
DS1-FD Series areDC current operatedrelays. They operate
(relay contacts change state) when the current level through
the hole exceeds the adjustable setpoint. They accept 24
VAC or 24 VDC power. The outputs are isolated from the
input and the power supply. The sensor can be supplied
with form C relay output (-SDT ), either resetting when the
monitored current falls below the setpoint, or latching in the
tripped condition until an external button closes between the
“reset” terminals.
Description
Installation
Setpoint Adjustment
Setpoint Adjustment
DS1-FD switches have two setpoint adjustment mecha-
nisms:
1. Turn the setpoint CoarseAdjustment (CA) fully CW
to set the trip point at the maximum (400 ADC).
DO NOT OVERTURN!
2. Turn the Fine Adjustment (FA) fully CCW .
3. Slowly turn the CA CCW until the sensor trips.
4. Slowly turn FA CW until the sensor untrips.
5. The adjustment can be left at this point and the output
will change on current increase.
6. Turning the FA CCW will cause the sensor output to
trip. This setting will detect a current decrease and
the relay contacts will revert to original condition
when current falls below the set point.
7. If turning FA CW in step 4 does not allow the output to
untrip, return to step 1, and readjust using CA.
Adjustment Notes:
1. Relay output contacts are mechanical, and can be tested
with an ohmmeter if the controlled circuit is not ener-
gized.
2. If the controlled circuit is energized, testing can be
1. Sensor is always tripped
A. Current may be higher than 400 ADC.
B. The setpoint may be too low. Turn Coarse Adjust-
ment pot CW to increase setpoint.
C. Sensor output has been overloaded and contacts are
burned out. Check the output load, remembering to
include inrush on inductive loads (coils, motors, bal-
lasts).
2. Sensor will not trip
A. Unit is not powered. Check power supply and power
wiring, confirm Green LED is on.
B. The current may be lower than the 20 amp minimum
needed to operate the sensor output. Loop the con-
ductor through the sensing aperture twice or more to
increase the current “seen” by the sensor.
C. The setpoint may be too high. Turn pot CCW to
decrease setpoint.
D. Switch has been overloaded and contacts are burned
out. Check the output load, remembering to include
inrush on inductive loads (coils, motors, ballasts).
done with a volt meter. A closed contact will show no
potential and an open contact will show full controlled
circuit voltage.
3. We recommend adjusting setpoint to allow for normal
voltage variations.
5. Hysteresis (deadband) is 5% of the setpoint. During set
point adjustment, the hysteresis will be tighter than in
normal operation to make adjustment easier.
6. When adjusting the latching version models, remember
to short between terminals 6 and 7 to allow the output
to reset.
Trouble Shooting
Power Wiring
Connect 24VAC or DC powertoTerminals 1 and2. Tighten
to 5-7 In-Lb torque. The connection is not polarity sensitive.
The Green LED will light when the sensor is energized.
Output Wiring
Connect control or monitoring wires to the sensor. Use
up to 14-22 AWG copper wire and tighten terminals to 5-7
In-Lb torque. Be sure the output load does not exceed the
relay contact rating. Note that the NO contact closes on
current rise, and the NC contact opens on current rise.
Mount the sensor to a DIN rail or secure to a panel with
screws through the mounting holes. Run wire to be moni-
tored through opening in the sensor.
DS1-FD switches work in the same environment as mo-
tors, contactors, heaters, pull-boxes, and other electrical
enclosures. They can be mounted in any position or hung
directly on wires with a wire tie. Just leave at least one
inch distance between sensor and other magnetic devices.
1234
Power
Supply
5
NO
NC
Coarse
Fine
12345G
POWER
R
STATUS
COARSE
FINE
234
Power
Supply
5
NO
NC
Coarse
Fine
G
POWER
R
STATUS
COARSE
FINE
1234567
EXTERNAL
RESET
Connection-Auto Reset Connection-Latching
Note: reset is not isolated from sensor
power. Do Not add voltage to the reset
button, shorting action only
MONITORED
CIRCUITAMPS OUTPUT CONTACT RED
STATUS
LED
. NO NC
None or < 20ADC OPEN CLOSED OFF
Lower Than Set Point OPEN CLOSED OFF
Higher Than Set Point CLOSED OPEN ON
Contact and LED Action:
DS1-FD Inst. Rev1, 07-11-18 P/N 393000107