Nittan NAM-AS3 User manual

ISSUE: 02
No:
DATE:
PAGE:
1of 9
OCTOBER2006
NISM/NAMAS3/02
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
INTRODUCTION
DESCRIPTION
The NAM-AS3 forms part of the Nittan (UK)'s
SENSORTEC-ANALOGUErangeofAnalogue
AddressableDevices.
Thismoduleisdesignedtoperformalooppowered,
addressable input module function from the detection
signallingloopofananalogue-addressablefiredetec-
tion system.
The NAM-AS3 may be used for a variety of purposes
such as monitoring a 'relay contact input' or monitor the
operationofa'sprinklerflowmonitoringswitch'.
OPERATION
The fire alarm control equipment must be capable of
communicating with the NAM-AS3 input module. If in
doubt, check with panel manufacturer.
The NAM-AS3 is a looppowered,two-wiresignallingde-
vice, it is connected onto the detection signalling loop's
SIG+ and -S wires, exactly as any other 'AS' sensor or
device.
FEATURES
*Monitoringa relay contact input.
*Monitoring the operationofa sprinkler flowswitch.
NAM-AS3 Input Module is made up as
follows:-
1 x Metal enclosure c/w 20mm knockouts
1 x NAM-AS3 PCB c/w internal plastic PCB enclosure
withhingedlid.
1 x Earth point (on lid)
1 x Earth point (inside of enclosure)
1 x 200mm Earth Strap
1 x Label inside lid for product identification and
deviceaddressidentification.
INPUT MODULE NAM-AS3
SENSORTEC-ANALOGUE FAMILY:-
SENSORS:-
ST-I-AS - Analogue Ionisation Smoke Sensor
ST-P-AS - Analogue Photoelectric Smoke Sensor
ST-H-AS -AnalogueHeatSensor
STB-4 - Standard Base for above sensors
DEVICES:-
ST-NCP-AS - AddressableCallPoint
BACK BOX - Back Box for ST-NCP-AS
MCM-AS4-ZoneMonitor/ControlUnit
SCM-AS4-AddressableSounderControlModule
NAM-AS3 - Addressable Input Module
OCM-AS3-OutputControlModule
SCI-5 -Basemounted Short Circuit Isolator
SCI-6 -Plate mountedShort Circuit Isolator
1-Gang Box - Single gang box for SCI-6
ADDRESSABLESOUNDERS:-
VCT-03-AS-NB -AddressableWallSounder
c/wVectorPlate/Cap(R=Red,W=WhitePlate/Cap).
VCT-03-CP(W)-SpareVectorPlate/Cap(White)
VCT-03-CP(R)-SpareVectorPlate/Cap(Red)
VCT-03-NT-AS-AddressableSounderc/wSTB-4Base
pre-wiredtothesounder.
VPR-SA2-NTAS-AddressableSounder,IP65rated,
wallmounted.
www.acornfiresecurity.com
www.acornfiresecurity.com

ISSUE: 02
No:
DATE:
PAGE:
2of 9
OCTOBER2006
NISM/NAMAS3/02
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
INPUT MODULE NAM-AS3
INSTALLATION
1)
a) Remove the NAM-AS3 boxed unit from its packaging.
b) Remove the 4 x posi-screws holding the lid to the main enclosure of the NAM-AS3.
c) Completely remove the single top screw holding the P.C.B. enclosure to the rear of the
main enclosure.
d) Unscrew halfway the two remaining lower screws holding the PCB enclosure to the rear of
the main enclosure.
e) Gently tilt and lift out the P.C.B. enclosure and safely store the PCB enclosure until the
wiring stage. (Note:Please take ESD precautions when removing the P.C.B. from the main
enclosure.
2)
a) Using initially a 3-4mm 'pilot' drill and then a special 'knock out' drilling tool, as shown
below, drill out the required amount of knockout holes for cable gland entry to the main
enclosure of NAM-AS3.
b) Using the template on page 5 of this manual, mark and drill the main enclosure screw
positions in the wall.
c) Position the NAM-AS3 enclosure to the wall and screw the 4 x fixing screws through the
rear of the enclosure.
d) Terminate all the loop cables and glands as required into the knockouts in the main
enclosure.
e) Insert the PCB enclosure in reverse order as per instructions above.
3)
a) Terminate all the loop cables and any IP/OP auxiliary switching cables where required into
the terminals on the PCB, please see page 8 of this manual for connection details.
b) Please note there is an earthing stud on the lid and on the rear of the main enclosure box
if an earth is required on the fire system devices. An earthing cable/strap is provided with the
NAM-AS3.
c) When all the necessary commissioning has successfully been carried out, replace the lid
onto the enclosure, replace the 4 x lid fixing posi-screws.
www.acornfiresecurity.com
www.acornfiresecurity.com

ISSUE: 02
No:
DATE:
PAGE:
3of 9
OCTOBER2006
NISM/NAMAS3/02
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
ENCLOSURE DESCRIPTION
TOPVIEWWITHLIDREMOVED SIDE VIEW 1
SIDE VIEW 2
Ø20.0mm
KNOCKOUTS
EARTHSTUD
2XLOWERPCB
ENCLOSURE
FIXINGSCREWS
TOPPCB
ENCLOSURE
FIXINGSCREW
PCB/
ENCLOSURE
Ø20.0mm
KNOCKOUTS
PCB&
CABLETERMINALS
1
387 2
On
465
LED CL
LEDINDICATIONS
DIL/Address
SettingSwitch COMMS TRIGGERED
SIG
S-
SIG -S
SCRN SCRN
NITTAN (UK) LTD - NAM-AS3
PLK1
www.acornfiresecurity.com
www.acornfiresecurity.com

ISSUE: 02
No:
DATE:
PAGE:
7of 9
OCTOBER2006
NISM/NAMAS3/02
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
ENCLOSURE (INTERNAL ASSEMBLY DIMENSIONS)
163mm
NOT TO SCALE
Ø20.0mm
22mm 22mm
30mm 30mm
54mm
48mm
160mm
1
387 2
On
465
LED CL
LEDINDICATIONS
DIL/Address
SettingSwitch COMMS TRIGGERED
SIG
S-
SIG -S
SCRN SCRN
NITTAN (UK) LTD - NAM-AS3
PLK1
www.acornfiresecurity.com
www.acornfiresecurity.com

ISSUE: 02
No:
DATE:
PAGE:
8of 9
OCTOBER2006
NISM/NAMAS3/02
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
CONNECTION WIRING DETAILS
= ON
= OFF
64
32
16
8
4
2
1
Example address switch
is set to 37 Decimal .
ON OFF
128
ADDRESS SETTING
CONNECTIONS TO NAM-AS3 PCB
CONNECTION DETAILS (PCB) AND ADDRESS SETTING
N/OFIRE
CONTACT
NAM-AS3
C
-S
L
SIG+
LOOP
WIRING
Screen
LINKPLK
FIRE LED
ON
FIRE LED
OFF
IN/OUT OUT/IN
1
387 2
On
465
LED CL
LED INDICATIONS
DIL/Address
Setting Switch COMMS TRIGGERED
SIG
S-
SIG -S
SCRN SCRN
PLK1
Address:
REMOTELEDINDICATOR
OUTPUT
3mA@24Vd.c. EXTERNALRELAY
INPUT
-
+FIRE
www.acornfiresecurity.com
www.acornfiresecurity.com

ISSUE: 02
No:
DATE:
PAGE:
9of 9
OCTOBER2006
NISM/NAMAS3/02
NAM-AS3 LOOP POWERED
INPUT MODULE
INSTALLATION & TECHNICAL
MANUAL
NITTAN(UK) LTD.
SUBJECT TO CHANGE WITHOUT PRIORNOTICE.
NAM-AS3-TECHNICALSPECIFICATION
Part Numbers:-
ModelNumber - - - NAM-AS3.
Description - - - AddressableInputModule(Boxed).
ComputerReferenceNumber - - - F16N85110
Protocol:-
CommunicationProtocol - - - NISM/WFM/02 (Nittan AS Protocol).
AddressSetting - - - 8 Bit, DIL Switch
TypeIdentificationData - - - 2 Bits Fixed.
Ratings:-
CurrentConsumption* - - - 200µA (Quiescent) c/w conventional detector zone.
(*From loop @24v) - - - 4mA(Max.)
PowerSupplyRequirements - - - LoopPowered, NoexternalPSUrequired.
LED Indications:-
On Board LED Indication a) - - Red 'COMMS.' LED:- ('Pulses' when polled).
b) - - Red'TRIGGERED'LED:-('Pulses'whenNAM-AS3Operate's.
Note:'COMMS'&'TRIGGERED'LEDsboth'Pulse'
simultaneouslywhentheNAM-AS3operates).
General Specifications:-
Mass - - - 50g (PCB only).
- - - 1.1Kgcomplete(Boxed).
20mmKnockouts - - - 12 nos.
OperatingTemperature - - - -10 Deg. C. to +50 Deg. C.
I.P.Rating - - - I.P.43.(Boxed).
Transistorswitch'LEDRepeat' - - - 3mA @ 24V d.c.
- (For remoteLEDoperation).
EarthStrap - - - 200mm length, 24/0.2ØGreen/yellow c/w 2 x 4.5-5mm ring
crimp ends.
www.acornfiresecurity.com
www.acornfiresecurity.com
Table of contents
Other Nittan I/O System manuals
Popular I/O System manuals by other brands

Allen-Bradley
Allen-Bradley PowerFlex 750 Series installation instructions

Measurement Computing
Measurement Computing CIO-DIO96 user guide

APARIAN
APARIAN A-HRT-4I user manual

Beijer Electronics
Beijer Electronics G Series quick start guide

Rockwell Automation
Rockwell Automation AB Quality Allen-Bradley SLC 500 user manual

QTS
QTS AN-X2-MOD-MON user manual