operating personnel may be caused and an emergency
warning is urgently required when any danger occurs.
MUST
Ensure that AC power supply is switched off before starting wiring, and connection is made properly.
Otherwise it may cause electric shock.
DANGER

- 2 -
ENSURE TO
COMPLY
PROHIBITED
● Do not touch the equipment with wet hands or dip into water or splash water over the equipment.
It may cause electrification or trouble.
● Do not overhaul or modify equipment.
It may cause electrification and trouble.
● Do not use the equipment in location where operating temperature exceeds its range (0-
60°C) and
where explosive gas or corrosive gas is generated.
It may cause the equipment trouble or fire ignition.
● Do not put anything into the openings.
It may cause the equipment trouble or fire.
● The installation work on AC power must be performed by a qualified person.
● Please ensure that the terminal cover of AC power supply is attached properly after completion of
work. Otherwise it may cause electric shock.
● Wire connection to each terminal should be properly carried out in accordance with specified rating
and polarity. Incorrect wiring may cause trouble or fire.
● Carry out sufficient
checking of operating condition of interlocking devices in case of test operation.
Improper operation may cause damages to the equipment or cause danger to personnel.
● The equipment is for indoor use only. Do not install it outside.
It may cause malfunction.
WARNING
● Please make sure wiring to smoke detector as two-wire connecting arrangement. (Do not connect
end-of-line resistor to end of detector line.)
● Maximum number of smoke detectors to be connected is 20. (Only 0KB3 can be connected but old model
0KB and
0IB cannot be connected.)
● Smoke detector connection terminals (L+ and C-) have polarity.
● Please use shield wire for wiring in electromagnetic disturbing environment
● This equipment cannot be connected to detectors in automatic fire alarm system.
● The Smoke Detector Control Panel is operated in normal monitoring mode [Normal] or in setting mode [AD Set
],
by confirming [Mode SW] condition at initial time (power supply switch on time or reset operation time).
Please
set to normal monitoring mode [Normal] at monitoring time and setting completion time.
If initial operation (power supply switch on or reset operation) is carried out by setting mode [AD Set
] side, fire
cannot be detected since system operates by setting mode.
● Make sure to check the equipment by activating smoke detectors.
CAUTION
Connect
earth wire
●
Make sure to connect
an
earth wire.
Otherwise it may cause electric shock during the use
of
equipment or in the event of electric leakage.

- 3 -
3. Name of each section
(Indication /Operation)
(Terminal)
⑫
⑭
⑱
⑰
⑯
⑬
⑮
U
nused
U
nused
U
nused
① Mode SW (mode switch)
At normal monitoring time: set to [Normal] (assigned) side.
At address setting time: set to [AD Set] (address setting) side.
② Up (increment switch)
③ Down (decrement switch)
When 2 or more alarms sound, digital indication can be scrolled.
④ Sensor Address/Err. Code (detector address/error code)
To indicate digitally smoke detector address or error code.
⑤ Silence (audible sound stop switch)
To stop alarm sound of the Smoke Detector Control Panel.
⑥ Fault (trouble light: yellow)
To turn on at smoke detector line (L+, C-) fault/short circuit,
at smoke detector detachment and at smoke detector trouble time.
Fault is not latched at automatic reset.
⑦ Fire Alarm (fire light: red)
To turn on when 2 or more smoke detectors operate.
It remains ON until pressing Reset.
⑧ Detector Operated (1 detector operation light: red)
To turn on when 1 or more smoke detector operates.
It remains ON until pressing Reset.
⑨ Reset (reset switch)
To reset fire indication of operated smoke detector and the
Control Panel.
⑩ Power Indication (power supply light: green)
To turn on when [Power SW] (power supply switch) is switched on
at power supply time.
⑪ Power SW (power supply switch)
⑫ Earth Terminal
⑬ Detector Operated (1 detector operation signal transfer terminal:
no-voltage c contact).
⑭ Fire Alarm (fire signal transfer terminal: no-voltage c contact).
⑮ L+, C- (detector line connecting terminal).
⑯ AC 100V~240V Power-Line (power supply input terminal).
⑰ Fault (trouble signal transfer terminal: no voltage c contact).
⑱ R+, R- (reset input terminal).
Terminal to input reset signal when reset operation is carried out
externally.
* Please use round crimp terminal with insulation coating (RAV1.25-3)
when connecting wire to terminal block.
①
②
③
④
⑨
⑩
⑤
⑪
⑧
⑦
⑥

- 4 -
4. Digital indication list
● Digital indication at operation time/trouble time
Digital indication
Content of digital
indication
Details
Detector address
●
To indicate smoke detector address when
[Fire
Alarm] (fire light) or [Detector Operated]
(1 detector operation light) turns on.
When 2 or more detectors operate, maximum 5
detector(*) addresses are indicated in order of
operation.
● To indicate all addresses (*) of smoke detectors
which become unable to monitor normally due to
detector line fault, smoke detector detachment and
smoke detector trouble when Fault (trouble light)
turns on.
* When pressing [up] or [down] swit
ch, it scrolls.
Detector line short
circuit ●Indicated when detector line is in short circuit.
Detector connection
number setting error
●
When [Power SW]
(power supply switch) is
switched on, this will be indicated together with
[Fault] (trouble light) turning on. This will be
indicated when detector connection number
registered to the Smoke Detector Control Panel and
actually connected smoke detector address number
(type of address) are different.
● Digital indication at setting mode time
Digital indication
Content of digital
indication
Details
Setting mode of
connecting detector
number
● Mode to register connecting detector number to the
Smoke Detector Control Panel.
Reading mode of
connecting detector
number
● Mode to read connecting detector number to the
Smoke Detector Control Panel.
Setting mode of
detector address ● Mode to register address to smoke detector.
Reading mode of
detector address
● Mode to read address registered to smoke
detector.
Successful setting
●Indicated when registration is properly made by
connecting detector number setting mode or by
detector address setting mode.
Reading error
Writing error
● Indicated when reading or writing are not properly
done.
5. Alarm priority order
There remains a possibility of multiple numbers of alarm sounds.
Even though lower priority alarm has occurred, higher priority alarm is activated first.
~
① Fire Alarm
② Detector Operated (1 detector operation)
③ Fault e
Priority order
H
igh
L
ow
(ok)

- 5 -
6. Operation specification
Condition
Indication Light 7 Seg Indication
Terminal Indication
Buzzer Sound
(*1)
Power
Indication
(green)
Fault
(yellow)
Detector
Operated
1 detector
Operation
(red)
Fire
Alarm
(red)
Sensor
Address/
Err Code
Detector
address/code
Fault
Detector
Operated
1 detector
operation
Fire
Alarm
9-11
10-11
1-3 2-3 4-6 5-6
At monitoring
time ○ - - - - OPEN
CLOSE
CLOSE
OPEN
CLOSE
OPEN
At power cut time
- - - - - CLOSE
OPEN
CLOSE
OPEN
CLOSE
OPEN
-
Detector wire line
fault
○ ○ - -
[01~20]
Address
Indication
(*2)
CLOSE
OPEN
CLOSE
OPEN
CLOSE
OPEN
intermittent
sound B
Detector wire
short circuit [E1]
Detector
ommision
[01~20]
Address
Indication
(*3)
Detector
connection
number setting
error
[- -]
Trouble detector
detection by
regular
self-diagnosis
function
○ ○ - - [01~20] address
indication CLOSE
OPEN
CLOSE
OPEN
CLOSE
OPEN
intermittent
sound A
1 detector
operation ○ - ○ - [01~20] address
indication OPEN
CLOSE
OPEN
CLOSE
CLOSE
OPEN
intermittent
sound C
fire (more than 2
detectors
operation)
○ - ○ ○ [01~20] address
indication (*4)
OPEN
CLOSE
OPEN
CLOSE
OPEN
CLOSE
continuous
sound
* 1 Intermittent sound A: cycle 0.15Hz(bi- - - -tu, bi- - - -tu, bi- - - -tu), Intermittent sound
B: cycle 0.5Hz(bi- -tu, bi- -tu, bi- -tu), Intermittent sound
C: cycle 5Hz (bi-tu, bi-tu, bi-tu)
* 2 To indicate all addresses of smoke detectors which become unable to normal monitor by detector line fault.
When [up] or [down] switch is pressed, digital indication scrolls.
* 3 To indicate all addresses ofsmoke detectos which become unable to normal monitor by detector ommission.
When [up] or [down] switch is pressed, digital indication scrolls.
* 4 To indicate max. 5 smoke detector addresses in operation order when 2 or more smoke detectors operate.
When [up] or [down] switch is pressed, digital indication scrolls.

- 6 -
7. Overall connecting diagram
Smoke Detector
Control Panel
(CPC-4A)
Power-Line
Fault
Detector
Operated Fire Alarm
Above D Type (Class C) earth
or equivalent (below 100Ω)
Power supply input
(AC100V-240V)
L
Smoke detector
(0KB3)
C
P
L
Smoke detector
(0KB3)
C
P
C
-
L+
11
10
2
3
1
5
6
4
R+
R
-
External reset switch (momentary type)
(pulse signal over 500msec)
* 1 It is recommended to use either AE cable or CPEV cable with conductor diameter over 0.65mm.
It is recommended to use shielded CPEV-S cable where electromagnetic noise causes disturbance.
Connect the shielded part of cable to the earth terminal.
* 2 After connection, please operate the detectors and confirm that the Smoke Detector Control Panel will
reset from operating condition to normal monitoring condition by external reset switch input.
No
-voltage c contact: indication of device board shows condition at monitoring time (at power supply time).
Detector line *1
* Do not connect end-of-line
resistor to end of detector line.
9
External reset switch input line *2
MUST
● Ensure that AC power supply is switched off before starting wiring, and connection is made properly.
Otherwise it may cause electric shock.
In case of improper work or incorrect connection method, electrification possibility may remain.
DANGER

- 7 -
8. Setting of the number of detectors connected
To register smoke detector number to be connected to the Smoke Detector Control Panel.
① Switch off [Power SW] (power supply).
② Switch on [Power SW] (power supply) by setting [Mode SW] (mode switch) to [AD Set] (address setting) side.
③ [SO] is indicated digitally.
④ Set to [connecting detector number setting mode].
Select [SO] and push [Silence] (audible sound stop switch).
● The number of connected detectors registered to the Smoke Detector Control Panel is 2
at the time of factory
shipment. Please register actual number of smoke detectors (0KB3) to be connected.
The registered number of connected detector is
stored in the Smoke Detector Control Panel. Even when power
supply is off, the stored registration will not be erased.
When registered number in the Smoke Detector Control Panel and the number of
connecting detector address
(address type) do not correspond, smoke detector connecting number setting error appears.
Power SW
Every time [Reset] (reset switch) is pressed, digital indication changes.
Power SW
CAUTION

- 8 -
⑤ [01] is indicated digitally. Indicate detector number to be connected to the Smoke Detector Control Panel by
pressing [up] (increment switch) or [down] (decrement switch). (Connecting detector number can be
registered up to [01~20].)
⑥ Register connecting detector number by pressing [Silence] (audible sound stop switch).
When [ ] (ok: setting succeed) is indicated, registration is completed. (About 3 seconds later,
indication will reset automatically and return to ③ condition.)
⑦ Confirm registered connecting detector number by setting to [connecting detector number reading
mode]. Push [Reset] (reset switch) and indicate [S1] and push [Silence] (audible sound stop switch).
Registered connecting detector number is indicated digitally. (About 3 seconds later, indication will
reset automatically and return to ③ condition.)
⑧ When registration is completd, release setting mode.
Switch off [Power SW] (power supply) and set [Mode SW] (mode switch) to [Normal] (assigned) side
and switch on [power SW] (power supply), then setting mode is released and returns to normal
monitoring mode.
● Please make sure to return to normal monitoring mode after completion of setting detector connecting number.
Otherwise the system becomes unable to detect fire and unable to operate properly.
・・・
(o k)
Example: when 2 connecting
detector numbers are set.
Power SW
Power SW
CAUTION

- 9 -
9. Smoke detector address setting
To register smoke detector address to be connected to this the Smoke Detector Control Panel.
Smoke detector (0KB3) is registered as 01 address at the time of factory shipment.
① Switch off [Power SW] (power supply) and connect the Smoke Detector Control Panel with smoke detector one for one.
② Switch on [Power SW] (power supply) by setting [Mode SW] (mode switch) to [AD Set] (address setting) side.
③ When [SO] is indicated digitally, set to [Address Setting Mode]. Push [Reset] (reset switch) and indicate [AO]
and push [silence] (audible sound stop switch).
● Please make sure to register smoke detectors with non-overlapping address (1-20).
The Smoke Detector Control Panel
is unable to detect overlapping addresses. Unless properly registered, connecting
detector number error message may be indicated.
The registered address is stored in smoke detector. Even when power supply is off, the registration will not be erased.
● When setting address, please make sure to connect smoke detector control panel and smoke detector (0KB3) one for
one.
When multiple numbers of smoke detectors are connected, they may be registered with the same address or writing
error may be indicated.
Smoke Detector Control Panel
(CPC-4A)
L
Smoke Detector
(0KB3)
C
P
C
-
L+
Power SW
Power SW
CAUTION

- 10 -
④ [01] is indicated digitally. Indicate the address of smoke detector to be registered, by pressing [up] (increment switch)
or [down] (decrement switch). (Address can be registered up to [01~20].)
* Please set address number from [01] upward in series for easy management.
⑤ Register address by pressing [Silence] (audible sound stop switch).
When [ ] (ok: setting suceed) is indicated digitally, registration is compledted. (About 3 seconds later, indication
will automatically reset and return to ③ condition.
*Please enter the registered address into the available space of the product label attached to the back of the smoke
detector, in order to identify the address.
⑥ Confirm registered address by setting to [Address Reading Mode]. Push [Reset] (reset switch) and indicate [A1] and
push [Silence] (audible sound stop switch), then registered detector address is indicated digitally. (About 3 seconds
later, indication will automatically reset and return to ③ condition.)
* When [- -] is indicated, this means reading error.
When [Reset] (reset switch) is pressed, indication is restored. When reading error is indicated, check wiring and
others,and set again.
Example: When the address is
set at [02].
Detector Back
Smoke
detector
(0KB3)
NITTAN CO.,LTD.
・・・
(ok)
Example: when address
is set as [02]

- 11 -
⑦ When you wish to continue registration of address to other smoke detector, replace registering smoke detector body
only, and register address to all smoke detectors one by one in line with the above ③~⑥.
⑧ When registration is completed, release setting mode.
Switch off [Power SW] (power supply) and set [Mode SW] (mode switch) to [Normal] (assigned) side.
⑨ Connect the number of smoke detectors registered in the above [8. Setting of detector connection number].
⑩ Return to normal monitoring mode.
When [Power SW] (power supply) is switched on under the condition of [Normal]
(assigned) at [Mode SW] (mode switch), it returns to normal monitoring mode.
● Please make sure to return to normal monitoring mode after completion of setting detector address.
Otherwise the system becomes unable to detect fire and unable to operate properly.
Power SW
Power SW
CAUTION

- 12 -
10. Troubleshooting
If the condition is not rectified after applying the following procedures, please contact the distributor from which you purchased
or NITTAN Co., Ltd.
Condition Cause Corrective Measures
[Power Indication] (power supply
light) is turning off.
Power is not supplied to
[Power-Line] (power
supply input terminal).
Supply power to [Power-Line] (power supply input
terminal).
[Power SW] (power
supply switch) is not ON.
Switch on [Power SW] (power supply switch).
While [Fault] (trouble light) is
turning on and alarm buzzer is
sounding, smoke detector address
[01~20] is indicated digitally.
* Alarm buzzer cycle: 0.5Hz
(bi- -tu, bi- -tu, bi- -tu)
There is a cable break in
the detector line (L+,
C-) .
Repair the cable break.
When repaired, trouble alarm will be self reset.
Smoke detector is
detached.
Connect a smoke detector.
When connected, trouble alarm will be self reset.
While [Fault] (trouble light) is
turning on and alarm buzzer is
sounding, smoke detector address
[01~20] is indicated digitally.
* Alarm buzzer cycle: 0.15Hz
(bi- - - -tu, bi- - - -tu, bi- - - -tu)
Smoke detector is in
trouble.
Replace smoke detector of which address is indicated
digitally.
After replacement, push [Reset] (reset switch) and
system will be reset.
While [Fault] (trouble light) is
turning on and alarm buzzer is
sounding, [E1] is indicated
digitally.
* Alarm buzzer cycle: 0.5Hz
(bi- -tu, bi- -tu, bi- -tu)
Detector line is in short
circuit.
Repair short circuit point.
When repaired, trouble alarm will be self reset.
When [Power SW] (power supply
switch) is switched on,
[- -] is indicated digitally and
[Fault] (trouble light) is turning
on.
* Alarm buzzer cycle: 0.5Hz
(bi- -tu, bi- -tu, bi- -tu)
Detector numbers
registered to the Smoke
Detector Control Panel
and detector address
number (number of
address type) are
different.
Register detector connecting number, by referring to
[8. Setting of detector connection number].
Detectors registered with
the same address are
included in connecting
smoke detectors.
Confirm that smoke detector address is not
overlapping, by referring to [9. Smoke detector
address setting].
Wiring is influenced by
noise from other
equipment.
Replace detector wiring with shield wire.
When only 1 detector is
operating, [Fire Alarm] (fire
light) is turning on.
End-of-line resistor is
connected to wiring. Remove end-of-line resistor.
Even when a detector operates,
address is not indicated digitally.
Old models (0KB, 0IB)
are connected. Connect 0KB3, the address of which is registered.
Wiring is affected by
noise from other
equipment.
Replace detector wiring with shield wire.

- 13 -
11. Product specification
Model Name CPC-4A
Rated Voltage AC 100-240V (±10V), 50/60 Hz
Rated Power Supervisory condition: 1.6VA (AC 100V)/2.8VA (AC 240V)
Alarm condition: 3.2VA (AC 100V)/4.7VA (AC 240V)
Detector Power Voltage Rated DC 19V
Max. No. of Detector 20 Max
External Wire Resistance Below 20ohm (between Control Panel and distal Smoke Detector)
External Reset Switch Input
Line External Wire Resistance
Below 2ohm (between smoke detector control panel and external reset switch)
Connecting Detector 0KB3 (old model 0KB and 0IB are not connectable)
Switch
Power SW (Power Supply Switch) : Latching Type
Reset (Reset Switch) : Momentary Type
Mode SW (Mode Switch) Slide Type
Silence (Audible Sound Stop Switch) : Momentary Type
up (Feed Switch) : Momentary Type
down (Return Switch) : Momentary Type
Indicator Light
Power Indication (Power Supply Light) : Green
Fault (Trouble Light) : Yellow
Fire Alarm (Fire Light) :Red
Detector Operated (One Detector Operation Light) : Red
Sensor Address/Err Code (Detector Address/Code) : 7 Segment LED (Two Digit Indication)
Relay Contact Point
(Non-Voltage C Contact)
Fault , Fire Alarm, Detector Operated
Contact Point Ratings: DC30V, 1A / AC 125V, 0.3A (resistance load)
Audible sound
(electronic buzzer)
Detector line fault/short circuit, detector detachment,
detector connecting number setting error. :intermittent sound (cycle: 0.5Hz)
Trouble detector detection by regular self-diagnosis function. :intermittent sound (cycle: 0.15Hz)
When Detector Operated (One Detector Operation Light) turns on. :intermittent sound (cycle: 5Hz)
When Fire Alarm (Fire Light) turns on. :continuous sound
Function
●Regular self-diagnosis function:
Function to detect trouble by conducting diagnosis on smoke detector at power switch on time and
at every 6 hours after power switch on.
● Line fault/short circuit monitoring function:
Function to constantly monitor detector line fault/short circuit.
● Detector omission monitoring function:
Function to constantly monitor smoke detector omission.
● Address indication function:
Function to indicate address of operated or troubled detector.
● External reset function:
Function to oconduct reset operation externally by input of pulse signal of over 500msec to fire
control device terminal (R+, R-).
● Power supply cut signal trasnfer function:
Function to transfer trouble signal from fire control device terminal (9, 10, 11) at power supply cut
time.
● Address setting function:
Function to set address to smoke detector.
Recommend cable(over
0.65mm conductive diameter)
Polyethelene insulation cable (AE cable) for alarm
Polyethelene insulation vinyl sheath cable (with shield) (CPEV-S cable)
Material
Body: aluminium (alumite treatment)
Cover: steel sheet (trivalent chrome chemical conversion treatment)
Screw: iron and steel (trivalent chrome chemical conversion treatment)
Mounting bracket (separate purchase): steel sheet (trivalent chrome chemical conversion treatment)
Outside Dimension W 110mm x H 40mm x D 195mm (body only)
Weight about 560g (body only)
Operating Environment Temperature: 0ºC to +60ºC, Humidity: below 85% RH ( non-condensation)
Storage Temperature Range
-20ºC to +70ºC
RoHS directive Complied
Safety standard ETL approved (UL STD 61010-1 Third Edition/Recognized Component)
Insulation characteristics: Pollution degree 2, overvoltage category Ⅱ
Mounting to use mounting bracket (separate purchase)