manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. NK TECHNOLOGIES
  6. •
  7. Switch
  8. •
  9. NK TECHNOLOGIES AS1 - DODC - FL User manual

NK TECHNOLOGIES AS1 - DODC - FL User manual

INSTRUCTIONS
1. Run the wire to be monitored through
aperture.
2. Mount the sensor.
3. Connect output wiring.
A. Use up to 14 AWG copper wires.
B. Ensure load matches the output shown on
the sensor label.
4. Adjust Setpoint
A. Use the potentiometer to adjust the set-
point.
AS1 DODC SERIES
AC Current Operated Switch
With Dual Output
AS1 - DODC - FL
CASE STYLE:
FL - Fixed Core, Top Terminals
OUTPUT (Solid State Switch):
DODC - Dual Normally Open, 1.0A @ 30VDC
SENSOR TYPE:
AS1 - AC current operated switch with single range
0.75A -- 20A
AS2 - AC current operated switch with single range
20A -- 50A
Model Number KeySpecifications
Power Required None - self powered
Output Switch Isolated Solid State Switch
Switch Rating DODC - N.O. 1A @ 30VDC
Off State Leakage <10 Microamps
Response Time 100 mS
Hysteresis < 8% of Setpoint
Set Point Ranges A Contact: Adjustable 0.75A - 20A
B Contact: Adjustable 0.75A - 20A
Start-up Delay 2.0 Seconds (fixed)
Setpoint Adjust 4 Turn potentiometer
Isolation Voltage Designed to meet UL508 require-
ments to 1,270 VAC
Tested to 5,000 VAC
Frequency Range 6-100Hz
Sensing Apeture -FL 0.75” (19mm)
Environmental -4 to122Deg F (-20 to 50 Deg C)
0-95% RH, Non Condensing
Ranges & Maximum Amps
Quick “How To” Guide
AS1-DODC-FL Inst. Rev 2 12/14 P/N 39-360-0001
3511 Charter Park Drive, San Jose, CA 95136
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
[email protected], www.nktechnologies.com
Know Your Power
Other NK Technologies Products Include:
AC & DC Current Transducers
AC & DC Current Operated Switches
1φ& 3φPower Transducers
Current & Potential Transformers (CTs&PTs)
TYPE RANGE MAXIMUM INPUTAMPS
FIXED CORE 0.75- 20 A
CONTINUOUS 6 SEC. 1 SEC.
50A 200A 400A
FIXED CORE 20-50 A 50A 200A 400A
AS1 Series are self-powered, solid-state current-operated
switches which trigger when the current level sensed
through the apertureexceeds the adjusted setpoint. The solid
state output contacts can switch DC low voltage only; up
to 30 VDC, and up to one amp.
For All Versions
Run wire to be monitored through aperture (opening) in
the sensor.
AS1 switches can be located in the same environment as
motors, contactors, heaters, pull-boxes, and other electri-
cal enclosures. Mounting can be done in any position or
hung directly on wires with a wire tie. Ensure at least one
inch clearance exists between sensor and other magnetic
devices.
Description
Installation
Output Wiring
Setpoint Adjustment
Connect control or monitoring wires to the sensor. Use
up to 14 AWG copper wire and tighten terminals to 5
inch-pounds torque. Be sure the output load does not
exceed the switch rating.
CAUTION Incandescent lamps canhave “Cold Filament
Inrush” current of up to 10 times their rated amperage. Use
caution when switching lamps.
AS1SeriesSETPOINT isadjustedwith a4-turnpotentiom-
eter. The pot is shipped factory set to the lowest setpoint,
fully clockwise (CCW). Turning the pot counter-clockwise
(CW) will increase the setpoint. The pot has a slip-clutch to
prevent damage at either end of its rotation. To determine
where the adjustment is, turn the pot all the way CCW. This
will return it to the minimum setpoint.
Adjustment Notes:
1. Output contacts are solid-state. Check output status by
applying voltage to the contacts and reading the voltage
drop across the contacts. An Ohmmeter set on “Continu-
ity” will give misleading results.
2. It is recommended that setpoint be adjusted to allow for
voltage variations of 10-15%.
Typical Adjustment
1. Both “A” and “B” contacts are adjustable. Turn the pots
to minimum setpoint (4 turns CCW). Each contact has a
delay before closing of two seconds, but only during the
initial start up. This delay is not adjustable, but after the
1. Sensor is always tripped
A. The setpoint maybetoo low. Turn pot CWto increase
setpoint.
B. Switch has been overloaded and contacts are burned
out. Check the output load, remembering to include
inrush on inductive loads (coils, motors, ballasts)
2. Sensor will not trip
A. The setpoint may be too high. Turn pot CCW to
decrease setpoint.
sensor is in normal monitoring mode, the contact s will
close nearly instantaneously after current rise over the set
point.
2. Have normal operating current running through sensor.
Provided the monitored current is above 0.75A, both
outputs should be tripped since the trip points are at their
minimums. LEDs indicate the status of the contacts; slow
flashing (once every 2 to 3 seconds) indicates untripped
while fast flashing (2 to 3 times per second) indicates
contacts are tripped.
3. Turn the pot foreach contact setpoint adjustment CWuntil
the unit un-trips. This is indicated by the slow flashing of
the LED and by the changing of the output switch status.
The contacts are fully isolated from each other.
4. Now turn the pot CCW slowly until the unit trips again.
It now set at the current level being monitored.
A. To Set UNDERLOAD - Turn the pot about 1/8 turn
(or less) farther CCW.
B. To Set OVERLOAD - Turn the pot about 1/8 turn
(or less) farther CW.
B. Monitored current is below minimum required. Loop
the monitored wire several times through the aper-
ture until the “sensed” current rises above minimum.
Sensed Amps = (Actual Amps) x (Number of Loops).
Count loops on the inside of the aperture.
C. Switch has been overloaded and contacts are burned
out. Check the output load, remembering to include
inrush on inductive loads (coils, motors, ballasts).
Trouble Shooting
Setpoint
"A"
Setpoint
"B"
NORMALLY OPEN
"A" Contact
NORMALLY OPEN
"B" Contact
LED "A" LED "B"
AMPS
TIME
Startup
Inrush
Normal Operation Belt or
Coupling
Breaks
2 Sec. delay

Other NK TECHNOLOGIES Switch manuals

NK TECHNOLOGIES DS3 Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES DS3 Series User manual

NK TECHNOLOGIES DS1-FD Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES DS1-FD Series User manual

NK TECHNOLOGIES AS3 Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES AS3 Series User manual

NK TECHNOLOGIES DS1-FD Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES DS1-FD Series User manual

NK TECHNOLOGIES DS3 Series User manual

NK TECHNOLOGIES

NK TECHNOLOGIES DS3 Series User manual

Popular Switch manuals by other brands

AMX UDM-0808-SIG quick start guide

AMX

AMX UDM-0808-SIG quick start guide

StarTech.com ST121HDBTSC quick start guide

StarTech.com

StarTech.com ST121HDBTSC quick start guide

ANTAIRA LNX-500AG user manual

ANTAIRA

ANTAIRA LNX-500AG user manual

Quintech RFS 0702 Operation and Adjustment Procedure

Quintech

Quintech RFS 0702 Operation and Adjustment Procedure

Elko EKO07115 quick start guide

Elko

Elko EKO07115 quick start guide

DONG SUNG SENSORS DQ Series manual

DONG SUNG SENSORS

DONG SUNG SENSORS DQ Series manual

CyberPower CyberSwitch CSW8RU user guide

CyberPower

CyberPower CyberSwitch CSW8RU user guide

Cisco Nexus 9364C Hardware installation guide

Cisco

Cisco Nexus 9364C Hardware installation guide

Extron electronics SW AV user manual

Extron electronics

Extron electronics SW AV user manual

DANLERS COPIR IP66 instructions

DANLERS

DANLERS COPIR IP66 instructions

Lucent Technologies Cajun P333T quick start guide

Lucent Technologies

Lucent Technologies Cajun P333T quick start guide

Sunricher SR-ZGP2801K4-DIM-E instruction manual

Sunricher

Sunricher SR-ZGP2801K4-DIM-E instruction manual

MicroNet SP212D user manual

MicroNet

MicroNet SP212D user manual

Compaq A7340A - Surestore FC 1Gb/2Gb Switch 16B Quick setup guide

Compaq

Compaq A7340A - Surestore FC 1Gb/2Gb Switch 16B Quick setup guide

Russound 857 instruction manual

Russound

Russound 857 instruction manual

EXFO IQS-9100B user guide

EXFO

EXFO IQS-9100B user guide

Irenis Blankom BMS-0512C quick start

Irenis

Irenis Blankom BMS-0512C quick start

GarrettCom 500-Series Installation and user guide

GarrettCom

GarrettCom 500-Series Installation and user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.