Nittan EL.MO. Spa MCMAS5 User manual

MCMAS5 - TECHNICAL MANUAL - 090010924
2
FOREWORD
FOR THE INSTALLER:
Please follow carefully the specifications relative to electric and security systems realization further to the manufacturer’s
prescriptions indicated in the manual provided.
Provide the user the necessary indication for use and system’s limitations, specifying that there exist precise specifications and
different safety performances levels that should be proportioned to the user needs. Have the user view the directions indicated
in this document.
FOR THE USER:
Periodically check carefully the system functionality making sure all enabling and disabling operations were made correctly.
Have skilled personnel make the periodic system’s maintenance. Contact the installer to verify correct system operation in case
its conditions have changed (e.g.: variations in the areas to protect due to extension, change of the access modes, etc…)
-------------------------------
This device has been projected, assembled and tested with the maximum care, adopting control procedures in accordance with
the laws in force. The full correspondence to the functional characteristics is given exclusively when it is used for the purpose it
was projected for, which is as follows:
Conventional detectors input module for AS protocol loop.
Any use other than the one mentioned above has not been forecasted and therefore it is not possible to guarantee the correct
functioning of the device. Similarly, any other use of this technical manual other than the one it has been compiled for — that is:
to illustrate the devices technical features and operating mode - is expressly prohibited.
The manufacturing process is carefully controlled in order to prevent defaults and bad functioning. Nevertheless, an extremely low
percentage of the components used is subjected to faults just as any other electronic or mechanic product. As this item is meant
to protect both property and people, we invite the user to proportion the level of protection that the system offers to the actual risk
(also taking into account the possibility that the system was operated in a degraded manner because of faults and the like), as
well reminding that there are precise laws for the design and assemblage of the systems destinated to these kind of applications.
The system’s operator is hereby advised to see regularly to the periodic maintenance of the system, at least in accordance
with the provisions of current legislation, as well as to carry out checks on the correct running of said system on as regular
a basis as the risk involved requires, with particular reference to the control unit, sensors, sounders, dialer(s) and any other
device connected. The user must let the installer know how well the system seems to be operating, based on the results of
periodic checks, without delay.
Design, installation and servicing of systems which include this product, should be made by skilled staff with the necessary
knowledge to operate in safe conditions in order to prevent accidents. These systems’ installation must be made in accordance
with the laws in force. Some equipment’s inner parts are connected to electric main and therefore electrocution may occur
if servicing was made before switching off the main and emergency power. Some products incorporate rechargeable or non
rechargeable batteries as emergency power supply. Their wrong connection may damage the product, properties and the
operator’s safety (burst and fire).
According to Directive 2012/19/EU on the Waste of Electric and Electronic Equipment
(WEEE), it is here specied that this Electrical-Electromechanic Device started to be
commercialized after 13th August 2005, and it shall be disposed of separately from or-
dinary waste products.
DISPOSAL INSTRUCTIONS
www.acornfiresecurity.com
www.acornfiresecurity.com

090010924 - TECHNICAL MANUAL - MCMAS5
3
1. GENERAL
EL.MO.’s MCMAS5 is the new conventional detectors input module for AS protocol analogic loop systems.
Born from the experience and from the studies of our R&D team, it can boast several strengths:
• Easy to install. Easier wirings thanks to the removable terminal board;
• Compact. Compatible with optional 503 flush mount box;
• Versatile. Can be powered up from an external power supply unit or directly from the loop;
• Suitable for power group monitoring. Where there is no dedicated serial line for monitoring power supply units directly from
a control unit, MCMAS5 can monitor the fault status of the PSU through a LED and by bouncing the alarm to the control unit.
Since the fault is signalled by lack of power on the fault line, any line interruption is treated as a fault as well.
2. TECHNICAL SPECIFICATIONS
Model: MCMAS5
Protection class: IP3X
Power supply: 24 VDC
Operating voltage: 20.5 VDC to 27.5 VDC
Power consumption (with a single
detector):
idle: 6.2 mA from 24 V PSU and 12.5 mA from the loop, or 18.5 mA from the loop
alarm mode: 26 mA from 24 V PSU and 13.5 mA from the loop, or 37.5 mA from the loop
Connections: terminals for: loop connection, 1 relay output, 1 power supply input, 1 power supply unit
monitoring input and 1 conventional detectors line input.
LED indicators: power supply unit fault LED, polling indicator LED, detectors line fault and relay activation LED
Controls: rotary dip switches to set ID address
jumpers to set operating functions and power supply source
Relay contacts carrying capacity: 0.5 A @ 125 VAC; 2 A @ 30 VDC
Operating temperature: −10 to +55 °C — 93% r.h.
Weight: 61 g
Dimensions: W 91.6 × H 54.7 × D 23 mm
Distanc between centers: W 83 mm
Parts supplied: technical manual, balancing resistor (1 × 3650 Ω), alarm resistor (1 × 560 Ω)
3. PRODUCT COMPLIANCE
Install the conventional detectors input module MCMAS5 as an accessory of compatible and CE compliant control units only.
Also see the Declaration of Conformity at the end of this manual, or download it from the www.elmospa.com website.
4. INSTALLATION
Install MCMAS5 on AS protocol loops only.
WARNING: in order to avoid false alarms or electronic components damage, make sure panel and
loop are disconnected from power during wiring, installation and maintenance operations.
4.1 Overview and wiring diagram
Wire as shown in pic. 1. Diagrams labeled b, c, d and e show tipical wiring examples for some different kind of commonly used
detectors: follow the wiring instructions on your detectors’ technical manual.
Detectors’ line needs a 3650 Ω end of line resistor (included) which is to be installed inside the casing of the last detector of the line.
For further data on how and when to wire supply line terminals, see section 4.4 Jumpers settings.
www.acornfiresecurity.com
www.acornfiresecurity.com

MCMAS5 - TECHNICAL MANUAL - 090010924
4
Power supply unit,
if present
Terminal board
AS Protocol loop.
Connect the cable
shields togheter.
Rotary switches
Pins
PSU fault output
(drop-out alarm relay)
Reset button
Jumpers
Relay commanded
devices, if present
+24 VDC
Detector line:
refer to the following
diagrams
DC
Connect the screen
to an insulated
terminal
MCMAS5
L C
Optional external
alarm repeater
3÷20 mA @ 24 V
Every base of the line but the last
Optional external
alarm repeater
3÷20 mA @ 24 V
Last base of the line
EOL resistor
3650 Ω1% ¼ W
3K65 Ω
+
−+
−
+
−
Connect to the
loop cable shield
a)
b)
Pic. 1a – Overview and wiring diagram
Pic. 1b – Sample wiring for UB6 bases
Pic. 1c – Sample wiring for a linear smoke detector (external power supply)
(Loop wired as in pic. 1a)
560 Ω, ¼ W
3650 Ω, 1%, ¼ W
(Monitored)
power supply unit
Fault
relay
Alarm
relay
Linear smoke detector
Connect to the loop
cable shield
c)
www.acornfiresecurity.com
www.acornfiresecurity.com

090010924 - TECHNICAL MANUAL - MCMAS5
5
Pic. 1d – Sample wiring for a linear smoke detector (power supplied by the loop)
Pic. 1e – Sample wiring for a glassbreak call point line
4.2 Unplugging and plugging back the terminal board
In order to clip the wires without holding the whole box in your hand, the terminal board
can be detached.
To unplug the terminal board:
• Insert the point of a small screwdriver between the green plasic block of the
terminal board and the white plastic of the bottom side of the box;
• Gently lever over the whole lenght of the board to make it raise in the arrow’s
direction (pic. 2);
• Pull the board out in the arrow’s direction.
To plug the terminal board back:
• Align the holes on the terminal board’s back with the pins;
• Slide back the board, pushing it as far as possible towards the box.
4.3 Serial address programming
Every module on the loop has a unique ID between 1 and 254.
• Set the address by maneuvering the rotary switches labeled ×100 (hundreds), ×10 (tens), and ×1 (units) on the front of
the box.
Pic. 2 —Detachable terminal board
560 Ω
¼ W
Glassbreak call point
Connect the screen
to an insulated terminal
3650 Ω
1%, ¼ W
Last call point of the line
560 Ω
¼ W
Connect to the
loop cable
shield
MCMAS5
L C
e)
560 Ω, ¼ W
3650 Ω, 1%, ¼ W
Fault
relay
Alarm
relay
Linear smoke detector
Connect the cable shields
of the loop to the one of
the L/C line
d)
Pic. 3 – Sample programming for serial address 172 = 1×100 + 7×10 + 2×1
www.acornfiresecurity.com
www.acornfiresecurity.com

MCMAS5 - TECHNICAL MANUAL - 090010924
4.4 Jumpers settings
Each jumper (pic. 1a) is a plastic cap with a protruding tab allowing for an easy removal and containing a conductive element on the
inside. The conductive element realizes an electric bridge between two of the three vertically aligned pins protruding from the board.
Connecting the lower pins activates the function described below the jumpers’ picture on the label; connecting the upper pins activates
the above function.
JUMPER SETTINGS
FROM LOOP Connected devices are powered by the loop (“Power supply” terminals left empty).
EXT. POWER 24 VDC voltage provided by an external power supply unit through the “Power supply”
terminals.
DISABLE No power supply unit monitoring (“PSU/fault” terminal left empty).
PSU/FAULT
Power supply unit monitoring. The device expects to see a 24 VDC line voltage at the
PSU/fault terminal. A fault signal is sent to the control unit and through the LED indicator if
tension goes to 0 V (including if the line to the PSU/fault terminal gets cut).
4.5 Flush-mount installation
Use a 503 box with blank cover.
Pic. 4 —Flush mounting
www.acornfiresecurity.com
www.acornfiresecurity.com

090010924 - TECHNICAL MANUAL - MCMAS5
5. PROGRAMMING
• Following the instructions in the control unit programming manual, set the activation of MCMAS5’s relay output whenever an
alarm signal comes from the module’s detector line.
This setting is mandatory for every detector type, but give special attention if it is used to power off a linear smoke detector in order to
reset it (pic. 1b and 1c).
WARNING: once the relay has been activated it will be necessary to send a reset signal from the
control unit to power the linear smoke detector again.
6. LED MEANING
LED LIGHT MEANING
PSU/FAULT Green steady light Regular functioning
Red blinking light Power supply unit fault
DETECT./OUT
Spento Regular functioning
Red blinking light Controlled detectors line fault (open / shorted / not supplied
L–C line) or lack of end of line resistor
Red steady light Relay output activation
POLLING Green blinking light Regular functioning (loop polling)
7. TEST
Reproduce a fault and an alarm signal on the detectors’ line to ensure the module responds correctly. It should warn the control unit,
LEDs should correctly light up and the relay output should properly function.
If the PSU monitoring function is active, reproduce a line interruction and verify the proper propagation of the fault signal.
8. SUMMARY
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. PRODUCT COMPLIANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.1 Overview and wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.2 Unplugging and plugging back the terminal board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.3 Serial address programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.4 Jumpers settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.5 Flush-mount installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5. PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6. LED MEANING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7. TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
8. SUMMARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
9. CERTIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
www.acornfiresecurity.com
www.acornfiresecurity.com
Table of contents
Other Nittan I/O System manuals
Popular I/O System manuals by other brands

Allen-Bradley
Allen-Bradley PowerFlex 750 Series installation instructions

Measurement Computing
Measurement Computing CIO-DIO96 user guide

APARIAN
APARIAN A-HRT-4I user manual

Beijer Electronics
Beijer Electronics G Series quick start guide

Rockwell Automation
Rockwell Automation AB Quality Allen-Bradley SLC 500 user manual

QTS
QTS AN-X2-MOD-MON user manual