Northern Lights OWN-GEN User manual

OWN-GEN
WaveNet Digital Monitoring System
GeneralInstallation
andUserManual
Marine Generators | Marine Diesel Engines | Land-Based Generators

Northern Lights
4420 14th Avenue N.W.
Seattle, WA 98107
Tel: (206) 789-3880
Fax: (206) 782-5455
Copyright ©2012 Northern Lights, Inc.
All rights reserved. Northern Lights™, and
the Northern Lights logo are trademarks of
Northern Lights, Inc.
Printed in U.S.A.
PART NO.: OWN-GEN 1/12

4.7.3 Event History Log ...........................16 - 17
4.8 WaveNet LED Status Indicators.......... 18
4.9 Lamp Indication Meanings............18 -19
4.10 Warnings & Failures...................19 - 20
4.11 Genset Online ................................... 20
GROUP 5 -
ADVANCED SETUP..........................20
GROUP 6 RECOMMENDED MAINTENANCE
..... 20
GROUP 7 - WAVENET REMOTE PANEL
7.1
Remote Unit Settings
................................ 21
7.2
On-Line Genset Status Mode
...............21 - 22
7.2.1 Genset Controller’s Name................22
7.2.2 State.................................................22
7.2.3 Status Mark...................................... 22
7.3 On-Line Genset Parameter Mode 22 - 23
GROUP 8 - APPENDEX A: ACCESSORY LIST
8.1
WaveNet Controller Harness - Accessories
.... 23
8.2 CT’s (Current Transformers)............... 24
8.3
WaveNet Replaceable 12/24 VDC Relays
.. 24
8.4 WaveNet Fusing.................................. 24
GROUP 9
-
APPENDIX B: ADDITIONAL DRAWINGS
.26
WaveNet Specifications.....................................2
GROUP 1 - WAVENET CONTROLLER SERIES
1.1 This Manual...........................................3
GROUP 2 -
RECEIVING, HANDLING & STORAGE..4
GROUP 3 - INSTALLATION & WIRING
3.1 Safety Information................................. 5
3.2 12/24 VDC System Operation...............5
3.2.1 Relays................................................6
3.2.2 Relay Fuses.......................................6
3.3 WaveNet Terminals........................6 - 10
3.3.1 Current Transformer Wiring Note.....10
GROUP 4 -
OPERATION & BASIC USER CONFIGURATION
4.1 Power-Up............................................10
4.2 Controller Alarming ............................. 10
4.3 Controller States..........................11 - 12
4.3.1
Locking the WaveNet Screen in Run Mode
. 12
4.4 WaveNet Start / Stop Behavior....12 - 13
4.5 Controller Sleep..................................13
4.6 WaveNet Menu System Operation...... 13
4.7 Basic Menu.........................................14
4.7.1 Clock Setup......................................14
4.7.2 Basic Setup...................................... 15
Proprietary Information
This publication is the sole property of Northern Lights, Inc.
It may not be reproduced in whole or part without the expressed written permission of Northern Lights, Inc.
© Northern Lights, Inc. 2012. All rights reserved. Litho U.S.A. Publication number: OWN-GEN 8/12
Table of Contents
USER MANUAL
for WaveNet Generator Set Controllers
1

OWN-GEN 01/12
2
Table 1: Wavenet Specifications
VDC Rating 12/24 VDC
Standby Current
Consumption 50 mA @ 12 VDC
Load Equivalency Number
(LEN)
WaveNet: 1 / WaveNet remote:2(NMEA 2000® Spec. : 1 LEN=50mA)
Operating Temp -40oC to +85oC (-40oF to +185oF)
LCD Operating Temp. ** -20oC to +70oC (-4oF to +158oF)
Function
Range Function Range
Speed Sensing 0-300vac, 0-3600rpm
Voltage Sensing Max 700vac, +/- 1%
Current Sensing * Max 5A, +/- 2%
Frequency Sensing 1 - 100 HZ
Engine Temp 10-265 oF
Oil Pressure 0-90 PSI
Analog Input 7mA Max
Digital Input 7mA Max
LCD Display 128 x 60 Graphic Display, Backlit, 60oviewing angle
LED Display Red, Green, Yellow LED representation, Daytime visible, 60o
viewing angle
NMEA 2000®Connector DeviceNet Micro-C
Relays replaceable relays for Run signal and Preheat signal, 12 or
24VDC Coil
Dimensions W x H x D: 139 x 113 x 65 mm (5.7 x 4.45 x 2.56 in.)
Weight 0.45 kg (1.0 lb)
* Use of industry standard CT required.
** The LCD display will exhibit color and response time changes at high and low
temperatures respectively but will not be damaged as long as within Operating Temp.
WAVENET SPECIFICATIONS

OWN-GEN 01/12
1. WAVENET CONTROLLER SERIES
3
WaveNet Front View
WaveNet Back View
The WaveNet is designed for use on generator sets
with mechanical engines. It can monitor analog
data from senders on the engine and generator
such as oil pressure, coolant temperature, current,
voltage, engine speed and generator frequency
.
In addition to the monitoring features, the
WaveNet controller can be used to provide
protective warnings or shutdowns.
This manual is divided into two sections:
1. Hardware installation
2. Operation / Configuration
1.1 THIS MANUAL

OWN-GEN 01/12
4
Receiving:
Every effort is made to ensure that your WaveNet gen-set controller arrives at its destination
undamaged and ready for installation. The packaging is designed to protect the WaveNet internal
components as well as the enclosure. Care should be taken to protect the equipment from impact at
all times. Do not remove the protective packaging until the equipment is at the installation site and
ready to be installed.
When the WaveNet reaches its destination, the customer should inspect the shipping box and controller
for
any signs of damage that may have occurred during transportation. Any damage should be reported
to a Northern Lights representative after a thorough inspection has been completed.
A shipping label affixed to the shipping box includes a variety of product and shipping information,
such as items and Customer numbers. Make certain that this information matches your order ....
information.
Each WaveNet controller is packaged in its own box. Do not discard the packing material until the
controller is ready for installation.
Handling:
As previously mentioned, each WaveNet gen-set controller is packaged in its own individual box.
Protect the equipment from impact at all times and do not carelessly stack. Once the controller is at
the installation site and ready to be installed, the packaging material may be removed.
Storage:
Although well packaged, this equipment is not suitable for outdoor storage. WaveNet is to be stored
indoors for any period of time, it should be stored with its protective packaging in place. Protect the controller
at all times from excessive moisture, dirty conditions, corrosive conditions, and other contaminants. It is
strongly recommended that the package-protected equipment be stored in a climate-controlled environment
of -20 to 65°C (-4 to 149°F), with a relative humidity of 80% or less. Do not stack other equipment on top
of the stored controllers.
2. RECEIVING, HANDLING & STORAGE

OWN-GEN 01/12
3. WAVENET SERIES INSTALLATION AND WIRING
The following general safety precautions should be headed:
1. The WaveNet may carry high Voltage/Current which can cause serious injury or death.
Extreme caution must be exercised when connections are being installed to or from the
controller. All wiring connections must be de-energized before any installations are performed.
Wiring of the WaveNet should be performed by qualified electricians only.
2. AC power may carry high Voltage/Current which can cause serious injury or death.
De-energize all AC power sources before any connections are performed.
3. NEVER energize AC power with AC current sensing connector unplugged. An energized,
unplugged connector could result in severe injury or death. Never unplug an energized
connector.
4.
WaveNet is connected on a NMEA 2000 network. Installation must be made by an
NMEA 2000 certified technician.
The WaveNet controller can be placed in either 12V or 24V electrical systems.
Generator systems contain high voltage circuits. Working on powered equipment can cause damage to
equipment, injury, or death. The following symbols will be used in this document to classify information:
3.1 SAFETY INFORMATION
3.2 WAVENET 12/24VDC SYSTEM OPERATION
Caution: This is used to indicate something that you should take
special notice of but that is not normally a threat to safety.
Danger: This is used to indicate a potential for injury or death.
Danger - High Voltage: This is similar to Danger above but relates
specifically to conditions where high voltage is encountered.
5
updated 1-17-12

OWN-GEN 01/12
3.2.2 RELAY FUSES
3.3 WAVENET TERMINALS
3.2.1 RELAYS
The WaveNet controller is designed to operate on 12 or 24 VDC systems. When operating on 12VDC
systems the fuel and preheat outputs require 12VDC relays, and 24VDC relays when operating on
24VDC systems. The WaveNet comes preinstalled with the correct relays depending on the product
number specified when ordered.
Contact Northern Lights if replacement relays are required.
Relays for 12 or 24VDC system operation are as follows:
• 22-42047 for 12VDC operation
• 22-40085 for 24VDC operation
CAUTION: needs to be taken when connecting relay outputs to an inductive load. Due to the
inductive nature of certain loads (starters, pull coils), initial current draw may be higher than stated
in the load specs which could damage the onboard relays.
Output relays are protected by onboard 40A fuse protection. Smaller amperage fuses from many
automotive stores may be used in place of the higher current 40A. If installing lower amperage fuse
protection, be certain that the current draw on each relay does not exceed the fuse current limit.
An approved 40A fuse is: LITTLEFUSE – 257040 (32VDC, 40A, auto fast action)
Figure 1 on page 6 shows the location of all terminals on the controller and the numbering of all
circuits.
Table 2 lists the minimum wire size, maximum current capacity, name, and function of each circuit.
The wire gauges given in the table are the minimum recommended only.
6

Figure 1 - General WaveNet System Wiring Diagram
7
WaveNet is connected on a NMEA 2000 network. Installation must be made by an NMEA 2000
certified technician.
updated 1-17-12

OWN-GEN 01/12
TABLE 2 Table 2: WaveNet Terminal Details
Quick
Fit
Terminals
Terminal Wire Size
(AWG) Current Max* Functions
Crank 12 40A Crank Output Terminal
Battery +112 40A Positive Battery Terminal
Battery -112 40A Negative Battery Terminal
Fuel 12 40A Fuel Output Terminal
Extra Relay
12 40A Pre-Heat Input Terminal
Extra Relay 12 40A Pre-Heat Output Terminal
Speed 1 18 100mA Speed Signal Connection
Speed 2 18 100mA Speed Signal Connection
* Total controller current output (max 60A)
1Ensure wire gauge is sufficient: otherwise (especially during cranking) there could be a voltage drop across the cable to
the controller from the battery related features of the controller.
Analog
Inputs Terminal
Detail Terminal
Location Wire Size
(AWG) Current Max. Function
Ground 1 18 7mA N/A
Input 2 2 18 7mA N/A
Input 3 3 18 7mA Engine Temperature Sender
(Low Resistance, Gain of 3)
Input 4 4 18 7mA Oil Pressure Sender
(Low Resistance, Gain of 3)
Input 5 5 18 7mA N/A
Input 6 6 18 7mA N/A
Input 7 7 18 7mA N/A
5V out 8 18 7mA N/A
Digital
Inputs Terminal
Detail Terminal
Location Wire Size
(AWG) Current Max. Function
Input H - GND
1 18 7mA N/A
Input G - GND
2 18 7mA N/A
Input F - GND
3 18 7mA Auxiliary Failure1
Input E - GND
4 18 7mA Option Coolant Level Switch1
Input D - BAT
5 18 7mA N/A
Input C - BAT
6 18 7mA N/A
Input B - BAT
7 18 7mA N/A
Input A - BAT
8 18 7mA N/A
Emer. Stop
9 18 7mA
Allows Manual Emergency Stop
(Open = Active)
10 10 18 7mA
N/A
Ground
11 18 7mA
Ground
Ground
12 18 7mA
Ground
1Ground input to generate logic high.
8

OWN-GEN 01/12
TABLE 2 (CONTINUED)
Digital
Outputs Terminal
Detail Terminal
Location Wire Size
(AWG) Current Max. Function
+ V Bat 1 18 1.5A N/A
Output A 2 18 200mA N/A
Output B 3 18 200mA N/A
Output C 4 18 200mA N/A
Output D 5 18 200mA N/A
Output E 6 18 200mA N/A
Output F 7 18 200mA N/A
Output G 8 18 200mA N/A
Output H 9 18 200mA N/A
+ V Bat 10 18 1.5A N/A
RS485
(Modbus)
Terminal
Detail Terminal
Location Wire Size
(AWG) Current Max. Function
RS485-A 1 18 7mA N/A
Ground 2 18 7mA N/A
RS485-B 3 18 7mA N/A
RS485-A 4 18 7mA N/A
Ground 5 18 7mA N/A
RS485-B 6 18 7mA N/A
AC
Voltage
Sensing
Terminal
Detail Terminal
Location Wire Size
(AWG) Current Max. Function
Phase A * 1 18 7mA Monitor Generated AC Voltage
Phase B * 2 18 7mA Monitor Generated AC Voltage
Phase C * 3 18 7mA Monitor Generated AC Voltage
Neutral 4 18 7mA AC Voltage Neutral connection
* Place 1Afuse between the hot lines and the voltage sensing terminals of WaveNet.
AC
Current
Sensing
Terminal
Detail Terminal
Location Wire Size
(AWG) Current Max. Function
Phase A 1 18 5A Phase A Current Sensing CT -
Phase B 2 18 5A Phase B Current Sensing CT -
Phase C 3 18 5A Phase C Current Sensing CT -
Phase A 4 18 5A Phase A Current Sensing CT +
Phase B 5 18 5A Phase B Current Sensing CT +
Phase C 6 18 5A Phase C Current Sensing CT +
It is extremely important to connect each phase to the appropriate terminal location. Never
misphase inputs. Always match terminal details to the matching terminal location
The current transformers (CTs) negative leads must be terminated individually into the WaveNetAC
Current connector. DO NOT CONNECT TOGETHER.
9

OWN-GEN 01/12
TABLE 2 (CONTINUED)
NMEA
2000®Terminal
Detail Terminal
Location Wire Size
(AWG) Current
Max. Function
NET-H 1 22 7mA NMEA2000®Data High
NET-S 2 22 7mA NMEA2000®Bus Power +
NET-L 3 22 7mA NMEA2000®Data Low
NET-C 4 22 7mA NMEA2000®Bus Ground
10
The current transformers (CTs) negative leads must be terminated individually into the
WaveNet AC Current connector. Do not tie the negative leads together to a common ...
neutral or ground. The negative lead of the CT is usually black.
WaveNet is connected on a NMEA 2000 network. Installation must be made by an NMEA
2000 certified technician.
4.1 POWER-UP
4.2 CONTROLLER ALARMING
If the emergency stop input of the digital input terminal is not connected to ground the controller will
alarm and display “Emergency Stop” when powered. Emergency Stop also forces the controller to the
OFF mode.
To prevent this ground the emergency stop input (pin 9) to ground (pin 12) on the digital input
terminal. See Figure 1 on page 6.
T
he controller will display the firmware and hardware version on the screen and flash the indicator lamps
on the side of the controller.
The controller will then enter the OFF mode. By default, it is possible to manually start the generator in
the OFF mode. The user can disable manual start in OFF mode in the basic menu (in which case the
WaveNet must be in the AUTO mode to manually start the generator). See section 4.7.2 on page 15.
Pressing the Info key will cause the controller to enter the AUTO mode. From this mode, the user
can put the controller into RUN mode (i.e. start the generator) manually or from a WaveNet Remote
Panel.
The controller has the ability to remember whether it was in the OFF or AUTO mode the last time it
was powered up and will reenter that mode when it is repowered.
3.3.1 CURRENT TRANSFORMER (CT) WIRING NOTE
4 WAVENET OPERATION & BASIC USER CONFIGURATION
updated 1-17-12

OWN-GEN 01/12
The WaveNet incorporates 3 primary modes of operation:
1. OFF Mode
2. AUTO Mode
3. RUN Mode
1. OFF Mode – When the WaveNet
is set to the OFF mode, automatic
starting will be disabled. No automatic
controls will be initiated. The OFF
mode may be initiated when no
generator controls are required or
when the controller configuration
requires adjustment by pressing the
Stop button. The user can disable
manual start in OFF mode in the basic
menu. See section 4.7.2 on page 15.
All of the failures and most of the warnings are disabled when the controller is in the OFF mode.
The controller will beep every few seconds to alert the user that the unit is in the OFF mode and
cannot automatically start. To silence this alarm, press the Stop key.
In OFF mode, you may simultaneously press the Up and Down arrow keys to perform a lamp
test.
2.AUTO Mode - When the WaveNet is set
to theAUTO mode by pressing the Info key,
automatic starting will be enabled.
If the
engine is started,
failures will be automatically
detected allowing for safe engine operation.
While in AUTO mode the controller will
display engine temperature, battery
voltage and engine hours.
4.3 CONTROLLER STATES
11

OWN-GEN 01/12
When in the RUN mode the WaveNet LCD screen can be locked to display a particular parameter
group. To do this press the Up and Down keys to scroll to the parameter group you wish to view
and then press the Enter key to lock the screen. You will see a lock symbol displayed on the top
right hand side of the display just under the date and time.
To unlock the screen press Enter again or use the arrow keys to scroll to a different parameter
group which causes the lock symbol to disappear. The screen will automatically unlock after 10
minutes.
4.3 CONTROLLER STATES (CONT’D)
4.3.1 LOCKING THE WAVENET SCREEN WHILE IN RUN MODE
There are two ways to start the generator (start conditions):
1. Start key – Located on the WaveNet front panel.
2. Remote WaveNet panel Start key
12
3. RUN Mode – The controller starts the engine/generator and enters the RUN mode
when it receives the command from a WaveNet Remote Panel or the user manually
starts the engine/generator by pressing the Start key.
The controller will automatically shut the
engine/generator down and re-enter the
auto mode if it initiated an engine/
generator start. When the controller is in
the OFF mode automatic starting is
disabled.
When the controller is in the RUN mode,
generator parameters will be displayed on
the screen to allow the user to monitor the
engine status. These include engine speed, generator voltage and current, and
engine temperature as well as others. The parameters are displayed in groups and the
screen scrolls between the various groups. The Page Roll Display menu option
controls how long each parameter group is displayed on the screen before moving on to
the next group. See Table 5 on page 15 for more information.
4.4 WAVENET START / STOP BEHAVIOR

OWN-GEN 01/12
4.4 WAVENET START / STOP BEHAVIOR (CONT’D)
When the controller is in the AUTO mode the two manual start conditions above can be used to
start the generator. When the controller is in the RUN mode it will display the reason for start on
the screen (NMEA 2000 Run, Manual Run).
Stopping the Generator
The Stop key on the front panel can be used to place the WaveNet in OFF regardless of the start
condition.
13
4.5 CONTROLLER SLEEP
The controller has a low power sleep mode that it can enter when in the OFF or AUTO states. In
this state the LCD screen backlighting is turned off. The time it takes to enter the sleep mode is
configurable in the menu. It is recommended that the Sleep Delay is set as short as possible to
prolong the life of the backlighting and to reduce battery consumption.
The backlight display will illuminate automatically when a key is pressed. A key press will only
cause the controller to exit the sleep mode. The key must be pressed again to perform its normal
function.
The WaveNet incorporates a menu system to allow the end user to adjust basic settings.
Each menu has a “Back” selection. To go back to the previous menu scroll up to the Back selection
and press the Enter key. When in the basic menu you can go back to the OFF mode by pressing
the Stop key.
In the OFF state press Enter to access the
WaveNet menu system. This is called the
Basic Menu. The following keys perform the
menu navigation:
1. Scroll up using the Up key
2. Scroll down using the Down key
3. Enter menus by pressing the Enter key.
4.6 WAVENET MENU SYSTEM OPERATION

OWN-GEN 01/12
When you press the Enter key in the OFF mode you will enter the Basic Menu which includes the
Clock Setup, Basic Setup, Advanced Setup, and Failure History submenus.
1. Clock Setup
2. Basic Setup
3. Advanced Setup
4. Failure History
Table 3: Basic Menu Layout
Basic Menu: Clock Setup Year, Month, Date, Day, Hour, Minute, 12/24
Basic Setup
Contrast Adj, Page Roll Delay, State Roll Delay, Sleep
Delay, Maintenance, Not In Auto, Off Mode Start
Failure History
14
The Clock Setup menu will allow you to set the clock. The clock is important if you are planning to
use the Event Log (records all failures and warnings and when they occurred).
4.7 BASIC MENU
4.7.1 CLOCK SETUP
The WaveNet internal clock information can remain “in memory” for approximately 2 weeks
when no DC power is supplied to the controller. Two week memory storage is available in a
completely charged controller clock. DC power is required to be supplied continually to the
WaveNet for approximately 1 hour to allow a complete clock charge.
Table 4 – Clock Setup Menu
Menu SELECTION AND RANGE
Year 2000-2099
Month January - December
Date 01-31
Day Monday - Sunday
Hour 00 - 23
Minute 00 - 59
12/24 12 Hours - 24 Hours

OWN-GEN 01/12
The Basic Setup menu will allow the user to customize the basic features of the WaveNet to their
preference.
The Contrast Adjustment allows the user to adjust the contrast of the LCD.
The Page Roll Delay controls how long each group of parameters are displayed in the RUN state
(i.e. when the engine/generator is running) before displaying the next set of parameters.
The second line of the WaveNet LCD screen is usually dedicated to displaying warnings,
and events. The State Roll Delay determines how long the warning or event message is
displayed before moving on to the next message.
Setting the State Roll Delay to a larger value may cause some warning or event
messages to not be displayed if the event or warning is of a short duration.
The Sleep Delay determines how long to wait after the last key press before turning off the LCD
backlighting.
The Sleep Delay also controls the automatic exit from the menu system. First the control-
ler exits
to the Basic Menu after the first sleep delay, exits to the OFF state after the second sleep
delay, and finally goes into sleep mode after the third sleep delay. The Sleep Delay does not work
in the RUN Mode or during cranking.
The controller can be made to NOT sound the alarm when the controller is not in theAUTO mode.
This is controlled by the Not In Auto setting.
The OFF Mode Start setting can be set to Enable to allow a manual start from the OFF mode.
Otherwise a manual run can only be performed when the controller is in the AUTO mode.
4.7.2 BASIC SETUP
15
Table 5 – Basic Setup Menu
Menu SELECTION AND RANGE
Contrast Adjust 5-95 %
Page Roll Delay 1-10 s
State Roll Delay 1-10 (1 is shortest delay, 10 is longest)
Sleep Delay 10-600s. Shorter is ideal to extend the backlighting life.
Maintenance
Read only. Displays the amount of hours until next service if this
feature is enabled. If service is overdue the hours become negative.
Not In Auto Disable Beep, Enable Beep
OFF Mode Start Disable, Enable

OWN-GEN 01/12
The WaveNet incorporates an event history logging
system. When engine failures or events occur, an
entry is created in the WaveNet Event History Log.
See Table 6 – Event Log Entries below for the possible
events that are stored.
A total of 70 entries can be recorded. Entries may be viewed simply by scrolling up or down using
the Up and Down keys. In addition to the entry reason information, the associated date and time of
the entry will be displayed.
The 70 entries are subdivided into a maximum of 30 events and 40 failures. This prevents one
type from flushing the other types from the log.
Simply scroll through the Failure History Log by
pressing the Up or Down arrow keys located on
the WaveNet.
The event history log can store up to 30 event and 40 failures entries. If these are
exceeded the oldest entry is replaced with the newest entry. The events and failures are
displayed together in the log in reverse chronological order (i.e. newest entry first).
16
4.7.3 EVENT HISTORY LOG
Table 6: Event Log Entries
An “*” beside the Event Entry indicates the Event is a WaveNet event. All other events are failures. (See page section 4.10 on page 19)
Event Entry Description
ADC SWITCH FAILURE These are internal WaveNet failures. Try power cycle the
WaveNet. If failure occurs repeatedly the unit could be defective.
ADE READ FAILURE
ADE WRITE FAIL
AUTO ENABLE * Info button on the front face of controller pressed. WaveNet
placed in AUTO mode.
AUXILIARY FAIL The Auxiliary Fail digital input has been triggered.
EEPROM FAILURE
This is an internal WaveNet failure. Try to power cycle the
WaveNet. If the failure occurs repeatedly the unit could be defective.
EMERGENCY STOP The emergency stop input (located on the digital input terminal)
has been activated.
EPS LOADS ERROR AC current sensing indicating that the generator is not running.
This could indicate something is wrong with the WaveNet.
(See section 4.11 on page 20.)
HIGH BATTERY Failure occurred due to high battery voltage.
HIGH ENGINE TEMP Failure occurred due to high engine coolant temperature.
EVENT LOG ENTRIES

OWN-GEN 01/12
EVENT LOG ENTRIES
17
Event Entry Description
INITIALIZING *
EEPROM is being loaded with factory defaults. This occurs on first
power up.
KEY BOARD FAILURE This is an internal WaveNet failure. Try to power cycle the
WaveNet. If failure occurs repeatedly, the unit could be defective.
LOCKED ROTOR Cranking attempt failed on locked motor.
LOSS OF ECM COMM NMEA2000 messages required by the WaveNet have not been
received. The generator has shut down.
LOW BATTERY Low battery voltage failure.
LOW COOLANT (LEVEL) Low coolant level failure.
LOW OIL PRESSURE Low oil pressure failure.
MANUAL START * Generator started manually from the front panel Start key
MANUAL STOP * Generator stopped manually from the front panel Stop button
OFF ENABLE * Front panel Stop key pressed to disable automatic starting.
OPEN ENG TEMP
Analog sender always reads the maximum voltage. Could indicate
that the sender is not connected to the analog input. (i.e. broken wire)
OPEN ENGINE TEMP
OPEN OIL PRES
OVER CRANK The engine did not start after multiple attempts.
OVER CURRENT Over current failure.
OVER FREQUENCY Generator frequency over the failure threshold.
OVER SPEED Generator RPM too high.
OVER VOLTAGE Generator voltage high.
POWER ON * WaveNet was powered up from unpowered state.
SHORT ENG TEMP Analog sender reads zero volts or close to zero. This could be
caused by a shorted sender.
SHORT ENGINE TEMP
SHORT OIL PRES
TLE6230 FAILURE These are internal WaveNet failures. Try power cycle int WaveNet.
If the failure occurs repeatedly the unit could be defective.
UNDER FREQUENCY The generator frequency is too low.
UNDER SPEED The engine speed is too low.
UNDER VOLTAGE
The generator voltage is too low.

OWN-GEN 01/12
Some industry standard failures, warnings, and events
on the WaveNet are indicated by a series of LEDs on the
left side of the controller.
Specific LED indicators will be illuminated depending
upon the condition of the controller. The WaveNet LED
indicators allow a quick check of the controller’s condition.
The WaveNet displays multi color LED’s for specific
condition representation.
Red
- Represents Failure Conditions
Yellow
- Represents Warning Conditions
Green
- Represents Normal/Active Conditions
An LED test may be performed by the
user for illumination of all controller
LED’s. The LED test may be per-
formed
by simultaneously pressing
the Up key and the Down key on the
WaveNet.
4.8 WAVENET LED STATUS INDICATORS
Table 7: WaveNet Lamp Indication Meanings
LED
Description LED color LED Status Indication
Over Crank Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents an Over Crank
condition on the final crank attempt. This is a Failure.
A solid yellow illuminated LED represents an Over
Crank Warning condition when there are crank attempts
still remaining.
High Engine
Temp Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents a High engine
Temp Failure condition
A solid yellow illuminated LED represents a High engine
Temp Warning Condition
Low Oil
Press Red
Yellow
Solid Red
Solid Yellow
A solid red illuminated LED represents a Low Oil
Pressure Failure condition.
A solid yellow illuminated LED represents a Low Oil
Pressure Warning condition.
18
4.9 LAMP INDICATION MEANINGS
This manual suits for next models
1
Table of contents
Other Northern Lights Controllers manuals