
5-Jul-2022 Page 7 002596MAN-01
TABLE 1 - Power Supply Connections (AHW/AH4P)
Line Description Voltages
L1/N Line 1 L1 for 230-1-60, N for 115-1-60
L2 Line 2 All
GND Ground All
TABLE 2 - Power Supply Connections
(Plenum Heater)
Line Description Voltages
L1 Line 1 All
L2 Line 2 All
GND Ground All (connect to ground lug)
Wiring
NOTE: A properly qualified electrician
should be retained for all connections to the
unit and associated controls. The connec-
tions to the unit MUST CONFORM TO LOCAL
CODES.
Power Supply Connections
The air handler has a 0.875” knockout for main power sup-
ply connection from the breaker panel to the electrical box.
There are also 0.875” knockouts and plastic grommet(s) for con-
nections to plenum heater power supply, thermostat, and water
valve.
NOTE: Two separate power supplies are required, one for
the air handler and a second one for the plenum heater.
Each must have its own supply wires and breaker.
A schematic (wiring) diagram can be found on the
electrical box cover of the unit as well as in the Model Specific
Information section of this manual. The Electrical Specifica-
tions table in the Model Specific Information section contains
information about the wire and breaker size.
Control Transformer
The low voltage controls are powered by a class II trans-
former with impedance protection. If the transformer is acci-
dentally shorted out by directly connecting the R and C termi-
nals, it will need to be replaced.
IMPORTANT NOTE: For 208/230VAC-1-60
units, if connecting to 208VAC power supply
move the red wire connected to the 240 ter-
minal of the transformer to the 208 terminal
of the transformer.
that a simultaneous G call is required, and that especially for
externally installed plenum heaters (as for AH4P-series), an
airflow setting resulting in an air velocity of at least 400 ft/min at
the elements is needed to prevent plenum heater high tempera-
ture safety trips.
Also, a 24VAC water valve maybe connected between V
and C.
TABLE 3 - Control Signal Description
(Single Airflow)
Signal Description
C 24VAC Common (Ground)
R 24VAC Hot
W2 Auxiliary heat
G Blower ON
V 24VAC water valve (connect between V & C)
CP Plenum Heater dry contact
(Connect to C or I in plenum heater)
1 Plenum Heater dry contact.
(Connect to 1 and 2 in plenum heater)
For installations that require the controller to call for multi-
ple airflows, the grey wire jumper from G to an airflow terminal
should be disconnected (and well insulated to prevent acci-
dental shorting). The controller may then make a dry contact
between R and one of the five airflow terminals to activate those
airflows. A call for higher airflow will override a call for a lower
airflow value; for example, if R is connected to both the
1200cfm and 1500cfm terminals, the airflow will be 1500 cfm.
Note that if a 24VAC water valve connected between V
and C is to be opened, a G call must be made at the same time.
Auxiliary heat may be called for by making a dry contact
from R to W2, which will activate the plenum heater relay and
turn on the plenum heater through terminals CP and 1. Note
that a simultaneous airflow call is required, and that especially
for externally installed plenum heaters (as for AH4P-series), an
airflow setting resulting in an air velocity of at least 400 ft/min at
the elements is needed to prevent plenum heater high tempera-
ture safety trips.
TABLE 4 - Control Signal Description
(Multiple Airflows)
Signal Description
C 24VAC Common (Ground)
R 24VAC Hot
W2 Auxiliary heat
G Water valve open
900cfm
1200cfm
1500cfm
1900cfm
2300cfm
V 24VAC water valve (connect between V & C)
CP Plenum Heater dry contact
(Connect to C or I in plenum heater)
1 Plenum Heater dry contact.
(Connect to 1 and 2 in plenum heater)
Activate airflow at this airflow value
(disconnect grey wire jumper to G and insulate
its fork terminal)
Thermostat Requirements
(non-VSP models)
In the most usual and simplest installation, the required
room thermostat is one which makes a dry contact between the
air handler’s R and G terminals in heating or cooling mode when
it wants the air handler blower to run. This is the only require-
ment for the thermostat.
In this case, the provided grey wire jumper from G should
be connected to the terminal corresponding to the desired air-
flow (900, 1200, 1500, 1900, or 2300 cfm).
Auxiliary heat may be called for by making a dry contact
from R to W2, which will activate the plenum heater relay and
turn on the plenum heater through terminals CP and 1. Note