
5
• Theoutdoorunitrequiresbothpowerandcontrolcircuit
electrical connections. Refer to the wiring diagram /
schematic for identification and location of outdoor unit
field wiring interfaces (Figures 6 - 11, pages 10 - 15).
Make all electrical connections in accordance with all
applicable codes and ordinances.
• Overcurrentprotectionmustbeprovidedatthebranch
circuitdistributionpanelandsizedasshownontheunit
rating label and according to applicable local codes.
See the unit rating plate for minimum circuit ampacity
and maximum overcurrent protection limits.
• Providepowersupplyfortheunitinaccordancewiththe
unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment.
• Useonlycopperwireforthelinevoltagepowersupply
to this unit as listed inTable 1.Use proper code agency
listed conduit and a conduit connector for connecting
the supply wires to the unit.Use of rain tight conduit is
recommended.
• 208/230Voltunitsareshippedfromthefactorywired
for 230 volt operation.For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
• Optionalequipmentrequiringconnectiontothepower
or control circuits must be wired in strict accordance of
the NEC (ANSI/NFPA 70), applicable local codes, and
the instructions provided with the equipment.
Comfort AlertTM Diagnostics Module
(Select Models Only)
The Comfort AlertTM Diagnostics Module (Figure 2) is a
breakthrough innovation for troubleshooting heat pump
and air conditioning system failures.The module installs
easily in the electrical box of the outdoor unit near the
compressorcontactor.Bymonitoringandanalyzingdata
from the Copeland scroll compressor and the thermostat
demand, the module can accurately detect the cause of
electricalandsystemrelatedfailureswithoutanysensors.
A flashing LED indicator communicates the ALERT code
and a diagnostic key is also imprinted on the side of the
module to quickly direct the technician to the root cause
ofaproblem.NOTE:Thismoduledoesnotprovidesafety
protection! The Comfort AlertTM Diagnostics Module is a
monitoring device and cannot control or shut down other
devices.
24 VAC Power Wiring
The Comfort AlertTM module requires a constant nominal
24VAC power supply.The module cannot be powered by
the Cterminal on a defrost board or other control board
without experiencing nuisance alerts. NOTE: The wiring
to the module’s R& Cterminals must be routed directly
from the indoor unit or thermostat.
Iftheconstant24VAC(Rwire)isnotpresentintheoutdoor
unit,use oneofthe sparewiresin thethermostatcableto
bring power to the module.Connect the other end of the
spare wire to Rat the indoor unit or thermostat.
Figure 2. Comfort AlertTM Diagnostics Module
POWER LED
(Green)
TRIP LED
(Red)
ALERT LED
(Yellow)
Diagnostics
Key
Thermostat Demand Wiring
TheComfortAlertTM modulerequiresathermostatdemand
signal to operate properly. The thermostat demand
signal input (labeled Yon the module), should always be
connectedtothecompressorcontactorcoil.NOTE:When
thecoilisenergized,thedemandsignalinputis24VAC.
Whenthecoilisnotenergized,thedemandsignalinput
should be less than 0.5 VAC.
NOTES:
• Factory installed modules have different thermostat
demandsignalwiring.Alwaysfollowmanufacturerwiring
instructions when replacing the module.
• Afterthethermostatdemandsignalisconnected,verify
that 24 VAC across Y& Cwhen demand is present.
Interpreting the Diagnostic LED’s
Whenanabnormalsystemconditionoccurs,theComfort
AlertTM module displays the appropriate ALERT and/or
TRIP LED will flash a number of times consecutively,
pause and then repeat the process. To identify a Flash
Code number, count the number of consecutive flashes.
Each time the module powers up, the last ALERT Flash
Code that occurred prior to shut down is displayed for
one minute.The module will continue to display the LED
until the condition returns to normal or if 24 VAC power
is removed from the module. See Table 3 (page 16) for
flash code identification or Table 4 (page 17) for module
wiring troubleshooting.
LED Description
• POWERLED(Green):indicatesvoltageispresentat
the power connection of the module.
• ALERT LED (Yellow): communicates an abnormal
system condition through a unique flash code.
NOTE:TheALERTLED willflash consecutively,pause
andthenrepeattheprocess.Thenumberofconsecutive